Changing units to infiltration per area. Before it was at 75 Pa, Energyplus requires it at 4 Pa
This commit is contained in:
parent
2495046c44
commit
4654b2d88c
|
@ -466,7 +466,7 @@ class Idf:
|
|||
|
||||
def _add_infiltration_surface(self, thermal_zone, zone_name):
|
||||
schedule = f'INF_CONST schedules {thermal_zone.usage_name}'
|
||||
_infiltration = thermal_zone.infiltration_rate_area_system_off*1
|
||||
_infiltration = thermal_zone.infiltration_rate_area_system_off*cte.INFILTRATION_75PA_TO_4PA
|
||||
self._idf.newidfobject(self._INFILTRATION,
|
||||
Name=f'{zone_name}_infiltration',
|
||||
Zone_or_ZoneList_or_Space_or_SpaceList_Name=zone_name,
|
||||
|
|
|
@ -24,6 +24,7 @@ BTU_H_TO_WATTS = 0.29307107
|
|||
KILO_WATTS_HOUR_TO_JULES = 3600000
|
||||
WATTS_HOUR_TO_JULES = 3600
|
||||
GALLONS_TO_QUBIC_METERS = 0.0037854117954011185
|
||||
INFILTRATION_75PA_TO_4PA = (4/75)**0.65
|
||||
|
||||
|
||||
# time
|
||||
|
|
Loading…