!The DOE Prototype Building Models were developed by Pacific Northwest National Laboratory (PNNL), under contract with the U.S. !Department of Energy (DOE). These building models were derived from DOE's Commercial Reference Building Models with modifications !based on input from the ASHRAE Standard 90.1 committee, the Advanced Energy Design Guide series, and building industry experts. The !prototypes models were developed to quantify energy saving impacts from newly published editions of ASHRAE Standard 90.1, 189.1, IECC, !and other energy codes and standards. The basic building descriptions can be found in the Scorecards posted at www.energycodes.gov !website. The recommended citation of the prototype models is ! !DOE and PNNL. 2020. Commercial Prototype Building Models, Richland, WA, Pacific Northwest National Laboratory. Available at https://www.energycodes.gov/development/commercial/prototype_models. ! !Detailed descriptions of the prototype model development and addenda modeling strategies can be found in the following reports: !DOE, 2020. Preliminary Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2019. Report prepared by Zhang, J., M. Rosenberg, J. !Lerond, Y. Xie, Nambia, C., Y. Chen, R. Hart, M. Halverson, D. Maddox, and S. Goel, Richland, WA, Pacific Northwest National Laboratory. ! !Zhang, J., Y. Chen, Y. Xie, M. Rosenberg, R. Hart. Energy and Energy Cost Savings Analysis of the 2018 IECC for Commercial Buildings. !2018. PNNL-28125. Richland, WA: Pacific Northwest National Laboratory. ! !DOE. 2017. Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2016. Prepared by Athalye, R.A, M.A. Halverson, M.I. Rosenberg, B. Liu, !J. Zhang, R. Hart, V.V. Mendon, S. Goel, Y. Chen, Y. Xie, and M. Zhao, Richland, WA, Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/02202018_Standard_90.1-2016_Determination_TSD.pdf. ! !Zhang, J., Y. Xie, R.A. Athalye, J. Zhuge, M. Rosenberg, R. Hart, and B. Liu. Energy and Energy Cost Savings Analysis of the 2015 IECC !for Commercial Buildings. 2015. PNNL-24269 Rev. 1. Richland, WA: Pacific Northwest National !Laboratory. https://www.energycodes.gov/sites/default/files/documents/2015_IECC_Commercial_Analysis.pdf. ! !Halverson M.A., M.I. Rosenberg, W. Wang, J. Zhang, V.V. Mendon, R.A. Athalye, Y. Xie, R. Hart, S. Goel, 2014. ANSI/ASHRAE/IES Standard !90.1-2013 Determination of Energy Savings: Quantitative Analysis, PNNL-23479. Richland, WA: Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/901-2013_finalCommercialDeterminationQuantitativeAnalysis_TSD_0.pdf. ! !Goel S., R.A. Athalye, W. Wang, J. Zhang, M.I. Rosenberg, Y. Xie, and R. Hart, et al. 2014. Enhancements to ASHRAE Standard 90.1 !Prototype Building Models. PNNL-23269. Richland, WA: Pacific Northwest National Laboratory. https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-23269.pdf. ! !Zhang J., R.A. Athalye, R. Hart, M.I. Rosenberg, Y. Xie, S. Goel, and V.V. Mendon, et al. 2013. Energy and Energy Cost Savings Analysis !of the IECC for Commercial Buildings. PNNL-22760. Richland, WA: Pacific Northwest National Laboratory. http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-22760.pdf. ! !Thornton B.A., M.I. Rosenberg, E.E. Richman, W. Wang, Y. Xie, J. Zhang, H. Cho, VV Mendon, R.A. Athalye, and B. Liu. 2011. Achieving !the 30% Goal: Energy and Cost Savings Analysis of ASHRAE Standard 90.1-2010. PNNL-20405. Richland, WA: Pacific Northwest National !Laboratory. https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf. ! ! ! WeatherFile: USA_MN_Rochester.Intl.AP.726440_TMY3.epw ! BEGIN ECONOMIZER MAP ! Economizer Name, DX COIL Name ! PSZ-Office OA Controller, PSZ-OFFICE COOLING COIL ! PSZ-Fine Storage OA Controller, PSZ-Fine Storage Cooling Coil ! END ECONOMIZER MAP ! ! ! BEGIN EMS PROGRAM MAP ! EMS PROGRAM, DX COIL Name ! PSZ-Office, PSZ-OFFICE COOLING COIL ! PSZ-Fine Storage, PSZ-Fine Storage Cooling Coil ! END EMS PROGRAM MAP ! GPARM parameters as input: ! Case = ASHRAE901_Warehouse_STD2019_Rochester ! SelectedCase = ! ground_tempt = National_Warehouse_ASHRAE901_STD2016_Zone6A_semiheated_MN-Rochester-MN.gtp ! avg_oa_tempt_ip = 43.475 ! maxdiff_oa_tempt_ip = 60.3 ! ext_wall_type = MetalBuildingWall ! nonres_ext_wall_ufactor = 0.28391315 ! ext_wall_mass_density = 0 ! roof_type = MetalBuildingRoof ! nonres_roof_ufactor = 0.176026153 ! con_glass_code = ! overhang_to_be_deleted = no ! con_swingdoor_r_ip = 1.428571429 ! semiheated_ext_wall_ufactor = 0.533756722 ! semiheated_roof_ufactor = 0.34069578 ! semi_swingdoor_r_ip = 1.428571429 ! semi_overheaddoor_r_ip = 0.689655172 ! skylights = d_ab ! nonres_skylight = ! semiheated_skylight = ! daylighting_control = d_ab ! sidelighting_control = yes_AY ! fine_storage_dl_ctrl = no ! infil_office_ip = 0.043346154 ! infil_fine_ip = 0.04444186 ! infil_bulk_ip = 4937.76 ! infil_schedule_bulk = Bulk Storage Infil_Base Schedule ! damper_leak_bulk_ip = 2000 ! roof_solar_absorp_tbd = 0.77 ! LPD_office = 6.888902667 ! LPD_fine_storage = 7.427098188 ! LPD_bulk_storage = 3.552090438 ! exterior_lights_watts = 0 ! exterior_lights_watts_a = 113.8 ! exterior_lights_watts_b = 3955 ! light_schedule_fine = Storage Light Schedule ! light_schedule_bulk = Storage Light Schedule ! system_bulk = UnitHeater ! min_oa_sch = OA Damper Always ON Schedule ! econ_control_office = NoEconomizer ! econ_control_fine = NoEconomizer ! skip_economizer_control = No ! fan_tsp_office_ip = 1.108 ! fan_tsp_fine_ip = 2.607 ! cool_cop_office = 3.97037177 ! cool_cop_fine = 3.255048517 ! heat_eff_office = 0.8 ! heat_eff_fine = 0.7925 ! heat_eff_bulk = 0.7925 ! parasitic_gas_load = 0 ! swh_ua_ip = 2.393 ! avg_oa_tempt = 6.375 ! maxdiff_oa_tempt = 33.5 ! con_swingdoor_r = 0.475675676 ! semi_swingdoor_r = 0.475675676 ! semi_overheaddoor_r = 0.488888889 ! fan_tsp_office = 275.892 ! fan_tsp_fine = 649.143 ! swh_ua_TBD = 1.261536954 ! infil_office = 0.000220198 ! infil_fine = 0.000225765 ! infil_bulk = 2.330231241 ! damper_leak_bulk = 0.943841435 ! office_oa_flow_per_area = 0.000431801 ! storage_oa_flow_per_area = 0.000304801 ! door_infil = 0.176508178 ! frac_ofpk = 0.131 ! damper_sch = MinOA_MotorizedDamper_Sched ! economizer_lockout = LockoutWithHeating ! nonres_frame_width = 0 ! nonres_frame_cond = 0 ! nonres_frame = Skylight_Frame_Nonres ! Office_Plug_WD = Office_Plug_WD_ADV ! Office_Plug_WEH = Office_Plug_WEH_ADV ! addendum_cd = 2016AS ! pv_generator = no ! pv_surface_area = 0 ! STD189_overhang = no ! swh_et = 1 ! swh_ua = 0.798542707 ! ext_lgt_sch = Exterior_Lgt_ALWAYS_ON ! SZ_VAV_189_Office = no ! SZ_VAV_189_FineStorage = no ! LTG_SCH_SET = LTG_SET_STD2013 ! Office_Heating_WD = Office Heating WD_NO_OPTIMUM ! Office_Cooling_WD = Office Cooling WD_NO_OPTIMUM ! roof_emissivity = 0.9 ! roof_solar_absorp = 0.77 ! pipe_heat_loss = 481 ! skip_EMSprogram = no ! Wfile_TMY3 = USA_MN_Rochester.Intl.AP.726440_TMY3.epw ! loadProfile = No ! receptacle_ctrl_occ_reduction_frac = 0.959505267 ! receptacle_ctrl_unocc_reduction_frac = 0.818955113 ! CodeName = ASHRAE90.1_STD2019 ! CZ_City_Old = Burlington ! CZ_Label = 6A ! exterior_lights_watts_c = 1004.9 ! Addendum_AH = Yes ! LPD_Ctrl = 0.02 ! con_overheaddoor_r = 0.567741935 ! semiheated_frame_width = 0 ! semiheated_frame_cond = 0 ! semiheated_skylight_frame = Skylight_Frame_Semiheated ! nonres_window_u_factor = 0.34 ! nonres_window_shgc = 0.38 ! nonresLSG = 1 ! nonres_skylight_u_factor = 0.47 ! nonres_skylight_shgc = 0.4 ! nonresskyltLSG = 1 ! semiheated_skylight_u_factor = 0.75 ! semiheated_skylight_shgc = 0.55 ! semihtdskyltLSG = 1 ! AnalysisPurpose = ProgressIndicator ! AnalysisCodeName = ASHRAE901 ! AnalysisCodeYear = 2019 ! AnalysisAmendment = NoneAmend ! AnalysisPrototype = Warehouse ! AnalysisScope = National ! AnalysisState = National ! AnalysisClimateZone = 6A ! AnalysisCity = USA_MN_Rochester ! var_Ffactor_IP = 0.73 ! VT_Elec_Wheater = No ! specify overhang_pf for 1891 codes !- =========== ALL OBJECTS IN CLASS: VERSION =========== Version,9.0; !- =========== ALL OBJECTS IN CLASS: BUILDING =========== Building, Warehouse, !- Name 90, !- North Axis {deg} Urban, !- Terrain 0.04, !- Loads Convergence Tolerance Value 0.4, !- Temperature Convergence Tolerance Value {deltaC} FullExterior, !- Solar Distribution 25, !- Maximum Number of Warmup Days 6; !- Minimum Number of Warmup Days !- =========== ALL OBJECTS IN CLASS: TIMESTEP IN HOUR =========== Timestep,6; ConvergenceLimits, 1, !- Minimum System Timestep {minutes} 20; !- Maximum HVAC Iterations !- =========== ALL OBJECTS IN CLASS: INSIDE CONVECTION ALGORITHM =========== SurfaceConvectionAlgorithm:Inside,TARP; !- =========== ALL OBJECTS IN CLASS: OUTSIDE CONVECTION ALGORITHM =========== SurfaceConvectionAlgorithm:Outside,TARP; !- =========== ALL OBJECTS IN CLASS: SOLUTION ALGORITHM =========== HeatBalanceAlgorithm,ConductionTransferFunction; !- =========== ALL OBJECTS IN CLASS: RUN CONTROL =========== SimulationControl, Yes, !- Do Zone Sizing Calculation Yes, !- Do System Sizing Calculation Yes, !- Do Plant Sizing Calculation No, !- Run Simulation for Sizing Periods YES; !- Run Simulation for Weather File Run Periods !- =========== ALL OBJECTS IN CLASS: RUNPERIOD =========== RunPeriod, , !- Name 1, !- Begin Month 1, !- Begin Day of Month , !- Begin Year 12, !- End Month 31, !- End Day of Month , !- End Year Sunday, !- Day of Week for Start Day No, !- Use Weather File Holidays and Special Days No, !- Use Weather File Daylight Saving Period No, !- Apply Weekend Holiday Rule Yes, !- Use Weather File Rain Indicators Yes; !- Use Weather File Snow Indicators !- =========== ALL OBJECTS IN CLASS: SPECIALDAYPERIOD =========== RunPeriodControl:SpecialDays, New Years Day, !- Name 01/01, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, ML King Birthday, !- Name 3rd Monday in January, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Washington's Birthday, !- Name 3rd Monday in February, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Memorial Day, !- Name Last Monday in May, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Fourth of July, !- Name 07/04, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Labor Day, !- Name 1st Monday in September, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Columbus Day, !- Name 2nd Monday in October, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Veterans Day, !- Name 11/11, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Thanksgiving Day, !- Name 4th Thursday in November,!- Start Date 1, !- Duration {days} Holiday; !- Special Day Type RunPeriodControl:SpecialDays, Christmas Day, !- Name 12/25, !- Start Date 1, !- Duration {days} Holiday; !- Special Day Type !- =========== ALL OBJECTS IN CLASS: DAYLIGHTSAVINGPERIOD =========== RunPeriodControl:DaylightSavingTime, 2nd Sunday in March, !- Start Date 1st Sunday in November; !- End Date !- =========== ALL OBJECTS IN CLASS: LOCATION =========== ! Site:Location and design-day objects created by: ! ../../_p.bin/ddy2idf /projects/bigsim/weather/EnergyPlus/tmy3.new/all/USA_MN_Rochester.Intl.AP.726440_TMY3.ddy ! Site:Location, Rochester International Arpt_MN_USA Design_Conditions, !- Site:Location Name 43.90, !- Latitude {N+ S-} -92.50, !- Longitude {W- E+} -6.00, !- Time Zone Relative to GMT {GMT+/-} 398.00; !- Elevation {m} SizingPeriod:DesignDay, Rochester International Arpt Ann Htg 99.6% Condns DB, !- Name 1, !- Month 21, !- Day of Month WinterDesignDay,!- Day Type -26.2, !- Maximum Dry-Bulb Temperature {C} 0.0, !- Daily Dry-Bulb Temperature Range {C} DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type , !- Dry-Bulb Temperature Range Modifier Schedule Name Wetbulb, !- Humidity Condition Type -26.2, !- Wetbulb at Maximum Dry-Bulb {C} , !- Humidity Indicating Day Schedule Name , !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir} , !- Enthalpy at Maximum Dry-Bulb {J/kg} , !- Daily WetBulb Temperature Range {deltaC} 96634., !- Barometric Pressure {Pa} 5.7, !- Wind Speed {m/s} design conditions vs. traditional 6.71 m/s (15 mph) 310, !- Wind Direction {Degrees; N=0, S=180} No, !- Rain {Yes/No} No, !- Snow on ground {Yes/No} No, !- Daylight Savings Time Indicator ASHRAEClearSky, !- Solar Model Indicator , !- Beam Solar Day Schedule Name , !- Diffuse Solar Day Schedule Name , !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub) , !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud) 0.00; !- Clearness {0.0 to 1.1} SizingPeriod:DesignDay, Rochester International Arpt Ann Clg .4% Condns DB=>MWB, !- Name 7, !- Month 21, !- Day of Month SummerDesignDay,!- Day Type 31.2, !- Maximum Dry-Bulb Temperature {C} 10.6, !- Daily Dry-Bulb Temperature Range {C} DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type , !- Dry-Bulb Temperature Range Modifier Schedule Name Wetbulb, !- Humidity Condition Type 23.1, !- Wetbulb at Maximum Dry-Bulb {C} , !- Humidity Indicating Day Schedule Name , !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir} , !- Enthalpy at Maximum Dry-Bulb {J/kg} , !- Daily WetBulb Temperature Range {deltaC} 96634., !- Barometric Pressure {Pa} 6.7, !- Wind Speed {m/s} design conditions vs. traditional 3.35 m/s (7mph) 200, !- Wind Direction {Degrees; N=0, S=180} No, !- Rain {Yes/No} No, !- Snow on ground {Yes/No} No, !- Daylight Savings Time Indicator ASHRAETau, !- Solar Model Indicator , !- Beam Solar Day Schedule Name , !- Diffuse Solar Day Schedule Name 0.404, !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub) 2.226; !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud) !- =========== ALL OBJECTS IN CLASS: WATER MAINS TEMPERATURES =========== Site:WaterMainsTemperature, Correlation, !- Calculation Method , !- Temperature Schedule Name 6.375, !- Annual average outdoor air temperature {C} 33.5; !- Maximum difference in monthly average outdoor air temperatures {C} !- =========== ALL OBJECTS IN CLASS: Site:GroundTemperature:FCfactorMethod =========== Site:GroundTemperature:FCfactorMethod, 7.4, !- January Ground Temperature {C} -0.0, !- February Ground Temperature {C} -7.6, !- March Ground Temperature {C} -12.6, !- April Ground Temperature {C} -7.7, !- May Ground Temperature {C} 0.3, !- June Ground Temperature {C} 7.0, !- July Ground Temperature {C} 14.2, !- August Ground Temperature {C} 19.2, !- September Ground Temperature {C} 20.9, !- October Ground Temperature {C} 20.0, !- November Ground Temperature {C} 15.4; !- December Ground Temperature {C} !- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR =========== Material, Gypsum or plaster board - 9.5mm, !- Name MediumSmooth, !- Roughness 0.0095, !- Thickness {m} 0.58, !- Conductivity {W/m-K} 800, !- Density {kg/m3} 1090, !- Specific Heat {J/kg-K} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material, Bulk Storage Products Material, !- Name Rough, !- Roughness 2.43840494296412, !- Thickness {m} 1.44200004455643, !- Conductivity {W/m-K} 200.230661511125, !- Density {kg/m3} 836.800006332062, !- Specific Heat {J/kg-K} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material, Steel Frame/Cavity, !- Name MediumRough, !- Roughness 8.89001802122336E-02, !- Thickness {m} 8.41161885991101E-02, !- Conductivity {W/m-K} 641.378854952435, !- Density {kg/m3} 502.080003799237, !- Specific Heat {J/kg-K} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material, Interior Wall Addi Insul,!- Name MediumRough, !- Roughness 2.54000514892096E-08, !- Thickness {m} 4.32600013366928E-02, !- Conductivity {W/m-K} 22.425834089246, !- Density {kg/m3} 836.800006332062, !- Specific Heat {J/kg-K} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance !- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR-R =========== Material:NoMass, R13_Insulation, !- Name Rough, !- Roughness 2.28800006982422, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Opaque Door panel_con, !- Name MediumRough, !- Roughness 0.475675676, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Opaque Door panel_semi, !- Name MediumRough, !- Roughness 0.475675676, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Overhead Door_semi Panel,!- Name MediumRough, !- Roughness 0.488888889, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Overhead Door_con Panel, !- Name MediumRough, !- Roughness 0.567741935, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance !- =========== ALL OBJECTS IN CLASS: CONSTRUCTION =========== ! !- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR =========== Material, Std Wood 6inch, !- Name MediumSmooth, !- Roughness 0.15, !- Thickness {m} 0.12, !- Conductivity {W/m-K} 540.0000, !- Density {kg/m3} 1210, !- Specific Heat {J/kg-K} 0.9000000, !- Thermal Absorptance 0.7000000, !- Solar Absorptance 0.7000000; !- Visible Absorptance Material, AC02 Acoustic Ceiling, !- Name MediumSmooth, !- Roughness 1.2700000E-02, !- Thickness {m} 5.7000000E-02, !- Conductivity {W/m-K} 288.0000, !- Density {kg/m3} 1339.000, !- Specific Heat {J/kg-K} 0.9000000, !- Thermal Absorptance 0.7000000, !- Solar Absorptance 0.2000000; !- Visible Absorptance Material, F07 25mm stucco, !- Name Smooth, !- Roughness 0.0254, !- Thickness {m} 0.72, !- Conductivity {W/m-K} 1856, !- Density {kg/m3} 840, !- Specific Heat {J/kg-K} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material, F08 Metal surface, !- Name Smooth, !- Roughness 0.0008, !- Thickness {m} 45.28, !- Conductivity {W/m-K} 7824, !- Density {kg/m3} 500; !- Specific Heat {J/kg-K} Material, F08 Metal roof surface, !- Name Smooth, !- Roughness 0.0008, !- Thickness {m} 45.28, !- Conductivity {W/m-K} 7824, !- Density {kg/m3} 500, !- Specific Heat {J/kg-K} 0.9, !- Absorptance:Thermal 0.77; !- Absorptance:Solar Material, F12 Asphalt shingles, !- Name VeryRough, !- Roughness 0.0032, !- Thickness {m} 0.04, !- Conductivity {W/m-K} 1120, !- Density {kg/m3} 1260, !- Specific Heat {J/kg-K} 0.9, !- Absorptance:Thermal 0.77; !- Absorptance:Solar Material, F13 Built-up roofing, !- Name Rough, !- Roughness 0.0095, !- Thickness {m} 0.16, !- Conductivity {W/m-K} 1120, !- Density {kg/m3} 1460, !- Specific Heat {J/kg-K} 0.9, !- Absorptance:Thermal 0.77; !- Absorptance:Solar Material, G01 13mm gypsum board, !- Name Smooth, !- Roughness 0.0127, !- Thickness {m} 0.1600, !- Conductivity {W/m-K} 800.0000, !- Density {kg/m3} 1090.0000, !- Specific Heat {J/kg-K} 0.9000, !- Absorptance:Thermal 0.7000, !- Absorptance:Solar 0.5000; !- Absorptance:Visible Material, G01 16mm gypsum board, !- Name MediumSmooth, !- Roughness 0.0159, !- Thickness {m} 0.16, !- Conductivity {W/m-K} 800, !- Density {kg/m3} 1090; !- Specific Heat {J/kg-K} Material, G02 16mm plywood, !- Name Smooth, !- Roughness 0.0159, !- Thickness {m} 0.12, !- Conductivity {W/m-K} 544, !- Density {kg/m3} 1210; !- Specific Heat {J/kg-K} Material, M14 150mm heavyweight concrete roof, !- Name MediumRough, !- Roughness 0.1524, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, 100mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B MediumRough, !- Roughness 0.1016, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, 200mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B MediumRough, !- Roughness 0.2032, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, 100mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B MediumRough, !- Roughness 0.1016, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, 150mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B MediumRough, !- Roughness 0.1524, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, 200mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B MediumRough, !- Roughness 0.2032, !- Thickness {m} 2.31, !- Conductivity {W/m-K} 2322, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, M10 200mm concrete block wall, !- Name MediumRough, !- Roughness 0.2032, !- Thickness {m} 0.72, !- Conductivity {W/m-K} 800, !- Density {kg/m3} 832; !- Specific Heat {J/kg-K} Material, M10 200mm concrete block basement wall, !- Name MediumRough, !- Roughness 0.2032, !- Thickness {m} 1.326, !- Conductivity {W/m-K} 1842, !- Density {kg/m3} 912; !- Specific Heat {J/kg-K} Material:NoMass, CP02 CARPET PAD, !- Name VeryRough, !- Roughness 0.21648, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.8; !- Visible Absorptance Material:NoMass, Air_Wall_Material, !- Name Rough, !- Roughness 0.2079491, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7; !- Solar Absorptance Material:NoMass, Nonres_Roof_Insulation, !- Name MediumSmooth, !- Roughness 5.5435903890787, !- Thermal Resistance {m2-K/W} 0.9, !- Absorptance:Thermal 0.7, !- Absorptance:Solar 0.7; !- Absorptance:Visible Material:NoMass, Res_Roof_Insulation, !- Name MediumSmooth, !- Roughness 0.0299387330245182, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Semiheated_Roof_Insulation, !- Name MediumSmooth, !- Roughness 2.79778628499575, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Nonres_Exterior_Wall_Insulation, !- Name MediumSmooth, !- Roughness 3.29313522011485, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Res_Exterior_Wall_Insulation, !- Name MediumSmooth, !- Roughness 0.0299387330245182, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Semiheated_Exterior_Wall_Insulation, !- Name MediumSmooth, !- Roughness 1.64444403979094, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Nonres_Floor_Insulation, !- Name MediumSmooth, !- Roughness 0.0299387330245182, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Res_Floor_Insulation, !- Name MediumSmooth, !- Roughness 0.0299387330245182, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Semiheated_Floor_Insulation, !- Name MediumSmooth, !- Roughness 0.0299387330245182, !- Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance Material:NoMass, Std Opaque Door Panel, !- Name MediumRough, !- Roughness 0.123456790123457, !- (corresponds to default RSI-0.12327 or R-0.7) Thermal Resistance {m2-K/W} 0.9, !- Thermal Absorptance 0.7, !- Solar Absorptance 0.7; !- Visible Absorptance !- =========== ALL OBJECTS IN CLASS: CONSTRUCTION =========== Construction, InteriorFurnishings, !- Name Std Wood 6inch; !- Outside Layer Construction, Air_Wall, !- Name Air_Wall_Material; !- Outside Layer Construction, DropCeiling, !- Name AC02 Acoustic Ceiling; !- Outside Layer Construction, OpaqueDoor, !- Name Std Opaque Door Panel; !- Outside Layer Construction, AtticRoofDeck, !- Name F12 Asphalt shingles, !- Outside Layer G02 16mm plywood; !- Layer 2 Construction, int_wall, !- Name G01 13mm gypsum board, !- Outside Layer G01 13mm gypsum board; !- Layer 2 Construction, ext_slab_8in_with_carpet,!- Name 200mm Normalweight concrete floor, !- Outside Layer CP02 CARPET PAD; !- Layer 2 Construction, ext_slab_8in, !- Name 200mm Normalweight concrete floor; !- Outside Layer Construction, ext_slab_6in_with_carpet,!- Name 150mm Normalweight concrete floor, !- Outside Layer CP02 CARPET PAD; !- Layer 2 Construction, ext_slab_6in, !- Name 150mm Normalweight concrete floor; !- Outside Layer Construction, int_slab_floor, !- Name 100mm Normalweight concrete floor, !- Outside Layer CP02 CARPET PAD; !- Layer 2 Construction, int_slab_ceiling, !- Name CP02 CARPET PAD, !- Outside Layer 100mm Normalweight concrete floor; !- Layer 2 Construction, basement_wall, !- Name M10 200mm concrete block basement wall; !- Outside Layer Construction, int_wood_floor, !- Name AC02 Acoustic Ceiling, !- Outside Layer G02 16mm plywood, !- Layer 2 CP02 CARPET PAD; !- Layer 3 Construction, ext_soffit_floor, !- Name G02 16mm plywood; !- Outside Layer Construction, nonres_roof, !- Name F08 Metal roof surface, !- Outside Layer Nonres_Roof_Insulation; !- Layer #2 Construction, res_roof, !- Name F08 Metal roof surface, !- Outside Layer Res_Roof_Insulation; !- Layer #2 Construction, semiheated_roof, !- Name F08 Metal roof surface, !- Outside Layer Semiheated_Roof_Insulation; !- Layer #2 Construction, nonres_ext_wall, !- Name F08 Metal surface, !- Outside Layer Nonres_Exterior_Wall_Insulation, !- Layer #2 G01 16mm gypsum board; !- Layer #3 Construction, res_ext_wall, !- Name F08 Metal surface, !- Outside Layer Res_Exterior_Wall_Insulation, !- Layer #2 G01 16mm gypsum board; !- Layer #3 Construction, semiheated_ext_wall, !- Name F08 Metal surface, !- Outside Layer Semiheated_Exterior_Wall_Insulation, !- Layer #2 G01 16mm gypsum board; !- Layer #3 Construction, nonres_floor, !- Name Nonres_Floor_Insulation, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 CP02 CARPET PAD; !- Layer #2 Construction, res_floor, !- Name Res_Floor_Insulation, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 CP02 CARPET PAD; !- Layer #2 Construction, semiheated_floor, !- Name Semiheated_Floor_Insulation, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 CP02 CARPET PAD; !- Layer #2 Construction, nonres_floor_ceiling, !- Name - reverse ordered layers for nonres_floor CP02 CARPET PAD, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 Nonres_Floor_Insulation; !- Layer #2 Construction, res_floor_ceiling, !- Name - reverse ordered layers for res_floor CP02 CARPET PAD, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 Res_Floor_Insulation; !- Layer #2 Construction, semiheated_floor_ceiling, !- Name - reverse ordered layers for semiheated_floor CP02 CARPET PAD, !- Outside Layer 100mm Normalweight concrete floor, !- Layer #1 Semiheated_Floor_Insulation; !- Layer #2 !- =========== ALL OBJECTS IN CLASS: WINDOWMATERIAL:SIMPLEGLAZINGSYSTEM =========== WindowMaterial:SimpleGlazingSystem, Nonres Window Glazing Layer, !- Name 1.9306084, !- U-Factor {W/m2-K} 0.38, !- Solar Heat Gain Coefficient 0.38; !- Visible Transmittance WindowMaterial:SimpleGlazingSystem, Nonres Skylight Glazing Layer, !- Name 2.6687822, !- U-Factor {W/m2-K} 0.4, !- Solar Heat Gain Coefficient 0.4; !- Visible Transmittance WindowMaterial:SimpleGlazingSystem, Semiheated Skylight Glazing Layer, !- Name 4.258695, !- U-Factor {W/m2-K} 0.55, !- Solar Heat Gain Coefficient 0.55; !- Visible Transmittance Construction, NonresWindow_U_0.34_SHGC_0.38, !- Name Nonres Window Glazing Layer; !- Outside Layer Construction, Skylight_U_0.47_SHGC_0.4, !- Name Nonres Skylight Glazing Layer; !- Outside Layer Construction, SemiHtdSkylight_U_0.75_SHGC_0.55, !- Name Semiheated Skylight Glazing Layer; !- Outside Layer WindowProperty:FrameAndDivider, Skylight_Frame_Nonres, !- Name 0, !- Frame Width {m} , !- Frame Outside Projection {m} , !- Frame Inside Projection {m} 0, !- Frame Conductance {W/m2-K} 1, !- Ratio of Frame-Edge Glass Conductance to Center-Of-Glass Conductance 0.7, !- Frame Solar Absorptance 0.7, !- Frame Visible Absorptance 0.9, !- Frame Thermal Hemispherical Emissivity , !- Divider Type , !- Divider Width {m} , !- Number of Horizontal Dividers , !- Number of Vertical Dividers , !- Divider Outside Projection {m} , !- Divider Inside Projection {m} , !- Divider Conductance {W/m2-K} 1, !- Ratio of Divider-Edge Glass Conductance to Center-Of-Glass Conductance , !- Divider Solar Absorptance , !- Divider Visible Absorptance 0.9; !- Divider Thermal Hemispherical Emissivity WindowProperty:FrameAndDivider, Skylight_Frame_Semiheated, !- Name 0, !- Frame Width {m} , !- Frame Outside Projection {m} , !- Frame Inside Projection {m} 0, !- Frame Conductance {W/m2-K} 1, !- Ratio of Frame-Edge Glass Conductance to Center-Of-Glass Conductance 0.7, !- Frame Solar Absorptance 0.7, !- Frame Visible Absorptance 0.9, !- Frame Thermal Hemispherical Emissivity , !- Divider Type , !- Divider Width {m} , !- Number of Horizontal Dividers , !- Number of Vertical Dividers , !- Divider Outside Projection {m} , !- Divider Inside Projection {m} , !- Divider Conductance {W/m2-K} 1, !- Ratio of Divider-Edge Glass Conductance to Center-Of-Glass Conductance , !- Divider Solar Absorptance , !- Divider Visible Absorptance 0.9; !- Divider Thermal Hemispherical Emissivity !- =========== ALL OBJECTS IN CLASS: MATERIAL:SKYLIGHT:WINDOWGLASS =========== WindowMaterial:Glazing, REF A CLEAR MID 6MM, !- Name SpectralAverage, !- Optical Data Type , !- Window Glass Spectral Data Set Name 0.006, !- Thickness {m} 0.110, !- Solar Transmittance at Normal Incidence 0.270, !- Front Side Solar Reflectance at Normal Incidence 0.430, !- Back Side Solar Reflectance at Normal Incidence 0.140, !- Visible Transmittance at Normal Incidence 0.310, !- Front Side Visible Reflectance at Normal Incidence 0.350, !- Back Side Visible Reflectance at Normal Incidence 0.0, !- Infrared Transmittance at Normal Incidence 0.84, !- Front Side Infrared Hemispherical Emissivity 0.47, !- Back Side Infrared Hemispherical Emissivity 0.9; !- Conductivity {W/m-K} WindowMaterial:Gas, AIR 3MM, !- Name Air, !- Gas Type 0.0032; !- Thickness {m} WindowMaterial:Glazing, CLEAR 2.5MM, !- Name SpectralAverage, !- Optical Data Type , !- Window Glass Spectral Data Set Name 0.0025, !- Thickness {m} 0.8, !- Solar Transmittance at Normal Incidence 0.075, !- Front Side Solar Reflectance at Normal Incidence 0.075, !- Back Side Solar Reflectance at Normal Incidence 0.901, !- Visible Transmittance at Normal Incidence 0.081, !- Front Side Visible Reflectance at Normal Incidence 0.081, !- Back Side Visible Reflectance at Normal Incidence 0.0, !- Infrared Transmittance at Normal Incidence 0.84, !- Front Side Infrared Hemispherical Emissivity 0.84, !- Back Side Infrared Hemispherical Emissivity 0.9; !- Conductivity {W/m-K} !- =========== ALL OBJECTS IN CLASS: CONSTRUCTION =========== Construction, Interior Wall_1, !- Name Gypsum or plaster board - 9.5mm, !- Outside Layer R13_Insulation, !- Layer 2 Gypsum or plaster board - 9.5mm; !- Layer 3 Construction, Swinging Door_con, !- Name Opaque Door panel_con; !- Outside Layer Construction, Swinging Door_semi, !- Name Opaque Door panel_semi; !- Outside Layer Construction, Skylight Double Clear, !- Name CLEAR 2.5MM, !- Outside Layer AIR 3MM, !- Layer 2 CLEAR 2.5MM; !- Layer 3 Construction, Overhead Door_semi, !- Name Overhead Door_semi Panel;!- Outside Layer Construction, Overhead Door_con, !- Name Overhead Door_con Panel; !- Outside Layer Construction, Bulk Storage Products, !- Name Bulk Storage Products Material; !- Outside Layer Construction, Interior Wall, !- Name F07 25mm stucco, !- Outside Layer G01 16mm gypsum board, !- Layer 2 Interior Wall Addi Insul,!- Layer 3 Steel Frame/Cavity, !- Layer 4 G01 16mm gypsum board; !- Layer 5 Construction, InsulatedCeiling, !- Name Interior Wall Addi Insul,!- Outside Layer G01 16mm gypsum board; !- Layer 2 Construction:FfactorGroundFloor, OfficeFloor_Ffactor, !- Name 1.26363, !- F-Factor 236.87964658059664, !- Area 35.05029062578953; !- PerimeterExposed Construction:FfactorGroundFloor, FineStorageFloor_Ffactor, !- Name 1.26363, !- F-Factor 1156.5300391876226, !- Area 71.62450693096137; !- PerimeterExposed Construction:FfactorGroundFloor, BulkStorageFloor_Ffactor, !- Name 1.26363, !- F-Factor 3204.8422772668932, !- Area 185.91893288462248; !- PerimeterExposed !- =========== ALL OBJECTS IN CLASS: ZONE =========== Zone, Zone1 Office, !- Name 0, !- Direction of Relative North {deg} 0, !- X Origin {m} 0, !- Y Origin {m} 0, !- Z Origin {m} 1, !- Type 1, !- Multiplier autocalculate, !- Ceiling Height {m} autocalculate, !- Volume {m3} autocalculate, !- Floor Area {m2} , !- Zone Inside Convection Algorithm , !- Zone Outside Convection Algorithm Yes; !- Part of Total Floor Area Zone, Zone2 Fine Storage, !- Name 0, !- Direction of Relative North {deg} 0, !- X Origin {m} 0, !- Y Origin {m} 0, !- Z Origin {m} 1, !- Type 1, !- Multiplier autocalculate, !- Ceiling Height {m} autocalculate, !- Volume {m3} autocalculate, !- Floor Area {m2} , !- Zone Inside Convection Algorithm , !- Zone Outside Convection Algorithm Yes; !- Part of Total Floor Area Zone, Zone3 Bulk Storage, !- Name 0, !- Direction of Relative North {deg} 0, !- X Origin {m} 0, !- Y Origin {m} 0, !- Z Origin {m} 1, !- Type 1, !- Multiplier autocalculate, !- Ceiling Height {m} autocalculate, !- Volume {m3} autocalculate, !- Floor Area {m2} , !- Zone Inside Convection Algorithm , !- Zone Outside Convection Algorithm Yes; !- Part of Total Floor Area !- =========== ALL OBJECTS IN CLASS: SURFACEGEOMETRY =========== GlobalGeometryRules, UpperLeftCorner, !- Starting Vertex Position Counterclockwise, !- Vertex Entry Direction Relative; !- Coordinate System !- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER =========== BuildingSurface:Detailed, Office Front Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone1 Office, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,0,4.26699190227003, !- X,Y,Z ==> Vertex 1 {m} 0,0,0, !- X,Y,Z ==> Vertex 2 {m} 25.9067365494966,0,0, !- X,Y,Z ==> Vertex 3 {m} 25.9067365494966,0,4.26699190227003; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Office Right Wall, !- Name Wall, !- Surface Type Interior Wall, !- Construction Name Zone1 Office, !- Zone Name Zone, !- Outside Boundary Condition Zone2 Fine Storage, !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 25.9067365494966,0,4.26699190227003, !- X,Y,Z ==> Vertex 1 {m} 25.9067365494966,0,0, !- X,Y,Z ==> Vertex 2 {m} 25.9067365494966,9.14355407629293,0, !- X,Y,Z ==> Vertex 3 {m} 25.9067365494966,9.14355407629293,4.26699190227003; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Office Rear Wall, !- Name Wall, !- Surface Type Interior Wall, !- Construction Name Zone1 Office, !- Zone Name Zone, !- Outside Boundary Condition Zone2 Fine Storage, !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 25.9067365494966,9.14355407629293,4.26699190227003, !- X,Y,Z ==> Vertex 1 {m} 25.9067365494966,9.14355407629293,0, !- X,Y,Z ==> Vertex 2 {m} 0,9.14355407629293,0, !- X,Y,Z ==> Vertex 3 {m} 0,9.14355407629293,4.26699190227003; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Office Left Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone1 Office, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,9.14355407629293,4.26699190227003, !- X,Y,Z ==> Vertex 1 {m} 0,9.14355407629293,0, !- X,Y,Z ==> Vertex 2 {m} 0,0,0, !- X,Y,Z ==> Vertex 3 {m} 0,0,4.26699190227003; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Front Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 25.9067365494966,0,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 25.9067365494966,0,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,0,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,0,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Right Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,0,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,0,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,30.4785135876431,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,30.4785135876431,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Bulk Storage Front Wall, !- Name Wall, !- Surface Type semiheated_ext_wall, !- Construction Name Zone3 Bulk Storage, !- Zone Name Zone, !- Outside Boundary Condition Zone2 Fine Storage, !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,30.4785135876431,0, !- X,Y,Z ==> Vertex 3 {m} 0,30.4785135876431,0; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Left Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 0,30.4785135876431,0, !- X,Y,Z ==> Vertex 2 {m} 0,9.14355407629293,0, !- X,Y,Z ==> Vertex 3 {m} 0,9.14355407629293,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Bulk Storage Right Wall, !- Name Wall, !- Surface Type semiheated_ext_wall, !- Construction Name Zone3 Bulk Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,30.4785135876431,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,100.579094839222,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,100.579094839222,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Bulk Storage Rear Wall, !- Name Wall, !- Surface Type semiheated_ext_wall, !- Construction Name Zone3 Bulk Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,100.579094839222,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,100.579094839222,0, !- X,Y,Z ==> Vertex 2 {m} 0,100.579094839222,0, !- X,Y,Z ==> Vertex 3 {m} 0,100.579094839222,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Bulk Storage Left Wall, !- Name Wall, !- Surface Type semiheated_ext_wall, !- Construction Name Zone3 Bulk Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,100.579094839222,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 0,100.579094839222,0, !- X,Y,Z ==> Vertex 2 {m} 0,30.4785135876431,0, !- X,Y,Z ==> Vertex 3 {m} 0,30.4785135876431,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Office Roof, !- Name Roof, !- Surface Type InsulatedCeiling, !- Construction Name Zone1 Office, !- Zone Name Zone, !- Outside Boundary Condition Zone2 Fine Storage, !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 25.9067365494966,0,4.26699190227003, !- X,Y,Z ==> Vertex 1 {m} 25.9067365494966,9.14355407629293,4.26699190227003, !- X,Y,Z ==> Vertex 2 {m} 0,9.14355407629293,4.26699190227003, !- X,Y,Z ==> Vertex 3 {m} 0,0,4.26699190227003; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Roof, !- Name Roof, !- Surface Type nonres_roof, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,0,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 2 {m} 0,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 3 {m} 0,0,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Bulk Storage Roof, !- Name Roof, !- Surface Type semiheated_roof, !- Construction Name Zone3 Bulk Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,100.579094839222,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 0,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,30.4785135876431,8.53398380454007, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,100.579094839222,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Office Front Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,0,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 0,0,4.26699190227003, !- X,Y,Z ==> Vertex 2 {m} 25.9067365494966,0,4.26699190227003, !- X,Y,Z ==> Vertex 3 {m} 25.9067365494966,0,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Office Left Wall, !- Name Wall, !- Surface Type nonres_ext_wall, !- Construction Name Zone2 Fine Storage, !- Zone Name Outdoors, !- Outside Boundary Condition , !- Outside Boundary Condition Object SunExposed, !- Sun Exposure WindExposed, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 0,9.14355407629293,8.53398380454007, !- X,Y,Z ==> Vertex 1 {m} 0,9.14355407629293,4.26699190227003, !- X,Y,Z ==> Vertex 2 {m} 0,0,4.26699190227003, !- X,Y,Z ==> Vertex 3 {m} 0,0,8.53398380454007; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Office Floor, !- Name Floor, !- Surface Type OfficeFloor_Ffactor, !- Construction Name Zone1 Office, !- Zone Name GroundFCfactorMethod, !- Outside Boundary Condition , !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 25.9067365494966,9.14355407629293,0, !- X,Y,Z ==> Vertex 1 {m} 25.9067365494966,0,0, !- X,Y,Z ==> Vertex 2 {m} 0,0,0, !- X,Y,Z ==> Vertex 3 {m} 0,9.14355407629293,0; !- X,Y,Z ==> Vertex 4 {m} BuildingSurface:Detailed, Fine Storage Floor, !- Name Floor, !- Surface Type FineStorageFloor_Ffactor, !- Construction Name Zone2 Fine Storage, !- Zone Name GroundFCfactorMethod, !- Outside Boundary Condition , !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,30.4785135876431,0, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,0,0, !- X,Y,Z ==> Vertex 2 {m} 25.9067365494966,0,0, !- X,Y,Z ==> Vertex 3 {m} 25.9067365494966,9.14355407629293,0, !- X,Y,Z ==> Vertex 4 {m} 0,9.14355407629293,0, !- X,Y,Z ==> Vertex 5 {m} 0,30.4785135876431,0; !- X,Y,Z ==> Vertex 6 {m} BuildingSurface:Detailed, Bulk Storage Floor, !- Name Floor, !- Surface Type BulkStorageFloor_Ffactor, !- Construction Name Zone3 Bulk Storage, !- Zone Name GroundFCfactorMethod, !- Outside Boundary Condition , !- Outside Boundary Condition Object NoSun, !- Sun Exposure NoWind, !- Wind Exposure autocalculate, !- View Factor to Ground autocalculate, !- Number of Vertices 45.7177703814647,100.579094839222,0, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,30.4785135876431,0, !- X,Y,Z ==> Vertex 2 {m} 0,30.4785135876431,0, !- X,Y,Z ==> Vertex 3 {m} 0,100.579094839222,0; !- X,Y,Z ==> Vertex 4 {m} !- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:SUB =========== FenestrationSurface:Detailed, Office Front Wall Window 1, !- Name Window, !- Surface Type NonresWindow_U_0.34_SHGC_0.38, !- Construction Name of the Surface Office Front Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 3.65742163051717,0,2.43929602151392, !- X,Y,Z ==> Vertex 1 {m} 3.65742163051717,0,0.914355407629293, !- X,Y,Z ==> Vertex 2 {m} 7.31484326103434,0,0.914355407629293, !- X,Y,Z ==> Vertex 3 {m} 7.31484326103434,0,2.43929602151392; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Office Front Wall Window2, !- Name Window, !- Surface Type NonresWindow_U_0.34_SHGC_0.38, !- Construction Name of the Surface Office Front Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 18.5918932884623,0,2.43929602151392, !- X,Y,Z ==> Vertex 1 {m} 18.5918932884623,0,0.914355407629293, !- X,Y,Z ==> Vertex 2 {m} 22.2493149189795,0,0.914355407629293, !- X,Y,Z ==> Vertex 3 {m} 22.2493149189795,0,2.43929602151392; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Office Front Door, !- Name Door, !- Surface Type Swinging Door_con, !- Construction Name Office Front Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 12.039012867119,0.000000000000,2.133495951135, !- X,Y,Z ==> Vertex 1 {m} 12.039012867119,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 12.953323682378,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 12.953323682378,0.000000000000,2.133495951135; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Office Left Wall Window1,!- Name Window, !- Surface Type NonresWindow_U_0.34_SHGC_0.38, !- Construction Name of the Surface Office Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0,7.51904930207155,2.43929602151392, !- X,Y,Z ==> Vertex 1 {m} 0,7.51904930207155,0.914355407629293, !- X,Y,Z ==> Vertex 2 {m} 0,5.38555335093654,0.914355407629293, !- X,Y,Z ==> Vertex 3 {m} 0,5.38555335093654,2.43929602151392; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Office Left Wall Window2,!- Name Window, !- Surface Type NonresWindow_U_0.34_SHGC_0.38, !- Construction Name of the Surface Office Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0,3.75800072535639,2.43929602151392, !- X,Y,Z ==> Vertex 1 {m} 0,3.75800072535639,0.914355407629293, !- X,Y,Z ==> Vertex 2 {m} 0,1.62450477422138,0.914355407629293, !- X,Y,Z ==> Vertex 3 {m} 0,1.62450477422138,2.43929602151392; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Office Left Wall Door, !- Name Door, !- Surface Type Swinging Door_con, !- Construction Name Office Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0,5.02895474196111,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 0,5.02895474196111,0, !- X,Y,Z ==> Vertex 2 {m} 0,4.11459933433182,0, !- X,Y,Z ==> Vertex 3 {m} 0,4.11459933433182,2.13349595113502; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Overhead Door1, !- Name Door, !- Surface Type Overhead Door_con, !- Construction Name Fine Storage Front Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 33.479659311782,0.000000000000,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 33.479659311782,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 36.527540398794,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 36.527540398794,0.000000000000,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Overhead Door2, !- Name Door, !- Surface Type Overhead Door_con, !- Construction Name Fine Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 45.717770381465,4.941667349700,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,4.941667349700,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,7.989548436712,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,7.989548436712,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Overhead Door3, !- Name Door, !- Surface Type Overhead Door_con, !- Construction Name Fine Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 45.717770381465,23.087474042640,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,23.087474042640,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,26.135355129652,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,26.135355129652,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Overhead Door4, !- Name Door, !- Surface Type Overhead Door_con, !- Construction Name Fine Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 0.000000000000,28.015580613846,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,28.015580613846,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,24.967699526834,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,24.967699526834,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door1, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,93.950018133910,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,93.950018133910,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,90.902137046898,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,90.902137046898,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door2, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,84.882660341586,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,84.882660341586,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,81.834779254575,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,81.834779254575,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door3, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,75.815302549262,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,75.815302549262,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,72.767421462251,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,72.767421462251,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door4, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,66.747944756938,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,66.747944756938,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,63.700063669927,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,63.700063669927,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door5, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,57.680586964615,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,57.680586964615,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,54.632705877603,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,54.632705877603,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door6, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,48.613229172291,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,48.613229172291,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,45.565348085279,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,45.565348085279,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door7, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0.000000000000,39.545871379967,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,39.545871379967,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,36.497990292956,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,36.497990292956,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door8, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 45.717770381465,37.093047145699,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,37.093047145699,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,39.531328232711,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,39.531328232711,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door9, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 45.717770381465,55.273759445851,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,55.273759445851,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,57.712040532863,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,57.712040532863,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door10, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 45.717770381465,73.315058536411,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,73.315058536411,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,75.753339623423,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,75.753339623423,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door11, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 45.717770381465,89.887764572181,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 45.717770381465,89.887764572181,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 45.717770381465,92.326045659193,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 45.717770381465,92.326045659193,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door12, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Rear Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 40.439074862717,100.579094839222,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 40.439074862717,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 37.391193775705,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 37.391193775705,100.579094839222,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door13, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Rear Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 30.771439143478,100.579094839222,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 30.771439143478,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 27.723558056466,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 27.723558056466,100.579094839222,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door14, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Rear Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 16.687766818731,100.579094839222,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 16.687766818731,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 13.639885731719,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 13.639885731719,100.579094839222,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Overhead Door15, !- Name Door, !- Surface Type Overhead Door_semi, !- Construction Name Bulk Storage Rear Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 7.322384518536,100.579094839222,2.438251358764, !- X,Y,Z ==> Vertex 1 {m} 7.322384518536,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 4.274503431524,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 4.274503431524,100.579094839222,2.438251358764; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Door1, !- Name Door, !- Surface Type Swinging Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 45.7177703814647,47.5464811967232,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,47.5464811967232,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,48.4608366043525,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,48.4608366043525,2.13349595113502; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Door2, !- Name Door, !- Surface Type Swinging Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 45.7177703814647,65.071626509618,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,65.071626509618,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,65.9859819172473,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,65.9859819172473,2.13349595113502; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Door3, !- Name Door, !- Surface Type Swinging Door_semi, !- Construction Name Bulk Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 45.7177703814647,82.5967718225128,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,82.5967718225128,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,83.5111272301421,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,83.5111272301421,2.13349595113502; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Door4, !- Name Door, !- Surface Type Swinging Door_semi, !- Construction Name Bulk Storage Rear Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 23.352181134479,100.579094839222,2.133495951135, !- X,Y,Z ==> Vertex 1 {m} 23.352181134479,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 22.437825726850,100.579094839222,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 22.437825726850,100.579094839222,2.133495951135; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Bulk Storage Door5, !- Name Door, !- Surface Type Swinging Door_semi, !- Construction Name Bulk Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground , !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 0.000000000000,70.345058109595,2.133495951135, !- X,Y,Z ==> Vertex 1 {m} 0.000000000000,70.345058109595,0.000000000000, !- X,Y,Z ==> Vertex 2 {m} 0.000000000000,69.430702701966,0.000000000000, !- X,Y,Z ==> Vertex 3 {m} 0.000000000000,69.430702701966,2.133495951135; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Left Door, !- Name Door, !- Surface Type Swinging Door_con, !- Construction Name Fine Storage Left Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 0,19.3538561281534,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 0,20.2682115357827,2.13349595113502, !- X,Y,Z ==> Vertex 2 {m} 0,20.2682115357827,0, !- X,Y,Z ==> Vertex 3 {m} 0,19.3538561281534,0; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Fine Storage Right Door, !- Name Door, !- Surface Type Swinging Door_con, !- Construction Name Fine Storage Right Wall, !- Building Surface Name , !- Outside Boundary Condition Object autocalculate, !- View Factor to Ground , !- Frame and Divider Name 1, !- Multiplier 4, !- Number of Vertices 45.7177703814647,14.7820790900069,2.13349595113502, !- X,Y,Z ==> Vertex 1 {m} 45.7177703814647,14.7820790900069,0, !- X,Y,Z ==> Vertex 2 {m} 45.7177703814647,15.6964344976362,0, !- X,Y,Z ==> Vertex 3 {m} 45.7177703814647,15.6964344976362,2.13349595113502; !- X,Y,Z ==> Vertex 4 {m} !- =========== ALL OBJECTS FOR DAYLIGHTING =========== FenestrationSurface:Detailed, Skylight_R1C1, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 3.657600,34.136114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 2.438400,34.136114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 2.438400,32.916914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 3.657600,32.916914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R1C2, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 3.657600,40.232114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 2.438400,40.232114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 2.438400,39.012914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 3.657600,39.012914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R1C3, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 3.657600,46.328114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 2.438400,46.328114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 2.438400,45.108914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 3.657600,45.108914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R1C4, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 3.657600,52.424114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 2.438400,52.424114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 2.438400,51.204914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 3.657600,51.204914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R1C5, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 3.657600,58.520114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 2.438400,58.520114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 2.438400,57.300914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 3.657600,57.300914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R2C1, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 9.753600,34.136114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 8.534400,34.136114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 8.534400,32.916914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 9.753600,32.916914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R2C2, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 9.753600,40.232114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 8.534400,40.232114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 8.534400,39.012914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 9.753600,39.012914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R2C3, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 9.753600,46.328114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 8.534400,46.328114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 8.534400,45.108914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 9.753600,45.108914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R2C4, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 9.753600,52.424114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 8.534400,52.424114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 8.534400,51.204914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 9.753600,51.204914,8.533984; !- X,Y,Z ==> Vertex 4 {m} FenestrationSurface:Detailed, Skylight_R2C5, !- Name Window, !- Surface Type SemiHtdSkylight_U_0.75_SHGC_0.55, !- Construction Name Bulk Storage Roof, !- Building Surface Name , !- Outside Boundary Condition Object , !- View Factor to Ground Skylight_Frame_Semiheated, !- Frame and Divider Name , !- Multiplier 4, !- Number of Vertices 9.753600,58.520114,8.533984, !- X,Y,Z ==> Vertex 1 {m} 8.534400,58.520114,8.533984, !- X,Y,Z ==> Vertex 2 {m} 8.534400,57.300914,8.533984, !- X,Y,Z ==> Vertex 3 {m} 9.753600,57.300914,8.533984; !- X,Y,Z ==> Vertex 4 {m} !No skylights in fine storage !No Daylighting Control for fine storage !- =========== ALL OBJECTS IN CLASS: DAYLIGHTING:DETAILED =========== Daylighting:Controls, Zone3 Bulk Storage_DaylCtrl, !- Name Zone3 Bulk Storage, !- Zone Name SplitFlux, !- Daylighting Method , !- Availability Schedule Name Continuousoff, !- Lighting Control Type 0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control 0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control 3, !- Number of Stepped Control Steps 1, !- Probability Lighting will be Reset When Needed in Manual Stepped Control Zone3 Bulk Storage_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name 0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg} 22, !- Maximum Allowable Discomfort Glare Index , !- DElight Gridding Resolution {m2} Zone3 Bulk Storage_DaylRefPt1, !- Daylighting Reference Point 1 Name 0.116, !- Fraction of Zone Controlled by Reference Point 1 215; !- Illuminance Setpoint at Reference Point 1 {lux} Daylighting:ReferencePoint, Zone3 Bulk Storage_DaylRefPt1, !- Name Zone3 Bulk Storage, !- Zone Name 6.096, !- X-Coordinate of Reference Point {m} 45.718514, !- Y-Coordinate of Reference Point {m} 0; !- Z-Coordinate of Reference Point {m} !- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:INTERNALMASS =========== InternalMass, Bulk Storage Products Surface, !- Name Bulk Storage Products, !- Construction Name Zone3 Bulk Storage, !- Zone Name 6028.44715712782; !- Surface Area {m2} !- =========== ALL OBJECTS IN CLASS: SCHEDULETYPE =========== ScheduleTypeLimits, Any Number, !- Name 0.0, !- Lower Limit Value 10000, !- Upper Limit Value Continuous; !- Numeric Type ScheduleTypeLimits, Fraction, !- Name 0.0, !- Lower Limit Value 1.0, !- Upper Limit Value Continuous; !- Numeric Type ScheduleTypeLimits, Temperature, !- Name -60.0, !- Lower Limit Value 200, !- Upper Limit Value Continuous; !- Numeric Type ScheduleTypeLimits, On-Off Schedule, !- Name 0, !- Lower Limit Value 1, !- Upper Limit Value Discrete; !- Numeric Type ScheduleTypeLimits, Control Type, !- Name 0, !- Lower Limit Value 4, !- Upper Limit Value Discrete; !- Numeric Type ScheduleTypeLimits, On/Off, !- Name 0, !- Lower Limit Value 1, !- Upper Limit Value Discrete; !- Numeric Type ScheduleTypeLimits, COMPACT HVAC Any Number; !- Name !- =========== ALL OBJECTS IN CLASS: DAYSCHEDULE =========== Schedule:Day:Hourly, Office Occ WD, !- Name Fraction, !- Schedule Type Limits Name 0, !- Hour 1 0, !- Hour 2 0, !- Hour 3 0, !- Hour 4 0, !- Hour 5 0, !- Hour 6 0.11, !- Hour 7 0.21, !- Hour 8 1, !- Hour 9 1, !- Hour 10 1, !- Hour 11 1, !- Hour 12 0.53, !- Hour 13 1, !- Hour 14 1, !- Hour 15 1, !- Hour 16 1, !- Hour 17 0.32, !- Hour 18 0, !- Hour 19 0, !- Hour 20 0, !- Hour 21 0, !- Hour 22 0, !- Hour 23 0; !- Hour 24 Schedule:Day:Hourly, Office Occ WEH, !- Name Fraction, !- Schedule Type Limits Name 0, !- Hour 1 0, !- Hour 2 0, !- Hour 3 0, !- Hour 4 0, !- Hour 5 0, !- Hour 6 0, !- Hour 7 0, !- Hour 8 0, !- Hour 9 0, !- Hour 10 0, !- Hour 11 0, !- Hour 12 0, !- Hour 13 0, !- Hour 14 0, !- Hour 15 0, !- Hour 16 0, !- Hour 17 0, !- Hour 18 0, !- Hour 19 0, !- Hour 20 0, !- Hour 21 0, !- Hour 22 0, !- Hour 23 0; !- Hour 24 Schedule:Day:Hourly, Office Light WD, !- Name Fraction, !- Schedule Type Limits Name 0.18, !- Hour 1 0.18, !- Hour 2 0.18, !- Hour 3 0.18, !- Hour 4 0.18, !- Hour 5 0.18, !- Hour 6 0.23, !- Hour 7 0.42, !- Hour 8 0.90, !- Hour 9 0.90, !- Hour 10 0.90, !- Hour 11 0.90, !- Hour 12 0.80, !- Hour 13 0.90, !- Hour 14 0.90, !- Hour 15 0.90, !- Hour 16 0.90, !- Hour 17 0.61, !- Hour 18 0.18, !- Hour 19 0.18, !- Hour 20 0.18, !- Hour 21 0.18, !- Hour 22 0.18, !- Hour 23 0.18; !- Hour 24 Schedule:Day:Hourly, Office Light WD Sensor, !- Name Fraction, !- Schedule Type Limits Name 0.18, !- Hour 1 0.18, !- Hour 2 0.18, !- Hour 3 0.18, !- Hour 4 0.18, !- Hour 5 0.18, !- Hour 6 0.23, !- Hour 7 0.42, !- Hour 8 0.77, !- Hour 9 0.77, !- Hour 10 0.77, !- Hour 11 0.77, !- Hour 12 0.68, !- Hour 13 0.77, !- Hour 14 0.77, !- Hour 15 0.77, !- Hour 16 0.77, !- Hour 17 0.61, !- Hour 18 0.18, !- Hour 19 0.18, !- Hour 20 0.18, !- Hour 21 0.18, !- Hour 22 0.18, !- Hour 23 0.18; !- Hour 24 Schedule:Day:Hourly, Office Light WEH, !- Name Fraction, !- Schedule Type Limits Name 0.18, !- Hour 1 0.18, !- Hour 2 0.18, !- Hour 3 0.18, !- Hour 4 0.18, !- Hour 5 0.18, !- Hour 6 0.18, !- Hour 7 0.18, !- Hour 8 0.18, !- Hour 9 0.18, !- Hour 10 0.18, !- Hour 11 0.18, !- Hour 12 0.18, !- Hour 13 0.18, !- Hour 14 0.18, !- Hour 15 0.18, !- Hour 16 0.18, !- Hour 17 0.18, !- Hour 18 0.18, !- Hour 19 0.18, !- Hour 20 0.18, !- Hour 21 0.18, !- Hour 22 0.18, !- Hour 23 0.18; !- Hour 24 Schedule:Compact, Office_Plug_SCH, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: SummerDesignDay, !- Field 2 Until: 24:00,1.00, !- Field 3 For: WinterDesignDay, !- Field 5 Until: 24:00,0.00, !- Field 6 For: Weekdays Saturday, !- Field 8 Until: 06:00,0.2456865339, !- Field 9 Until: 07:00,0.2878515801, !- Field 11 Until: 08:00,0.4797526335, !- Field 13 Until: 12:00,0.959505267, !- Field 15 Until: 13:00,0.90193495098, !- Field 17 Until: 17:00,0.959505267, !- Field 19 Until: 18:00,0.4797526335, !- Field 21 Until: 24:00,0.2456865339, !- Field 23 For: AllOtherDays, !- Field 25 Until: 24:00,0.2456865339; !- Field 26 Schedule:Day:Hourly, Office Infiltration WD, !- Name Any Number, !- Schedule Type Limits Name 1.00, !- Hour 1 1.00, !- Hour 2 1.00, !- Hour 3 1.00, !- Hour 4 1.00, !- Hour 5 1.00, !- Hour 6 1.00, !- Hour 7 1.25, !- Hour 8 1.25, !- Hour 9 0.50, !- Hour 10 0.50, !- Hour 11 0.50, !- Hour 12 0.50, !- Hour 13 0.50, !- Hour 14 0.50, !- Hour 15 0.50, !- Hour 16 1.25, !- Hour 17 1.25, !- Hour 18 1.00, !- Hour 19 1.00, !- Hour 20 1.00, !- Hour 21 1.00, !- Hour 22 1.00, !- Hour 23 1.00; !- Hour 24 Schedule:Day:Hourly, Office Infiltration WEH, !- Name Fraction, !- Schedule Type Limits Name 1.00, !- Hour 1 1.00, !- Hour 2 1.00, !- Hour 3 1.00, !- Hour 4 1.00, !- Hour 5 1.00, !- Hour 6 1.00, !- Hour 7 1.00, !- Hour 8 1.00, !- Hour 9 1.00, !- Hour 10 1.00, !- Hour 11 1.00, !- Hour 12 1.00, !- Hour 13 1.00, !- Hour 14 1.00, !- Hour 15 1.00, !- Hour 16 1.00, !- Hour 17 1.00, !- Hour 18 1.00, !- Hour 19 1.00, !- Hour 20 1.00, !- Hour 21 1.00, !- Hour 22 1.00, !- Hour 23 1.00; !- Hour 24 Schedule:Day:Hourly, Office Heating WD_YES_OPTIMUM, !- Name Temperature, !- Schedule Type Limits Name 15.6, !- Hour 1 15.6, !- Hour 2 15.6, !- Hour 3 15.6, !- Hour 4 15.6, !- Hour 5 15.6, !- Hour 6 17.8, !- Hour 7 20.0, !- Hour 8 21.1, !- Hour 9 21.1, !- Hour 10 21.1, !- Hour 11 21.1, !- Hour 12 21.1, !- Hour 13 21.1, !- Hour 14 21.1, !- Hour 15 21.1, !- Hour 16 21.1, !- Hour 17 21.1, !- Hour 18 15.6, !- Hour 19 15.6, !- Hour 20 15.6, !- Hour 21 15.6, !- Hour 22 15.6, !- Hour 23 15.6; !- Hour 24 Schedule:Day:Hourly, Office Heating WD_NO_OPTIMUM, !- Name Temperature, !- Schedule Type Limits Name 15.6, !- Hour 1 15.6, !- Hour 2 15.6, !- Hour 3 15.6, !- Hour 4 15.6, !- Hour 5 15.6, !- Hour 6 21.1, !- Hour 7 21.1, !- Hour 8 21.1, !- Hour 9 21.1, !- Hour 10 21.1, !- Hour 11 21.1, !- Hour 12 21.1, !- Hour 13 21.1, !- Hour 14 21.1, !- Hour 15 21.1, !- Hour 16 21.1, !- Hour 17 21.1, !- Hour 18 15.6, !- Hour 19 15.6, !- Hour 20 15.6, !- Hour 21 15.6, !- Hour 22 15.6, !- Hour 23 15.6; !- Hour 24 Schedule:Day:Hourly, Office Heating WEH, !- Name Temperature, !- Schedule Type Limits Name 15.6, !- Hour 1 15.6, !- Hour 2 15.6, !- Hour 3 15.6, !- Hour 4 15.6, !- Hour 5 15.6, !- Hour 6 15.6, !- Hour 7 15.6, !- Hour 8 15.6, !- Hour 9 15.6, !- Hour 10 15.6, !- Hour 11 15.6, !- Hour 12 15.6, !- Hour 13 15.6, !- Hour 14 15.6, !- Hour 15 15.6, !- Hour 16 15.6, !- Hour 17 15.6, !- Hour 18 15.6, !- Hour 19 15.6, !- Hour 20 15.6, !- Hour 21 15.6, !- Hour 22 15.6, !- Hour 23 15.6; !- Hour 24 Schedule:Day:Hourly, Office Cooling WD_YES_OPTIMUM, !- Name Temperature, !- Schedule Type Limits Name 29.4, !- Hour 1 29.4, !- Hour 2 29.4, !- Hour 3 29.4, !- Hour 4 29.4, !- Hour 5 29.4, !- Hour 6 27.8, !- Hour 7 25.6, !- Hour 8 23.9, !- Hour 9 23.9, !- Hour 10 23.9, !- Hour 11 23.9, !- Hour 12 23.9, !- Hour 13 23.9, !- Hour 14 23.9, !- Hour 15 23.9, !- Hour 16 23.9, !- Hour 17 23.9, !- Hour 18 29.4, !- Hour 19 29.4, !- Hour 20 29.4, !- Hour 21 29.4, !- Hour 22 29.4, !- Hour 23 29.4; !- Hour 24 Schedule:Day:Hourly, Office Cooling WD_NO_OPTIMUM, !- Name Temperature, !- Schedule Type Limits Name 29.4, !- Hour 1 29.4, !- Hour 2 29.4, !- Hour 3 29.4, !- Hour 4 29.4, !- Hour 5 29.4, !- Hour 6 23.9, !- Hour 7 23.9, !- Hour 8 23.9, !- Hour 9 23.9, !- Hour 10 23.9, !- Hour 11 23.9, !- Hour 12 23.9, !- Hour 13 23.9, !- Hour 14 23.9, !- Hour 15 23.9, !- Hour 16 23.9, !- Hour 17 23.9, !- Hour 18 29.4, !- Hour 19 29.4, !- Hour 20 29.4, !- Hour 21 29.4, !- Hour 22 29.4, !- Hour 23 29.4; !- Hour 24 Schedule:Day:Hourly, Office Cooling WD_NO_SETBACK, !- Name Temperature, !- Schedule Type Limits Name 23.9, !- Hour 1 23.9, !- Hour 2 23.9, !- Hour 3 23.9, !- Hour 4 23.9, !- Hour 5 23.9, !- Hour 6 23.9, !- Hour 7 23.9, !- Hour 8 23.9, !- Hour 9 23.9, !- Hour 10 23.9, !- Hour 11 23.9, !- Hour 12 23.9, !- Hour 13 23.9, !- Hour 14 23.9, !- Hour 15 23.9, !- Hour 16 23.9, !- Hour 17 23.9, !- Hour 18 23.9, !- Hour 19 23.9, !- Hour 20 23.9, !- Hour 21 23.9, !- Hour 22 23.9, !- Hour 23 23.9; !- Hour 24 Schedule:Day:Hourly, Office Cooling WEH, !- Name Temperature, !- Schedule Type Limits Name 29.4, !- Hour 1 29.4, !- Hour 2 29.4, !- Hour 3 29.4, !- Hour 4 29.4, !- Hour 5 29.4, !- Hour 6 29.4, !- Hour 7 29.4, !- Hour 8 29.4, !- Hour 9 29.4, !- Hour 10 29.4, !- Hour 11 29.4, !- Hour 12 29.4, !- Hour 13 29.4, !- Hour 14 29.4, !- Hour 15 29.4, !- Hour 16 29.4, !- Hour 17 29.4, !- Hour 18 29.4, !- Hour 19 29.4, !- Hour 20 29.4, !- Hour 21 29.4, !- Hour 22 29.4, !- Hour 23 29.4; !- Hour 24 Schedule:Day:Hourly, Office FAN WD, !- Name Fraction, !- Schedule Type Limits Name 0, !- Hour 1 0, !- Hour 2 0, !- Hour 3 0, !- Hour 4 0, !- Hour 5 0, !- Hour 6 0, !- Hour 7 1, !- Hour 8 1, !- Hour 9 1, !- Hour 10 1, !- Hour 11 1, !- Hour 12 1, !- Hour 13 1, !- Hour 14 1, !- Hour 15 1, !- Hour 16 1, !- Hour 17 1, !- Hour 18 0, !- Hour 19 0, !- Hour 20 0, !- Hour 21 0, !- Hour 22 0, !- Hour 23 0; !- Hour 24 Schedule:Day:Hourly, Office FAN WEH, !- Name Fraction, !- Schedule Type Limits Name 0, !- Hour 1 0, !- Hour 2 0, !- Hour 3 0, !- Hour 4 0, !- Hour 5 0, !- Hour 6 0, !- Hour 7 0, !- Hour 8 0, !- Hour 9 0, !- Hour 10 0, !- Hour 11 0, !- Hour 12 0, !- Hour 13 0, !- Hour 14 0, !- Hour 15 0, !- Hour 16 0, !- Hour 17 0, !- Hour 18 0, !- Hour 19 0, !- Hour 20 0, !- Hour 21 0, !- Hour 22 0, !- Hour 23 0; !- Hour 24 Schedule:Day:Hourly, Office DHW WD, !- Name Fraction, !- Schedule Type Limits Name 0.000, !- Hour 1 0.000, !- Hour 2 0.000, !- Hour 3 0.000, !- Hour 4 0.000, !- Hour 5 0.000, !- Hour 6 0.050, !- Hour 7 0.101, !- Hour 8 0.399, !- Hour 9 0.501, !- Hour 10 0.501, !- Hour 11 0.696, !- Hour 12 0.900, !- Hour 13 0.798, !- Hour 14 0.696, !- Hour 15 0.798, !- Hour 16 0.297, !- Hour 17 0.050, !- Hour 18 0.000, !- Hour 19 0.000, !- Hour 20 0.000, !- Hour 21 0.000, !- Hour 22 0.000, !- Hour 23 0.000; !- Hour 24 Schedule:Day:Hourly, Office DHW SUNDAY, !- Name Fraction, !- Schedule Type Limits Name 0.000, !- Hour 1 0.000, !- Hour 2 0.000, !- Hour 3 0.000, !- Hour 4 0.000, !- Hour 5 0.000, !- Hour 6 0.015, !- Hour 7 0.015, !- Hour 8 0.015, !- Hour 9 0.015, !- Hour 10 0.015, !- Hour 11 0.015, !- Hour 12 0.015, !- Hour 13 0.015, !- Hour 14 0.015, !- Hour 15 0.015, !- Hour 16 0.015, !- Hour 17 0.015, !- Hour 18 0.000, !- Hour 19 0.000, !- Hour 20 0.000, !- Hour 21 0.000, !- Hour 22 0.000, !- Hour 23 0.000; !- Hour 24 Schedule:Day:Hourly, Office DHW WEH, !- Name Fraction, !- Schedule Type Limits Name 0.015, !- Hour 1 0.015, !- Hour 2 0.015, !- Hour 3 0.015, !- Hour 4 0.015, !- Hour 5 0.015, !- Hour 6 0.015, !- Hour 7 0.015, !- Hour 8 0.015, !- Hour 9 0.015, !- Hour 10 0.015, !- Hour 11 0.015, !- Hour 12 0.015, !- Hour 13 0.015, !- Hour 14 0.015, !- Hour 15 0.015, !- Hour 16 0.015, !- Hour 17 0.015, !- Hour 18 0.015, !- Hour 19 0.015, !- Hour 20 0.015, !- Hour 21 0.015, !- Hour 22 0.015, !- Hour 23 0.015; !- Hour 24 Schedule:Day:Hourly, Storage LIGHT WD, !- Name Fraction, !- Schedule Type Limits Name 0.10, !- Hour 1 0.10, !- Hour 2 0.10, !- Hour 3 0.10, !- Hour 4 0.10, !- Hour 5 0.10, !- Hour 6 0.10, !- Hour 7 0.60, !- Hour 8 0.75, !- Hour 9 0.85, !- Hour 10 0.85, !- Hour 11 0.85, !- Hour 12 0.85, !- Hour 13 0.85, !- Hour 14 0.85, !- Hour 15 0.85, !- Hour 16 0.75, !- Hour 17 0.60, !- Hour 18 0.10, !- Hour 19 0.10, !- Hour 20 0.10, !- Hour 21 0.10, !- Hour 22 0.10, !- Hour 23 0.10; !- Hour 24 Schedule:Day:Hourly, Storage Light WD Sensor, !- Name Fraction, !- Schedule Type Limits Name 0.10, !- Hour 1 0.10, !- Hour 2 0.10, !- Hour 3 0.10, !- Hour 4 0.10, !- Hour 5 0.10, !- Hour 6 0.10, !- Hour 7 0.60, !- Hour 8 0.64, !- Hour 9 0.72, !- Hour 10 0.72, !- Hour 11 0.72, !- Hour 12 0.64, !- Hour 13 0.72, !- Hour 14 0.72, !- Hour 15 0.7925, !- Hour 16 0.64, !- Hour 17 0.60, !- Hour 18 0.10, !- Hour 19 0.10, !- Hour 20 0.10, !- Hour 21 0.10, !- Hour 22 0.10, !- Hour 23 0.10; !- Hour 24 Schedule:Day:Hourly, Storage LIGHT WEH, !- Name Fraction, !- Schedule Type Limits Name 0.10, !- Hour 1 0.10, !- Hour 2 0.10, !- Hour 3 0.10, !- Hour 4 0.10, !- Hour 5 0.10, !- Hour 6 0.10, !- Hour 7 0.10, !- Hour 8 0.10, !- Hour 9 0.10, !- Hour 10 0.10, !- Hour 11 0.10, !- Hour 12 0.10, !- Hour 13 0.10, !- Hour 14 0.10, !- Hour 15 0.10, !- Hour 16 0.10, !- Hour 17 0.10, !- Hour 18 0.10, !- Hour 19 0.10, !- Hour 20 0.10, !- Hour 21 0.10, !- Hour 22 0.10, !- Hour 23 0.10; !- Hour 24 Schedule:Day:Hourly, Bulk Storage PLUG WD, !- Name Fraction, !- Schedule Type Limits Name 0.25, !- Hour 1 0.25, !- Hour 2 0.25, !- Hour 3 0.25, !- Hour 4 0.25, !- Hour 5 0.25, !- Hour 6 0.25, !- Hour 7 0.25, !- Hour 8 1, !- Hour 9 1, !- Hour 10 1, !- Hour 11 1, !- Hour 12 0.25, !- Hour 13 1, !- Hour 14 1, !- Hour 15 1, !- Hour 16 1, !- Hour 17 0.25, !- Hour 18 0.25, !- Hour 19 0.25, !- Hour 20 0.25, !- Hour 21 0.25, !- Hour 22 0.25, !- Hour 23 0.25; !- Hour 24 Schedule:Day:Hourly, Bulk Storage PLUG WEH, !- Name Fraction, !- Schedule Type Limits Name 0, !- Hour 1 0, !- Hour 2 0, !- Hour 3 0, !- Hour 4 0, !- Hour 5 0, !- Hour 6 0, !- Hour 7 0, !- Hour 8 0, !- Hour 9 0, !- Hour 10 0, !- Hour 11 0, !- Hour 12 0, !- Hour 13 0, !- Hour 14 0, !- Hour 15 0, !- Hour 16 0, !- Hour 17 0, !- Hour 18 0, !- Hour 19 0, !- Hour 20 0, !- Hour 21 0, !- Hour 22 0, !- Hour 23 0; !- Hour 24 Schedule:Day:Hourly, Fine Storage INFIL WD, !- Name Any Number, !- Schedule Type Limits Name 1.0, !- Hour 1 1.0, !- Hour 2 1.0, !- Hour 3 1.0, !- Hour 4 1.0, !- Hour 5 1.0, !- Hour 6 1.0, !- Hour 7 1.25, !- Hour 8 1.25, !- Hour 9 0.5, !- Hour 10 0.5, !- Hour 11 0.5, !- Hour 12 0.5, !- Hour 13 0.5, !- Hour 14 0.5, !- Hour 15 0.5, !- Hour 16 1.25, !- Hour 17 1.25, !- Hour 18 1.0, !- Hour 19 1.0, !- Hour 20 1.0, !- Hour 21 1.0, !- Hour 22 1.0, !- Hour 23 1; !- Hour 24 Schedule:Day:Hourly, Fine Storage INFIL WEH, !- Name Fraction, !- Schedule Type Limits Name 1.0, !- Hour 1 1.0, !- Hour 2 1.0, !- Hour 3 1.0, !- Hour 4 1.0, !- Hour 5 1.0, !- Hour 6 1.0, !- Hour 7 1.0, !- Hour 8 1.0, !- Hour 9 1.0, !- Hour 10 1.0, !- Hour 11 1.0, !- Hour 12 1.0, !- Hour 13 1.0, !- Hour 14 1.0, !- Hour 15 1.0, !- Hour 16 1.0, !- Hour 17 1.0, !- Hour 18 1.0, !- Hour 19 1.0, !- Hour 20 1.0, !- Hour 21 1.0, !- Hour 22 1.0, !- Hour 23 1.0; !- Hour 24 Schedule:Day:Hourly, Bulk Storage INFIL_Base WD, !- Name Fraction, !- Schedule Type Limits Name 0.765, !- Hour 1 0.765, !- Hour 2 0.765, !- Hour 3 0.765, !- Hour 4 0.765, !- Hour 5 0.765, !- Hour 6 0.765, !- Hour 7 0.765, !- Hour 8 1, !- Hour 9 1, !- Hour 10 1, !- Hour 11 1, !- Hour 12 0.765, !- Hour 13 1, !- Hour 14 1, !- Hour 15 1, !- Hour 16 1, !- Hour 17 0.765, !- Hour 18 0.765, !- Hour 19 0.765, !- Hour 20 0.765, !- Hour 21 0.765, !- Hour 22 0.765, !- Hour 23 0.765; !- Hour 24 Schedule:Day:Hourly, Bulk Storage INFIL_Base WEH, !- Name Fraction, !- Schedule Type Limits Name 0.765, !- Hour 1 0.765, !- Hour 2 0.765, !- Hour 3 0.765, !- Hour 4 0.765, !- Hour 5 0.765, !- Hour 6 0.765, !- Hour 7 0.765, !- Hour 8 0.765, !- Hour 9 0.765, !- Hour 10 0.765, !- Hour 11 0.765, !- Hour 12 0.765, !- Hour 13 0.765, !- Hour 14 0.765, !- Hour 15 0.765, !- Hour 16 0.765, !- Hour 17 0.765, !- Hour 18 0.765, !- Hour 19 0.765, !- Hour 20 0.765, !- Hour 21 0.765, !- Hour 22 0.765, !- Hour 23 0.765; !- Hour 24 Schedule:Day:Hourly, Bulk Storage INFIL_Adva WD, !- Name Fraction, !- Schedule Type Limits Name 0.75, !- Hour 1 0.75, !- Hour 2 0.75, !- Hour 3 0.75, !- Hour 4 0.75, !- Hour 5 0.75, !- Hour 6 0.75, !- Hour 7 0.75, !- Hour 8 1, !- Hour 9 1, !- Hour 10 1, !- Hour 11 1, !- Hour 12 0.75, !- Hour 13 1, !- Hour 14 1, !- Hour 15 1, !- Hour 16 1, !- Hour 17 0.75, !- Hour 18 0.75, !- Hour 19 0.75, !- Hour 20 0.75, !- Hour 21 0.75, !- Hour 22 0.75, !- Hour 23 0.75; !- Hour 24 Schedule:Day:Hourly, Bulk Storage INFIL_Adva WEH, !- Name Fraction, !- Schedule Type Limits Name 0.75, !- Hour 1 0.75, !- Hour 2 0.75, !- Hour 3 0.75, !- Hour 4 0.75, !- Hour 5 0.75, !- Hour 6 0.75, !- Hour 7 0.75, !- Hour 8 0.75, !- Hour 9 0.75, !- Hour 10 0.75, !- Hour 11 0.75, !- Hour 12 0.75, !- Hour 13 0.75, !- Hour 14 0.75, !- Hour 15 0.75, !- Hour 16 0.75, !- Hour 17 0.75, !- Hour 18 0.75, !- Hour 19 0.75, !- Hour 20 0.75, !- Hour 21 0.75, !- Hour 22 0.75, !- Hour 23 0.75; !- Hour 24 Schedule:Day:Hourly, Exterior Light Day Schdule, !- Name Fraction, !- Schedule Type Limits Name 1, !- Hour 1 1, !- Hour 2 1, !- Hour 3 1, !- Hour 4 1, !- Hour 5 1, !- Hour 6 1, !- Hour 7 1, !- Hour 8 0, !- Hour 9 0, !- Hour 10 0, !- Hour 11 0, !- Hour 12 0, !- Hour 13 0, !- Hour 14 0, !- Hour 15 0, !- Hour 16 0, !- Hour 17 1, !- Hour 18 1, !- Hour 19 1, !- Hour 20 1, !- Hour 21 1, !- Hour 22 1, !- Hour 23 1; !- Hour 24 Schedule:Day:Hourly, SYS Day 1, !- Name Any Number, !- Schedule Type Limits Name 1.00, !- Hour 1 1.00, !- Hour 2 1.00, !- Hour 3 1.00, !- Hour 4 1.00, !- Hour 5 1.00, !- Hour 6 1.00, !- Hour 7 1.00, !- Hour 8 1.00, !- Hour 9 1.00, !- Hour 10 1.00, !- Hour 11 1.00, !- Hour 12 1.00, !- Hour 13 1.00, !- Hour 14 1.00, !- Hour 15 1.00, !- Hour 16 1.00, !- Hour 17 1.00, !- Hour 18 1.00, !- Hour 19 1.00, !- Hour 20 1.00, !- Hour 21 1.00, !- Hour 22 1.00, !- Hour 23 1.00; !- Hour 24 !- =========== ALL OBJECTS IN CLASS: WEEKSCHEDULE =========== Schedule:Week:Daily, Office Light Wk Schedule,!- Name Office Light WEH, !- Sunday Schedule:Day Name Office Light WD, !- Monday Schedule:Day Name Office Light WD, !- Tuesday Schedule:Day Name Office Light WD, !- Wednesday Schedule:Day Name Office Light WD, !- Thursday Schedule:Day Name Office Light WD, !- Friday Schedule:Day Name Office Light WD, !- Saturday Schedule:Day Name Office Light WEH, !- Holiday Schedule:Day Name Office Light WD, !- SummerDesignDay Schedule:Day Name Office Light WD, !- WinterDesignDay Schedule:Day Name Office Light WD, !- CustomDay1 Schedule:Day Name Office Light WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office Light with Sensor Wk Schedule, !- Name Office Light WEH, !- Sunday Schedule:Day Name Office Light WD Sensor, !- Monday Schedule:Day Name Office Light WD Sensor, !- Tuesday Schedule:Day Name Office Light WD Sensor, !- Wednesday Schedule:Day Name Office Light WD Sensor, !- Thursday Schedule:Day Name Office Light WD Sensor, !- Friday Schedule:Day Name Office Light WD Sensor, !- Saturday Schedule:Day Name Office Light WEH, !- Holiday Schedule:Day Name Office Light WD Sensor, !- SummerDesignDay Schedule:Day Name Office Light WD Sensor, !- WinterDesignDay Schedule:Day Name Office Light WD Sensor, !- CustomDay1 Schedule:Day Name Office Light WD Sensor; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office People Wk Schedule, !- Name Office Occ WEH, !- Sunday Schedule:Day Name Office Occ WD, !- Monday Schedule:Day Name Office Occ WD, !- Tuesday Schedule:Day Name Office Occ WD, !- Wednesday Schedule:Day Name Office Occ WD, !- Thursday Schedule:Day Name Office Occ WD, !- Friday Schedule:Day Name Office Occ WD, !- Saturday Schedule:Day Name Office Occ WEH, !- Holiday Schedule:Day Name Office Occ WD, !- SummerDesignDay Schedule:Day Name Office Occ WD, !- WinterDesignDay Schedule:Day Name Office Occ WD, !- CustomDay1 Schedule:Day Name Office Occ WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office Infil Wk Schedule,!- Name Office Infiltration WEH, !- Sunday Schedule:Day Name Office Infiltration WD, !- Monday Schedule:Day Name Office Infiltration WD, !- Tuesday Schedule:Day Name Office Infiltration WD, !- Wednesday Schedule:Day Name Office Infiltration WD, !- Thursday Schedule:Day Name Office Infiltration WD, !- Friday Schedule:Day Name Office Infiltration WD, !- Saturday Schedule:Day Name Office Infiltration WEH, !- Holiday Schedule:Day Name Office Infiltration WD, !- SummerDesignDay Schedule:Day Name Office Infiltration WD, !- WinterDesignDay Schedule:Day Name Office Infiltration WD, !- CustomDay1 Schedule:Day Name Office Infiltration WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office Heating Wk Schedule, !- Name Office Heating WEH, !- Sunday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Monday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Tuesday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Wednesday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Thursday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Friday Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- Saturday Schedule:Day Name Office Heating WEH, !- Holiday Schedule:Day Name Office Heating WD_YES_OPTIMUM, !- SummerDesignDay Schedule:Day Name Office Heating WD_YES_OPTIMUM, !- WinterDesignDay Schedule:Day Name Office Heating WD_NO_OPTIMUM, !- CustomDay1 Schedule:Day Name Office Heating WD_NO_OPTIMUM; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office Cooling Wk Schedule, !- Name Office Cooling WEH, !- Sunday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Monday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Tuesday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Wednesday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Thursday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Friday Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- Saturday Schedule:Day Name Office Cooling WEH, !- Holiday Schedule:Day Name Office Cooling WD_YES_OPTIMUM, !- SummerDesignDay Schedule:Day Name Office Cooling WD_YES_OPTIMUM, !- WinterDesignDay Schedule:Day Name Office Cooling WD_NO_OPTIMUM, !- CustomDay1 Schedule:Day Name Office Cooling WD_NO_OPTIMUM; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office Fan Wk Schedule, !- Name Office FAN WEH, !- Sunday Schedule:Day Name Office FAN WD, !- Monday Schedule:Day Name Office FAN WD, !- Tuesday Schedule:Day Name Office FAN WD, !- Wednesday Schedule:Day Name Office FAN WD, !- Thursday Schedule:Day Name Office FAN WD, !- Friday Schedule:Day Name Office FAN WD, !- Saturday Schedule:Day Name Office FAN WEH, !- Holiday Schedule:Day Name Office FAN WD, !- SummerDesignDay Schedule:Day Name Office FAN WD, !- WinterDesignDay Schedule:Day Name Office FAN WD, !- CustomDay1 Schedule:Day Name Office FAN WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Office DHW Wk Schedule, !- Name Office DHW WEH, !- Sunday Schedule:Day Name Office DHW WD, !- Monday Schedule:Day Name Office DHW WD, !- Tuesday Schedule:Day Name Office DHW WD, !- Wednesday Schedule:Day Name Office DHW WD, !- Thursday Schedule:Day Name Office DHW WD, !- Friday Schedule:Day Name Office DHW WD, !- Saturday Schedule:Day Name Office DHW WEH, !- Holiday Schedule:Day Name Office DHW WD, !- SummerDesignDay Schedule:Day Name Office DHW WD, !- WinterDesignDay Schedule:Day Name Office DHW WD, !- CustomDay1 Schedule:Day Name Office DHW WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Storage Light with Sensor Wk Schedule, !- Name Storage LIGHT WEH, !- Sunday Schedule:Day Name Storage LIGHT WD Sensor, !- Monday Schedule:Day Name Storage LIGHT WD Sensor, !- Tuesday Schedule:Day Name Storage LIGHT WD Sensor, !- Wednesday Schedule:Day Name Storage LIGHT WD Sensor, !- Thursday Schedule:Day Name Storage LIGHT WD Sensor, !- Friday Schedule:Day Name Storage LIGHT WD Sensor, !- Saturday Schedule:Day Name Storage LIGHT WEH, !- Holiday Schedule:Day Name Storage LIGHT WD Sensor, !- SummerDesignDay Schedule:Day Name Storage LIGHT WD Sensor, !- WinterDesignDay Schedule:Day Name Storage LIGHT WD Sensor, !- CustomDay1 Schedule:Day Name Storage LIGHT WD Sensor; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Bulk Storage Plug Wk Schedule, !- Name Bulk Storage PLUG WEH, !- Sunday Schedule:Day Name Bulk Storage PLUG WD, !- Monday Schedule:Day Name Bulk Storage PLUG WD, !- Tuesday Schedule:Day Name Bulk Storage PLUG WD, !- Wednesday Schedule:Day Name Bulk Storage PLUG WD, !- Thursday Schedule:Day Name Bulk Storage PLUG WD, !- Friday Schedule:Day Name Bulk Storage PLUG WD, !- Saturday Schedule:Day Name Bulk Storage PLUG WEH, !- Holiday Schedule:Day Name Bulk Storage PLUG WD, !- SummerDesignDay Schedule:Day Name Bulk Storage PLUG WD, !- WinterDesignDay Schedule:Day Name Bulk Storage PLUG WD, !- CustomDay1 Schedule:Day Name Bulk Storage PLUG WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Fine Storage Infil Wk Schedule, !- Name Fine Storage INFIL WEH, !- Sunday Schedule:Day Name Fine Storage INFIL WD, !- Monday Schedule:Day Name Fine Storage INFIL WD, !- Tuesday Schedule:Day Name Fine Storage INFIL WD, !- Wednesday Schedule:Day Name Fine Storage INFIL WD, !- Thursday Schedule:Day Name Fine Storage INFIL WD, !- Friday Schedule:Day Name Fine Storage INFIL WD, !- Saturday Schedule:Day Name Fine Storage INFIL WEH, !- Holiday Schedule:Day Name Fine Storage INFIL WD, !- SummerDesignDay Schedule:Day Name Fine Storage INFIL WD, !- WinterDesignDay Schedule:Day Name Fine Storage INFIL WD, !- CustomDay1 Schedule:Day Name Fine Storage INFIL WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Bulk Storage Infil_Base Wk Schedule, !- Name Bulk Storage INFIL_Base WEH, !- Sunday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Monday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Tuesday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Wednesday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Thursday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Friday Schedule:Day Name Bulk Storage INFIL_Base WD, !- Saturday Schedule:Day Name Bulk Storage INFIL_Base WEH, !- Holiday Schedule:Day Name Bulk Storage INFIL_Base WD, !- SummerDesignDay Schedule:Day Name Bulk Storage INFIL_Base WD, !- WinterDesignDay Schedule:Day Name Bulk Storage INFIL_Base WD, !- CustomDay1 Schedule:Day Name Bulk Storage INFIL_Base WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Bulk Storage Infil_Adva Wk Schedule, !- Name Bulk Storage INFIL_Adva WEH, !- Sunday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Monday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Tuesday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Wednesday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Thursday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Friday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- Saturday Schedule:Day Name Bulk Storage INFIL_Adva WEH, !- Holiday Schedule:Day Name Bulk Storage INFIL_Adva WD, !- SummerDesignDay Schedule:Day Name Bulk Storage INFIL_Adva WD, !- WinterDesignDay Schedule:Day Name Bulk Storage INFIL_Adva WD, !- CustomDay1 Schedule:Day Name Bulk Storage INFIL_Adva WD; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Exterior Light Wk Schedule, !- Name Exterior Light Day Schdule, !- Sunday Schedule:Day Name Exterior Light Day Schdule, !- Monday Schedule:Day Name Exterior Light Day Schdule, !- Tuesday Schedule:Day Name Exterior Light Day Schdule, !- Wednesday Schedule:Day Name Exterior Light Day Schdule, !- Thursday Schedule:Day Name Exterior Light Day Schdule, !- Friday Schedule:Day Name Exterior Light Day Schdule, !- Saturday Schedule:Day Name Exterior Light Day Schdule, !- Holiday Schedule:Day Name Exterior Light Day Schdule, !- SummerDesignDay Schedule:Day Name Exterior Light Day Schdule, !- WinterDesignDay Schedule:Day Name Exterior Light Day Schdule, !- CustomDay1 Schedule:Day Name Exterior Light Day Schdule; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, SYS-ON, !- Name SYS Day 1, !- Sunday Schedule:Day Name SYS Day 1, !- Monday Schedule:Day Name SYS Day 1, !- Tuesday Schedule:Day Name SYS Day 1, !- Wednesday Schedule:Day Name SYS Day 1, !- Thursday Schedule:Day Name SYS Day 1, !- Friday Schedule:Day Name SYS Day 1, !- Saturday Schedule:Day Name SYS Day 1, !- Holiday Schedule:Day Name SYS Day 1, !- SummerDesignDay Schedule:Day Name SYS Day 1, !- WinterDesignDay Schedule:Day Name SYS Day 1, !- CustomDay1 Schedule:Day Name SYS Day 1; !- CustomDay2 Schedule:Day Name Schedule:Week:Daily, Storage Light Wk Schedule, !- Name Storage LIGHT WEH, !- Sunday Schedule:Day Name Storage LIGHT WD, !- Monday Schedule:Day Name Storage LIGHT WD, !- Tuesday Schedule:Day Name Storage LIGHT WD, !- Wednesday Schedule:Day Name Storage LIGHT WD, !- Thursday Schedule:Day Name Storage LIGHT WD, !- Friday Schedule:Day Name Storage LIGHT WD, !- Saturday Schedule:Day Name Storage LIGHT WEH, !- Holiday Schedule:Day Name Storage LIGHT WD, !- SummerDesignDay Schedule:Day Name Storage LIGHT WD, !- WinterDesignDay Schedule:Day Name Storage LIGHT WD, !- CustomDay1 Schedule:Day Name Storage LIGHT WD; !- CustomDay2 Schedule:Day Name !- =========== ALL OBJECTS IN CLASS: SCHEDULE =========== Schedule:Year, Office Light Schedule, !- Name Fraction, !- Schedule Type Limits Name Office Light Wk Schedule,!- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office People Schedule, !- Name Fraction, !- Schedule Type Limits Name Office People Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office Infil Schedule, !- Name Any Number, !- Schedule Type Limits Name Office Infil Wk Schedule,!- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office HVAC Schedule, !- Name Temperature, !- Schedule Type Limits Name Office Heating Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 4, !- End Month 1 30, !- End Day 1 Office Cooling Wk Schedule, !- Schedule:Week Name 2 5, !- Start Month 2 1, !- Start Day 2 8, !- End Month 2 31, !- End Day 2 Office Heating Wk Schedule, !- Schedule:Week Name 3 9, !- Start Month 3 1, !- Start Day 3 12, !- End Month 3 31; !- End Day 3 Schedule:Year, Office Fan Schedule, !- Name On-Off Schedule, !- Schedule Type Limits Name Office Fan Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office DHW Schedule, !- Name Fraction, !- Schedule Type Limits Name Office DHW Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Storage Light Schedule, !- Name Fraction, !- Schedule Type Limits Name Storage Light Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Bulk Storage Plug Schedule, !- Name Fraction, !- Schedule Type Limits Name Bulk Storage Plug Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Fine Sorage Infil Schedule, !- Name Any Number, !- Schedule Type Limits Name Fine Storage Infil Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Bulk Storage Infil_Base Schedule, !- Name Any Number, !- Schedule Type Limits Name Bulk Storage Infil_Base Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Bulk Storage Infil_Adva Schedule, !- Name Any Number, !- Schedule Type Limits Name Bulk Storage Infil_Adva Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Exterior Light Schedule, !- Name Fraction, !- Schedule Type Limits Name Exterior Light Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office Heating Schedule, !- Name Temperature, !- Schedule Type Limits Name Office Heating Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office Cooling Schedule, !- Name Temperature, !- Schedule Type Limits Name Office Cooling Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, UnitHeaterAvailability, !- Name Any Number, !- Schedule Type Limits Name SYS-ON, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, UnitVentMaxOA, !- Name Any Number, !- Schedule Type Limits Name SYS-ON, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Zone3HeatingCoilAvailability, !- Name Any Number, !- Schedule Type Limits Name SYS-ON, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Office Light with Sensor Schedule, !- Name Fraction, !- Schedule Type Limits Name Office Light with Sensor Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 Schedule:Year, Storage Light with Sensor Schedule, !- Name Fraction, !- Schedule Type Limits Name Storage Light with Sensor Wk Schedule, !- Schedule:Week Name 1 1, !- Start Month 1 1, !- Start Day 1 12, !- End Month 1 31; !- End Day 1 !- =========== ALL OBJECTS IN CLASS: SCHEDULE:COMPACT =========== Schedule:Compact, BLDG_LIGHT_OFFICE_SCH, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: Weekdays Saturday, !- Field 2 Until: 6:00,0.18, !- Field 3 Until: 7:00,0.18788861, !- Field 5 Until: 8:00,0.34310094, !- Field 7 Until: 12:00,0.62901839, !- Field 9 Until: 13:00,0.55549676, !- Field 11 Until: 17:00,0.62901839, !- Field 13 Until: 18:00,0.49831327, !- Field 15 Until: 24:00,0.18, !- Field 17 For: SummerDesignDay, !- Field 19 Until: 24:00,1, !- Field 20 For: WinterDesignDay, !- Field 22 Until: 24:00,0, !- Field 23 For: Sunday Holidays AllOtherDays, !- Field 25 Until: 24:00,0.18; !- Field 26 Schedule:Compact, BLDG_LIGHT_STORAGE_SCH, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: Weekdays Saturday, !- Field 2 Until: 7:00,0.1, !- Field 3 Until: 8:00,0.6, !- Field 5 Until: 9:00,0.75, !- Field 7 Until: 16:00,0.85, !- Field 9 Until: 17:00,0.75, !- Field 11 Until: 18:00,0.6, !- Field 13 Until: 24:00,0.1, !- Field 15 For: SummerDesignDay, !- Field 17 Until: 24:00,1, !- Field 18 For: WinterDesignDay, !- Field 20 Until: 24:00,0, !- Field 21 For: Sunday Holidays AllOtherDays, !- Field 23 Until: 24:00,0.1; !- Field 24 Schedule:Compact, BLDG_OCC_SCH, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: Weekdays Saturday WinterDesignDay, !- Field 2 Until: 06:00,0.00, !- Field 3 Until: 07:00,0.11, !- Field 5 Until: 08:00,0.21, !- Field 7 Until: 12:00,1.00, !- Field 9 Until: 13:00,0.53, !- Field 11 Until: 17:00,1.00, !- Field 13 Until: 18:00,0.32, !- Field 15 Until: 24:00,0.00, !- Field 17 For: SummerDesignDay, !- Field 19 Until: 06:00,0.000000001,!- Field 20 Until: 07:00,0.11, !- Field 22 Until: 08:00,0.21, !- Field 24 Until: 12:00,1.00, !- Field 26 Until: 13:00,0.53, !- Field 28 Until: 17:00,1.00, !- Field 30 Until: 18:00,0.32, !- Field 32 Until: 24:00,0.000000001,!- Field 34 For: Sunday Holidays AllOtherDays, !- Field 36 Until: 24:00,0.0; !- Field 37 Schedule:Compact, Office Activity Schedule,!- Name Any Number, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,131.85; !- Field 3 Schedule:Compact, FanSched, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: WeekDays Saturday CustomDay1 CustomDay2, !- Field 2 Until: 7:00,0.0, !- Field 3 Until: 18:00,1.0, !- Field 5 Until: 24:00,0.0, !- Field 7 For: Sunday Holiday, !- Field 9 Until: 24:00,0.0, !- Field 10 For: SummerDesignDay, !- Field 12 Until: 24:00,1.0, !- Field 13 For: WinterDesignDay, !- Field 15 Until: 24:00,1.0; !- Field 16 Schedule:Compact, MinOA_MotorizedDamper_Sched, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: WeekDays Saturday CustomDay1 CustomDay2, !- Field 2 Until: 8:00,0.0, !- Field 3 Until: 18:00,1.0, !- Field 5 Until: 24:00,0.0, !- Field 7 For: Sunday Holiday, !- Field 9 Until: 24:00,0.0, !- Field 10 For: SummerDesignDay, !- Field 12 Until: 24:00,1.0, !- Field 13 For: WinterDesignDay, !- Field 15 Until: 24:00,1.0; !- Field 16 Schedule:Compact, Bulk Storage Heating Setpoint Schedule, !- Name Temperature, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,10.0; !- Field 3 Schedule:Compact, ZoneControlSchedule, !- Name Control Type, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1; !- Field 3 Schedule:Compact, Hot Water Setpoint Temp Schedule, !- Name Any Number, !- Schedule Type Limits Name THROUGH: 12/31, !- Field 1 FOR: AllDays, !- Field 2 UNTIL: 24:00,60.0; !- Field 3 Schedule:Compact, ALWAYS_OFF, !- Name On/Off, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,0; !- Field 3 Schedule:Compact, ALWAYS_ON, !- Name On/Off, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1; !- Field 3 Schedule:Compact, Exterior_Lgt_ALWAYS_ON, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1; !- Field 3 Schedule:Compact, Exterior_Lgt_189_1, !- Name Fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:Weekdays, !- Field 2 Until: 9:00,0.5, !- Field 3 Until: 18:00,1.0, !- Field 5 Until: 24:00,0.5, !- Field 7 For:Saturday, !- Field 9 Until: 24:00,0.5, !- Field 10 For:Sunday Holidays AllOtherDays, !- Field 12 Until: 24:00,0.5; !- Field 13 Schedule:Compact, Always Off Schedule, !- Name Fraction, !- Schedule Type Limits Name THROUGH: 12/31, !- Field 1 FOR: AllDays, !- Field 2 UNTIL: 24:00,0; !- Field 3 Schedule:Compact, COMPACT HVAC-ALWAYS 1, !- Name COMPACT HVAC Any Number, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1; !- Field 3 Schedule:Compact, COMPACT HVAC-ALWAYS 4, !- Name COMPACT HVAC Any Number, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,4; !- Field 3 Schedule:Compact, Fine Storage Heating Setpoint Schedule, !- Name Temperature, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,15.56; !- Field 3 Schedule:Compact, Fine Storage Cooling Setpoint Schedule, !- Name Temperature, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,26.7; !- Field 3 Schedule:Compact, OA Damper Off during off hrs Schedule, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: WeekDay Saturday CustomDay1 CustomDay2, !- Field 2 Until: 8:00,0.0, !- Field 3 Until: 17:00,1.0, !- Field 5 Until: 24:00,0.0, !- Field 7 For: Sunday Holiday, !- Field 9 Until: 24:00,0.0, !- Field 10 For: SummerDesignDay, !- Field 12 Until: 24:00,1.0, !- Field 13 For: WinterDesignDay, !- Field 15 Until: 24:00,1.0; !- Field 16 Schedule:Compact, OA Damper Always ON Schedule, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1; !- Field 3 Schedule:Compact, MinOA_Sched, !- Name fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 24:00,1.0; !- Field 3 Schedule:Compact, Always On Schedule, !- Name Fraction, !- Schedule Type Limits Name THROUGH: 12/31, !- Field 1 FOR: AllDays, !- Field 2 UNTIL: 24:00,1; !- Field 3 Schedule:Compact, Exterior_Ltg_Sch, !- Name Fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: AllDays, !- Field 2 Until: 07:00,1.0, !- Field 3 Until: 19:00,0.0, !- Field 5 Until: 24:00,1.0; !- Field 7 Schedule:Compact, INFIL_Door_Opening_SCH, !- Name fraction, !- Schedule Type Limits Name Through: 12/31, !- Field 1 For: Weekdays, !- Field 2 Until: 06:00,0.0, !- Field 3 Until: 07:00,0.131, !- Field 5 Until: 08:00,1.0, !- Field 7 Until: 12:00,0.131, !- Field 9 Until: 13:00,1.0, !- Field 11 Until: 17:00,0.131, !- Field 13 Until: 18:00,1.0, !- Field 15 Until: 19:00,0.131, !- Field 17 Until: 24:00,0.0, !- Field 19 For: Saturday Sunday Holidays AllOtherDays, !- Field 21 Until: 24:00,0.0; !- Field 22 !- =========== ALL OBJECTS IN CLASS: PEOPLE =========== People, Office People, !- Name Zone1 Office, !- Zone or ZoneList Name BLDG_OCC_SCH, !- Number of People Schedule Name People, !- Number of People Calculation Method 5, !- Number of People , !- People per Zone Floor Area {person/m2} , !- Zone Floor Area per Person {m2/person} 0.3, !- Fraction Radiant autocalculate, !- Sensible Heat Fraction Office Activity Schedule,!- Activity Level Schedule Name , !- Carbon Dioxide Generation Rate {m3/s-W} , !- Enable ASHRAE 55 Comfort Warnings ZoneAveraged; !- Mean Radiant Temperature Calculation Type !- =========== ALL OBJECTS IN CLASS: LIGHTS =========== Lights, Office Lights, !- Name Zone1 Office, !- Zone or ZoneList Name BLDG_LIGHT_OFFICE_SCH, !- Schedule Name Watts/Area, !- Design Level Calculation Method , !- Lighting Level {W} 6.888902667, !- Watts per Zone Floor Area {W/m2} , !- Watts per Person {W/person} 0, !- Return Air Fraction 0.37, !- Fraction Radiant 0.18, !- Fraction Visible 1, !- Fraction Replaceable LightsWired, !- End-Use Subcategory No; !- Return Air Fraction Calculated from Plenum Temperature Lights, Fine Storage Area Lights,!- Name Zone2 Fine Storage, !- Zone or ZoneList Name BLDG_LIGHT_STORAGE_SCH, !- Schedule Name Watts/Area, !- Design Level Calculation Method , !- Lighting Level {W} 7.427098188, !- Watts per Zone Floor Area {W/m2} , !- Watts per Person {W/person} 0, !- Return Air Fraction 0.42, !- Fraction Radiant 0.18, !- Fraction Visible 1, !- Fraction Replaceable LightsWired, !- End-Use Subcategory No; !- Return Air Fraction Calculated from Plenum Temperature Lights, Bulk Storage Area Lights,!- Name Zone3 Bulk Storage, !- Zone or ZoneList Name BLDG_LIGHT_STORAGE_SCH, !- Schedule Name Watts/Area, !- Design Level Calculation Method , !- Lighting Level {W} 3.552090438, !- Watts per Zone Floor Area {W/m2} , !- Watts per Person {W/person} 0, !- Return Air Fraction 0.42, !- Fraction Radiant 0.18, !- Fraction Visible 1, !- Fraction Replaceable LightsWired, !- End-Use Subcategory No; !- Return Air Fraction Calculated from Plenum Temperature !- =========== ALL OBJECTS IN CLASS: ELECTRIC EQUIPMENT =========== ElectricEquipment, Office Plug Load, !- Name Zone1 Office, !- Zone or ZoneList Name Office_Plug_SCH, !- Schedule Name EquipmentLevel, !- Design Level Calculation Method 1912.5, !- Design Level {W} , !- Watts per Zone Floor Area {W/m2} , !- Watts per Person {W/person} , !- Fraction Latent , !- Fraction Radiant , !- Fraction Lost MiscPlug; !- End-Use Subcategory ElectricEquipment, Bulk Storage Plug Load, !- Name Zone3 Bulk Storage, !- Zone or ZoneList Name Bulk Storage Plug Schedule, !- Schedule Name EquipmentLevel, !- Design Level Calculation Method 8200.12, !- Design Level {W} , !- Watts per Zone Floor Area {W/m2} , !- Watts per Person {W/person} , !- Fraction Latent , !- Fraction Radiant , !- Fraction Lost MiscPlug; !- End-Use Subcategory !- =========== ALL OBJECTS IN CLASS: EXTERIORLIGHTS =========== Exterior:Lights, Exterior_Lights_a, !- Name Exterior_lighting_schedule_a, !- Schedule Name 113.8, !- Design Level {W} AstronomicalClock, !- Control Option General; !- End-Use Subcategory Exterior:Lights, Exterior_Lights_b, !- Name Exterior_lighting_schedule_b_2016, !- Schedule Name 3955, !- Design Level {W} AstronomicalClock, !- Control Option General; !- End-Use Subcategory Exterior:Lights, Exterior_Lights_c, !- Name Exterior_lighting_schedule_c_2016, !- Schedule Name 1004.9, !- Design Level {W} AstronomicalClock, !- Control Option General; !- End-Use Subcategory Schedule:Compact, Exterior_lighting_schedule_a, !- Name fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:AllDays, !- Field 2 Until: 06:00,0, !- Field 3 Until: 24:00,1; !- Field 5 Schedule:Compact, Exterior_lighting_schedule_b, !- Name fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:AllDays, !- Field 2 Until: 06:00,0.7, !- Field 3 Until: 24:00,1; !- Field 5 Schedule:Compact, Exterior_lighting_schedule_a_IECC2015, !- Name fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:Weekdays SummerDesignDay, !- Field 2 Until: 08:00,0, !- Field 3 Until: 18:00,1, !- Field 5 Until: 24:00,0, !- Field 7 For:Saturdays, !- Field 9 Until: 24:00,0, !- Field 10 For:AllOtherDays, !- Field 12 Until: 24:00,0; !- Field 13 Schedule:Compact, Exterior_lighting_schedule_b_2016, !- Name fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:AllDays, !- Field 2 Until: 06:00,0.5, !- Field 3 Until: 24:00,1; !- Field 5 Schedule:Compact, Exterior_lighting_schedule_c_2016, !- Name fraction, !- Schedule Type Limits Name Through:12/31, !- Field 1 For:AllDays, !- Field 2 Until: 06:00,0.5, !- Field 3 Until: 20:00,1, !- Field 5 Until: 24:00,0.5; !- Field 7 Schedule:Constant,SZ_system_OA_Max_Frac_SCH,Fraction, 0.75; !- =========== ALL OBJECTS IN CLASS: DAYLIGHTING:CONTROLS =========== Daylighting:Controls, Zone1 Office_DaylCtrl, !- Name Zone1 Office, !- Zone Name SplitFlux, !- Daylighting Method , !- Availability Schedule Name Continuousoff, !- Lighting Control Type 0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control 0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control 3, !- Number of Stepped Control Steps 1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control Zone1 Office_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name 180.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg} 22.0, !- Maximum Allowable Discomfort Glare Index , !- DElight Gridding Resolution {m2} Zone1 Office_DaylRefPt1, !- Daylighting Reference Point 1 Name 0.29, !- Fraction of Zone Controlled by Reference Point 1 377.0, !- Illuminance Setpoint at Reference Point 1 {lux} Zone1 Office_DaylRefPt2, !- Daylighting Reference Point 2 Name 0.1, !- Fraction of Zone Controlled by Reference Point 2 377.0; !- Illuminance Setpoint at Reference Point 2 {lux} Daylighting:ReferencePoint, Zone1 Office_DaylRefPt1, !- Name Zone1 Office, !- Zone Name 3.267500, !- X-Coordinate of Reference Point {m} 4.571800, !- Y-Coordinate of Reference Point {m} 0.762000; !- Z-Coordinate of Reference Point {m} Daylighting:ReferencePoint, Zone1 Office_DaylRefPt2, !- Name Zone1 Office, !- Zone Name 20.421600, !- X-Coordinate of Reference Point {m} 4.571800, !- Y-Coordinate of Reference Point {m} 0.762000; !- Z-Coordinate of Reference Point {m} !- =========== ALL OBJECTS IN CLASS: INFILTRATION =========== ZoneInfiltration:DesignFlowRate, Office Infiltration, !- Name Zone1 Office, !- Zone or ZoneList Name Office Infil Schedule, !- Schedule Name Flow/ExteriorArea, !- Design Flow Rate Calculation Method , !- Design Flow Rate {m3/s} , !- Flow per Zone Floor Area {m3/s-m2} 0.000220198,!- Flow per Exterior Surface Area {m3/s-m2} , !- Air Changes per Hour {1/hr} 0, !- Constant Term Coefficient 0, !- Temperature Term Coefficient 0.224, !- Velocity Term Coefficient 0; !- Velocity Squared Term Coefficient ZoneInfiltration:DesignFlowRate, Office Door Infiltration,!- Name Zone1 Office, !- Zone or ZoneList Name INFIL_Door_Opening_SCH, !- Schedule Name Flow/Zone, !- Design Flow Rate Calculation Method 0.176508178, !- Design Flow Rate {m3/s} , !- Flow per Zone Floor Area {m3/s-m2} , !- Flow per Exterior Surface Area {m3/s-m2} , !- Air Changes per Hour {1/hr} 1, !- Constant Term Coefficient 0.0000, !- Temperature Term Coefficient 0.0000, !- Velocity Term Coefficient 0.0000; !- Velocity Squared Term Coefficient ZoneInfiltration:DesignFlowRate, Fine Storage Infiltration, !- Name Zone2 Fine Storage, !- Zone or ZoneList Name Fine Sorage Infil Schedule, !- Schedule Name Flow/ExteriorArea, !- Design Flow Rate Calculation Method , !- Design Flow Rate {m3/s} , !- Flow per Zone Floor Area {m3/s-m2} 0.000225765, !- Flow per Exterior Surface Area {m3/s-m2} , !- Air Changes per Hour {1/hr} 0, !- Constant Term Coefficient 0, !- Temperature Term Coefficient 0.224, !- Velocity Term Coefficient 0; !- Velocity Squared Term Coefficient ZoneInfiltration:DesignFlowRate, Bulk Storage Infiltration, !- Name Zone3 Bulk Storage, !- Zone or ZoneList Name Bulk Storage Infil_Base Schedule, !- Schedule Name Flow/Zone, !- Design Flow Rate Calculation Method 2.330231241, !- Design Flow Rate {m3/s} , !- Flow per Zone Floor Area {m3/s-m2} , !- Flow per Exterior Surface Area {m3/s-m2} , !- Air Changes per Hour {1/hr} 0, !- Constant Term Coefficient 0, !- Temperature Term Coefficient 0.224, !- Velocity Term Coefficient 0; !- Velocity Squared Term Coefficient !- =========== ALL OBJECTS IN CLASS: VENTILATION =========== ZoneVentilation:DesignFlowRate, Bulk Storage Ventilation-1, !- Name Zone3 Bulk Storage, !- Zone or ZoneList Name Always On Schedule, !- Schedule Name Flow/Zone, !- Design Flow Rate Calculation Method 37.7600047937506, !- Design Flow Rate {m3/s} , !- Flow Rate per Zone Floor Area {m3/s-m2} , !- Flow Rate per Person {m3/s-person} , !- Air Changes per Hour {1/hr} Exhaust, !- Ventilation Type 31.1361206455786, !- Fan Pressure Rise {Pa} 0.51, !- Fan Total Efficiency 1, !- Constant Term Coefficient 0, !- Temperature Term Coefficient 0, !- Velocity Term Coefficient 0, !- Velocity Squared Term Coefficient 29.4444452244559, !- Minimum Indoor Temperature {C} , !- Minimum Indoor Temperature Schedule Name 100, !- Maximum Indoor Temperature {C} , !- Maximum Indoor Temperature Schedule Name -100, !- Delta Temperature {deltaC} , !- Delta Temperature Schedule Name -100, !- Minimum Outdoor Temperature {C} , !- Minimum Outdoor Temperature Schedule Name 100, !- Maximum Outdoor Temperature {C} , !- Maximum Outdoor Temperature Schedule Name 40; !- Maximum Wind Speed {m/s} ZoneVentilation:DesignFlowRate, Bulk Storage Ventilation-2, !- Name Zone3 Bulk Storage, !- Zone or ZoneList Name Always On Schedule, !- Schedule Name Flow/Zone, !- Design Flow Rate Calculation Method 0.943841435, !- Design Flow Rate {m3/s} , !- Flow Rate per Zone Floor Area {m3/s-m2} , !- Flow Rate per Person {m3/s-person} , !- Air Changes per Hour {1/hr} Natural, !- Ventilation Type , !- Fan Pressure Rise {Pa} 1, !- Fan Total Efficiency 0, !- Constant Term Coefficient 0, !- Temperature Term Coefficient 0.224, !- Velocity Term Coefficient 0, !- Velocity Squared Term Coefficient -73.3333352760033, !- Minimum Indoor Temperature {C} , !- Minimum Indoor Temperature Schedule Name 29.4444452244559, !- Maximum Indoor Temperature {C} , !- Maximum Indoor Temperature Schedule Name -100, !- Delta Temperature {deltaC} , !- Delta Temperature Schedule Name -100, !- Minimum Outdoor Temperature {C} , !- Minimum Outdoor Temperature Schedule Name 100, !- Maximum Outdoor Temperature {C} , !- Maximum Outdoor Temperature Schedule Name 40; !- Maximum Wind Speed {m/s} !- =========== ALL OBJECTS IN CLASS: SIZING PARAMETERS =========== Sizing:Parameters, 1.2, !- Heating Sizing Factor 1.2, !- Cooling Sizing Factor 6; !- Timesteps in Averaging Window !- =========== ALL OBJECTS IN CLASS: ZONE SIZING =========== Sizing:Zone, Zone1 Office, !- Zone or ZoneList Name SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method 14, !- Zone Cooling Design Supply Air Temperature {C} , !- Zone Cooling Design Supply Air Temperature Difference {deltaC} SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method 50, !- Zone Heating Design Supply Air Temperature {C} , !- Zone Heating Design Supply Air Temperature Difference {deltaC} 0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir} 0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir} SZ DSOA Zone1 Office, !- Design Specification Outdoor Air Object Name , !- Zone Heating Sizing Factor , !- Zone Cooling Sizing Factor DesignDay, !- Cooling Design Air Flow Method 0, !- Cooling Design Air Flow Rate {m3/s} , !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2} , !- Cooling Minimum Air Flow {m3/s} 0, !- Cooling Minimum Air Flow Fraction DesignDay, !- Heating Design Air Flow Method 0, !- Heating Design Air Flow Rate {m3/s} , !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2} , !- Heating Maximum Air Flow {m3/s} 0; !- Heating Maximum Air Flow Fraction DesignSpecification:OutdoorAir, SZ DSOA Zone1 Office, !- Name Flow/Area, !- Outdoor Air Method 0.0, !- Outdoor Air Flow per Person {m3/s-person} 0.000431801, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2} 0; !- Outdoor Air Flow per Zone {m3/s} Sizing:Zone, Zone2 Fine Storage, !- Zone or ZoneList Name SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method 14, !- Zone Cooling Design Supply Air Temperature {C} , !- Zone Cooling Design Supply Air Temperature Difference {deltaC} SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method 50, !- Zone Heating Design Supply Air Temperature {C} , !- Zone Heating Design Supply Air Temperature Difference {deltaC} 0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir} 0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir} SZ DSOA Zone2 Fine Storage, !- Design Specification Outdoor Air Object Name , !- Zone Heating Sizing Factor , !- Zone Cooling Sizing Factor DesignDay, !- Cooling Design Air Flow Method 0, !- Cooling Design Air Flow Rate {m3/s} , !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2} , !- Cooling Minimum Air Flow {m3/s} 0, !- Cooling Minimum Air Flow Fraction DesignDay, !- Heating Design Air Flow Method 0, !- Heating Design Air Flow Rate {m3/s} , !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2} , !- Heating Maximum Air Flow {m3/s} 0; !- Heating Maximum Air Flow Fraction DesignSpecification:OutdoorAir, SZ DSOA Zone2 Fine Storage, !- Name Flow/Area, !- Outdoor Air Method 0, !- Outdoor Air Flow per Person {m3/s-person} 0.000304801, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2} 0; !- Outdoor Air Flow per Zone {m3/s} Sizing:Zone, Zone3 Bulk Storage, !- Zone or ZoneList Name SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method 12.78, !- Zone Cooling Design Supply Air Temperature {C} , !- Zone Cooling Design Supply Air Temperature Difference {deltaC} SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method 43.3333344812747, !- Zone Heating Design Supply Air Temperature {C} , !- Zone Heating Design Supply Air Temperature Difference {deltaC} 0.009, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir} 0.016, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir} SZ DSOA Zone3 Bulk Storage, !- Design Specification Outdoor Air Object Name , !- Zone Heating Sizing Factor , !- Zone Cooling Sizing Factor DesignDay, !- Cooling Design Air Flow Method , !- Cooling Design Air Flow Rate {m3/s} 0, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2} , !- Cooling Minimum Air Flow {m3/s} , !- Cooling Minimum Air Flow Fraction DesignDay, !- Heating Design Air Flow Method , !- Heating Design Air Flow Rate {m3/s} 0, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2} 0, !- Heating Maximum Air Flow {m3/s} ; !- Heating Maximum Air Flow Fraction DesignSpecification:OutdoorAir, SZ DSOA Zone3 Bulk Storage, !- Name Flow/Area, !- Outdoor Air Method 0, !- Outdoor Air Flow per Person {m3/s-person} 0.000304801, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2} 0; !- Outdoor Air Flow per Zone {m3/s} !- =========== ALL OBJECTS IN CLASS: SYSTEM SIZING =========== Sizing:System, PSZ-Office, !- AirLoop Name Sensible, !- Type of Load to Size On autosize, !- Design Outdoor Air Flow Rate {m3/s} 1, !- Central Heating Maximum System Air Flow Ratio 7, !- Preheat Design Temperature {C} 0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir} 11.0, !- Precool Design Temperature {C} 0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir} 12, !- Central Cooling Design Supply Air Temperature {C} 40, !- Central Heating Design Supply Air Temperature {C} Coincident, !- Type of Zone Sum to Use No, !- 100% Outdoor Air in Cooling No, !- 100% Outdoor Air in Heating 0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir} 0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir} DesignDay, !- Cooling Supply Air Flow Rate Method 0, !- Cooling Supply Air Flow Rate {m3/s} , !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate , !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W} DesignDay, !- Heating Supply Air Flow Rate Method 0, !- Heating Supply Air Flow Rate {m3/s} , !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Heating Fraction of Autosized Heating Supply Air Flow Rate , !- Heating Fraction of Autosized Cooling Supply Air Flow Rate , !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W} ZoneSum, !- System Outdoor Air Method 1.0, !- Zone Maximum Outdoor Air Fraction CoolingDesignCapacity, !- Cooling Design Capacity Method autosize, !- Cooling Design Capacity {W} , !- Cooling Design Capacity Per Floor Area {W/m2} , !- Fraction of Autosized Cooling Design Capacity HeatingDesignCapacity, !- Heating Design Capacity Method autosize, !- Heating Design Capacity {W} , !- Heating Design Capacity Per Floor Area {W/m2} , !- Fraction of Autosized Heating Design Capacity OnOff; !- Central Cooling Capacity Control Method Sizing:System, PSZ-Fine Storage, !- AirLoop Name Sensible, !- Type of Load to Size On autosize, !- Design Outdoor Air Flow Rate {m3/s} 1, !- Central Heating Maximum System Air Flow Ratio 7, !- Preheat Design Temperature {C} 0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir} 11.0, !- Precool Design Temperature {C} 0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir} 12, !- Central Cooling Design Supply Air Temperature {C} 40, !- Central Heating Design Supply Air Temperature {C} Coincident, !- Type of Zone Sum to Use No, !- 100% Outdoor Air in Cooling No, !- 100% Outdoor Air in Heating 0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir} 0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir} DesignDay, !- Cooling Supply Air Flow Rate Method 0, !- Cooling Supply Air Flow Rate {m3/s} , !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate , !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W} DesignDay, !- Heating Supply Air Flow Rate Method 0, !- Heating Supply Air Flow Rate {m3/s} , !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Heating Fraction of Autosized Heating Supply Air Flow Rate , !- Heating Fraction of Autosized Cooling Supply Air Flow Rate , !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W} ZoneSum, !- System Outdoor Air Method 1.0, !- Zone Maximum Outdoor Air Fraction CoolingDesignCapacity, !- Cooling Design Capacity Method autosize, !- Cooling Design Capacity {W} , !- Cooling Design Capacity Per Floor Area {W/m2} , !- Fraction of Autosized Cooling Design Capacity HeatingDesignCapacity, !- Heating Design Capacity Method autosize, !- Heating Design Capacity {W} , !- Heating Design Capacity Per Floor Area {W/m2} , !- Fraction of Autosized Heating Design Capacity OnOff; !- Central Cooling Capacity Control Method !- =========== ALL OBJECTS IN CLASS: CURVE:BIQUADRATIC =========== Curve:Biquadratic, PSZ-AC_Unitary_PackagecoolCapFT, !- Name 0.942587793, !- Coefficient1 Constant 0.009543347, !- Coefficient2 x 0.00068377, !- Coefficient3 x**2 -0.011042676, !- Coefficient4 y 0.000005249, !- Coefficient5 y**2 -0.00000972, !- Coefficient6 x*y 12.77778, !- Minimum Value of x 23.88889, !- Maximum Value of x 23.88889, !- Minimum Value of y 46.11111; !- Maximum Value of y Curve:Biquadratic, PSZ-AC_Unitary_PackagecoolEIRFT, !- Name 0.342414409, !- Coefficient1 Constant 0.034885008, !- Coefficient2 x -0.0006237, !- Coefficient3 x**2 0.004977216, !- Coefficient4 y 0.000437951, !- Coefficient5 y**2 -0.000728028, !- Coefficient6 x*y 12.77778, !- Minimum Value of x 23.88889, !- Maximum Value of x 23.88889, !- Minimum Value of y 46.11111; !- Maximum Value of y !- =========== ALL OBJECTS IN CLASS: CURVE:CUBIC =========== Curve:Cubic, PSZ-Office Heating Coil PLF-FPLR, !- Name 0.8, !- Coefficient1 Constant 0.2, !- Coefficient2 x 0, !- Coefficient3 x**2 0, !- Coefficient4 x**3 0, !- Minimum Value of x 1; !- Maximum Value of x Curve:Cubic, PSZ-Fine Storage Heating Coil PLF-FPLR, !- Name 0.8, !- Coefficient1 Constant 0.2, !- Coefficient2 x 0, !- Coefficient3 x**2 0, !- Coefficient4 x**3 0, !- Minimum Value of x 1; !- Maximum Value of x !- =========== ALL OBJECTS IN CLASS: CURVE:QUADRATIC =========== Curve:Quadratic, PSZ-AC_Unitary_PackagecoolFFF, !- Name 0.8, !- Coefficient1 Constant 0.2, !- Coefficient2 x 0, !- Coefficient3 x**2 0.5, !- Minimum Value of x 1.5; !- Maximum Value of x Curve:Quadratic, PSZ-AC_Unitary_PackagecoolEIRFFF, !- Name 1.1552, !- Coefficient1 Constant -0.1808, !- Coefficient2 x 0.0256, !- Coefficient3 x**2 0.5, !- Minimum Value of x 1.5; !- Maximum Value of x Curve:Quadratic, PSZ-AC_Unitary_PackagecoolPLR, !- Name 0.85, !- Coefficient1 Constant 0.15, !- Coefficient2 x 0, !- Coefficient3 x**2 0, !- Minimum Value of x 1; !- Maximum Value of x !- =========== ALL OBJECTS IN CLASS: NODE LIST =========== NodeList, Zone3Inlets, !- Name Zone3UnitHeaterAirOutletNode; !- Node 1 Name NodeList, Zone3Exhausts, !- Name Zone3UnitHeaterAirInletNode; !- Node 1 Name !- =========== ALL OBJECTS IN CLASS: BRANCH LIST =========== BranchList, PSZ-Office Branches, !- Name PSZ-Office Main Branch; !- Branch 1 Name BranchList, PSZ-Fine Storage Branches, !- Name PSZ-Fine Storage Main Branch; !- Branch 1 Name !- =========== ALL OBJECTS IN CLASS: BRANCH =========== Branch, PSZ-Office Main Branch, !- Name , !- Pressure Drop Curve Name AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type PSZ-Office OA System, !- Component 1 Name PSZ-Office Air Loop Inlet, !- Component 1 Inlet Node Name PSZ-Office Mixed Air Outlet, !- Component 1 Outlet Node Name AirLoopHVAC:UnitarySystem, !- Component 2 Object Type PSZ-Office_Unitary_Package_DX, !- Component 2 Name PSZ-Office Mixed Air Outlet, !- Component 2 Inlet Node Name PSZ-Office Air Loop Outlet; !- Component 2 Outlet Node Name Branch, PSZ-Fine Storage Main Branch, !- Name , !- Pressure Drop Curve Name AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type PSZ-Fine Storage OA System, !- Component 1 Name PSZ-Fine Storage Air Loop Inlet, !- Component 1 Inlet Node Name PSZ-Fine Storage Mixed Air Outlet, !- Component 1 Outlet Node Name AirLoopHVAC:UnitarySystem, !- Component 2 Object Type PSZ-Fine_Unitary_Package_DX, !- Component 2 Name PSZ-Fine Storage Mixed Air Outlet, !- Component 2 Inlet Node Name PSZ-Fine Storage Air Loop Outlet; !- Component 2 Outlet Node Name !- =========== ALL OBJECTS IN CLASS: AIR PRIMARY LOOP =========== AirLoopHVAC, PSZ-Office, !- Name , !- Controller List Name PSZ-Office Availability Managers, !- Availability Manager List Name autosize, !- Design Supply Air Flow Rate {m3/s} PSZ-Office Branches, !- Branch List Name , !- Connector List Name PSZ-Office Air Loop Inlet, !- Supply Side Inlet Node Name PSZ-Office Return Air Outlet, !- Demand Side Outlet Node Name PSZ-Office Supply Path Inlet, !- Demand Side Inlet Node Names PSZ-Office Air Loop Outlet; !- Supply Side Outlet Node Names AirLoopHVAC, PSZ-Fine Storage, !- Name , !- Controller List Name PSZ-Fine Storage Availability Managers, !- Availability Manager List Name autosize, !- Design Supply Air Flow Rate {m3/s} PSZ-Fine Storage Branches, !- Branch List Name , !- Connector List Name PSZ-Fine Storage Air Loop Inlet, !- Supply Side Inlet Node Name PSZ-Fine Storage Return Air Outlet, !- Demand Side Outlet Node Name PSZ-Fine Storage Supply Path Inlet, !- Demand Side Inlet Node Names PSZ-Fine Storage Air Loop Outlet; !- Supply Side Outlet Node Names !- =========== ALL OBJECTS IN CLASS: CONTROLLER LIST =========== AirLoopHVAC:ControllerList, PSZ-Office OA System Controllers, !- Name Controller:OutdoorAir, !- Controller 1 Object Type PSZ-Office OA Controller;!- Controller 1 Name AirLoopHVAC:ControllerList, PSZ-Fine Storage OA System Controllers, !- Name Controller:OutdoorAir, !- Controller 1 Object Type PSZ-Fine Storage OA Controller; !- Controller 1 Name !- =========== ALL OBJECTS IN CLASS: AIR LOOP EQUIPMENT LIST =========== AirLoopHVAC:OutdoorAirSystem:EquipmentList, PSZ-Office OA System Equipment, !- Name OutdoorAir:Mixer, !- Component 1 Object Type PSZ-Office OA Mixing Box;!- Component 1 Name AirLoopHVAC:OutdoorAirSystem:EquipmentList, PSZ-Fine Storage OA System Equipment, !- Name OutdoorAir:Mixer, !- Component 1 Object Type PSZ-Fine Storage OA Mixing Box; !- Component 1 Name !- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR SYSTEM =========== AirLoopHVAC:OutdoorAirSystem, PSZ-Office OA System, !- Name PSZ-Office OA System Controllers, !- Controller List Name PSZ-Office OA System Equipment, !- Outdoor Air Equipment List Name PSZ-Office Availability Managers; !- Availability Manager List Name AirLoopHVAC:OutdoorAirSystem, PSZ-Fine Storage OA System, !- Name PSZ-Fine Storage OA System Controllers, !- Controller List Name PSZ-Fine Storage OA System Equipment, !- Outdoor Air Equipment List Name PSZ-Fine Storage Availability Managers; !- Availability Manager List Name !- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR NODE =========== OutdoorAir:Node, Zone3UnitHeaterOAInNode, !- Name -1.0; !- Height Above Ground {m} OutdoorAir:Node, PSZ-Office Cooling Coil Condenser Inlet, !- Name -1; !- Height Above Ground {m} OutdoorAir:Node, PSZ-Fine Storage Cooling Coil Condenser Inlet, !- Name -1; !- Height Above Ground {m} !- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR INLET NODE LIST =========== OutdoorAir:NodeList, PSZ-Office Outside Air Inlet; !- Node or NodeList Name 1 OutdoorAir:NodeList, PSZ-Fine Storage Outside Air Inlet; !- Node or NodeList Name 1 !- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR MIXER =========== OutdoorAir:Mixer, PSZ-Office OA Mixing Box,!- Name PSZ-Office Mixed Air Outlet, !- Mixed Air Node Name PSZ-Office Outside Air Inlet, !- Outdoor Air Stream Node Name PSZ-Office Relief Air Outlet, !- Relief Air Stream Node Name PSZ-Office Air Loop Inlet; !- Return Air Stream Node Name OutdoorAir:Mixer, PSZ-Fine Storage OA Mixing Box, !- Name PSZ-Fine Storage Mixed Air Outlet, !- Mixed Air Node Name PSZ-Fine Storage Outside Air Inlet, !- Outdoor Air Stream Node Name PSZ-Fine Storage Relief Air Outlet, !- Relief Air Stream Node Name PSZ-Fine Storage Air Loop Inlet; !- Return Air Stream Node Name !- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER LIST =========== AvailabilityManagerAssignmentList, PSZ-Office Availability Managers, !- Name AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type PSZ-Office Availability; !- Availability Manager 1 Name AvailabilityManagerAssignmentList, PSZ-Fine Storage Availability Managers, !- Name AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type PSZ-Fine Storage Availability; !- Availability Manager 1 Name !- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER:SCHEDULED =========== AvailabilityManager:NightCycle, PSZ-Office Availability, !- Name COMPACT HVAC-ALWAYS 1, !- Applicability Schedule Name FanSched, !- Fan Schedule Name CycleOnAny, !- Control Type 1.0, !- Thermostat Tolerance {deltaC} FixedRunTime, !- Cycling Run Time Control Type 1800; !- Cycling Run Time {s} AvailabilityManager:NightCycle, PSZ-Fine Storage Availability, !- Name COMPACT HVAC-ALWAYS 1, !- Applicability Schedule Name FanSched, !- Fan Schedule Name CycleOnAny, !- Control Type 1.0, !- Thermostat Tolerance {deltaC} FixedRunTime, !- Cycling Run Time Control Type 1800; !- Cycling Run Time {s} !- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:HEATING & COOLING =========== SetpointManager:SingleZone:Heating, PSZ-Office Supply Air Temp Manager - Htg, !- Name Temperature, !- Control Variable 12.7777781162733, !- Minimum Supply Air Temperature {C} 43.3333344812747, !- Maximum Supply Air Temperature {C} Zone1 Office, !- Control Zone Name Zone1 Office Zone Air Node, !- Zone Node Name Zone1 Office Zone Equip Inlet, !- Zone Inlet Node Name PSZ-Office Heating Coil Outlet; !- Setpoint Node or NodeList Name SetpointManager:SingleZone:Heating, PSZ-Fine Storage Supply Air Temp Manager - Htg, !- Name Temperature, !- Control Variable 12.7777781162733, !- Minimum Supply Air Temperature {C} 43.3333344812747, !- Maximum Supply Air Temperature {C} Zone2 Fine Storage, !- Control Zone Name Zone2 Fine Storage Zone Air Node, !- Zone Node Name Zone2 Fine Storage Zone Equip Inlet, !- Zone Inlet Node Name PSZ-Fine Storage Heating Coil Outlet; !- Setpoint Node or NodeList Name SetpointManager:SingleZone:Cooling, PSZ-Office Supply Air Temp Manager - Clg, !- Name Temperature, !- Control Variable 12.7777781162733, !- Minimum Supply Air Temperature {C} 43.3333344812747, !- Maximum Supply Air Temperature {C} Zone1 Office, !- Control Zone Name Zone1 Office Zone Air Node, !- Zone Node Name Zone1 Office Zone Equip Inlet, !- Zone Inlet Node Name PSZ-Office Air Loop Outlet; !- Setpoint Node or NodeList Name SetpointManager:SingleZone:Cooling, PSZ-Fine Storage Supply Air Temp Manager - Clg, !- Name Temperature, !- Control Variable 12.7777781162733, !- Minimum Supply Air Temperature {C} 43.3333344812747, !- Maximum Supply Air Temperature {C} Zone2 Fine Storage, !- Control Zone Name Zone2 Fine Storage Zone Air Node, !- Zone Node Name Zone2 Fine Storage Zone Equip Inlet, !- Zone Inlet Node Name PSZ-Fine Storage Air Loop Outlet; !- Setpoint Node or NodeList Name !- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:MIXED AIR =========== SetpointManager:MixedAir, PSZ-Office OAMixed Air Temp Manager, !- Name Temperature, !- Control Variable PSZ-Office Air Loop Outlet, !- Reference Setpoint Node Name PSZ-Office Mixed Air Outlet, !- Fan Inlet Node Name PSZ-Office Supply Fan Outlet, !- Fan Outlet Node Name PSZ-Office Mixed Air Outlet; !- Setpoint Node or NodeList Name SetpointManager:MixedAir, PSZ-Fine Storage OAMixed Air Temp Manager, !- Name Temperature, !- Control Variable PSZ-Fine Storage Air Loop Outlet, !- Reference Setpoint Node Name PSZ-Fine Storage Mixed Air Outlet, !- Fan Inlet Node Name PSZ-Fine Storage Supply Fan Outlet, !- Fan Outlet Node Name PSZ-Fine Storage Mixed Air Outlet; !- Setpoint Node or NodeList Name !- =========== ALL OBJECTS IN CLASS: CONTROLLER:OUTSIDE AIR =========== Controller:OutdoorAir, PSZ-Office OA Controller,!- Name PSZ-Office Relief Air Outlet, !- Relief Air Outlet Node Name PSZ-Office Air Loop Inlet, !- Return Air Node Name PSZ-Office Mixed Air Outlet, !- Mixed Air Node Name PSZ-Office Outside Air Inlet, !- Actuator Node Name autosize, !- Minimum Outdoor Air Flow Rate {m3/s} autosize, !- Maximum Outdoor Air Flow Rate {m3/s} NoEconomizer, !- Economizer Control Type ModulateFlow, !- Economizer Control Action Type , !- Economizer Maximum Limit Dry-Bulb Temperature {C} , !- Economizer Maximum Limit Enthalpy {J/kg} , !- Economizer Maximum Limit Dewpoint Temperature {C} , !- Electronic Enthalpy Limit Curve Name , !- Economizer Minimum Limit Dry-Bulb Temperature {C} LockoutWithHeating, !- Lockout Type FixedMinimum, !- Minimum Limit Type MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name , !- Minimum Fraction of Outdoor Air Schedule Name SZ_system_OA_Max_Frac_SCH; !- Maximum Fraction of Outdoor Air Schedule Name Controller:OutdoorAir, PSZ-Fine Storage OA Controller, !- Name PSZ-Fine Storage Relief Air Outlet, !- Relief Air Outlet Node Name PSZ-Fine Storage Air Loop Inlet, !- Return Air Node Name PSZ-Fine Storage Mixed Air Outlet, !- Mixed Air Node Name PSZ-Fine Storage Outside Air Inlet, !- Actuator Node Name autosize, !- Minimum Outdoor Air Flow Rate {m3/s} autosize, !- Maximum Outdoor Air Flow Rate {m3/s} DifferentialDryBulb, !- Economizer Control Type ModulateFlow, !- Economizer Control Action Type , !- Economizer Maximum Limit Dry-Bulb Temperature {C} , !- Economizer Maximum Limit Enthalpy {J/kg} , !- Economizer Maximum Limit Dewpoint Temperature {C} , !- Electronic Enthalpy Limit Curve Name , !- Economizer Minimum Limit Dry-Bulb Temperature {C} LockoutWithHeating, !- Lockout Type FixedMinimum, !- Minimum Limit Type MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name , !- Minimum Fraction of Outdoor Air Schedule Name SZ_system_OA_Max_Frac_SCH; !- Maximum Fraction of Outdoor Air Schedule Name !- =========== ALL OBJECTS IN CLASS: CONTROLLED ZONE EQUIP CONFIGURATION =========== ZoneHVAC:EquipmentConnections, Zone1 Office, !- Zone Name Zone1 Office Equipment, !- Zone Conditioning Equipment List Name Zone1 Office Zone Equip Inlet, !- Zone Air Inlet Node or NodeList Name , !- Zone Air Exhaust Node or NodeList Name Zone1 Office Zone Air Node, !- Zone Air Node Name Zone1 Office Return Outlet; !- Zone Return Air Node or NodeList Name ZoneHVAC:EquipmentConnections, Zone2 Fine Storage, !- Zone Name Zone2 Fine Storage Equipment, !- Zone Conditioning Equipment List Name Zone2 Fine Storage Zone Equip Inlet, !- Zone Air Inlet Node or NodeList Name , !- Zone Air Exhaust Node or NodeList Name Zone2 Fine Storage Zone Air Node, !- Zone Air Node Name Zone2 Fine Storage Return Outlet; !- Zone Return Air Node or NodeList Name ZoneHVAC:EquipmentConnections, Zone3 Bulk Storage, !- Zone Name Zone3Equipment, !- Zone Conditioning Equipment List Name Zone3Inlets, !- Zone Air Inlet Node or NodeList Name Zone3Exhausts, !- Zone Air Exhaust Node or NodeList Name Zone 3 Node, !- Zone Air Node Name Zone 3 Outlet Node; !- Zone Return Air Node or NodeList Name !- =========== ALL OBJECTS IN CLASS: ZONE EQUIPMENT LIST =========== ZoneHVAC:EquipmentList, Zone1 Office Equipment, !- Name SequentialLoad, !- Load Distribution Scheme AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type Zone1 Office Direct Air, !- Zone Equipment 1 Name 1, !- Zone Equipment 1 Cooling Sequence 1; !- Zone Equipment 1 Heating or No-Load Sequence ZoneHVAC:EquipmentList, Zone2 Fine Storage Equipment, !- Name SequentialLoad, !- Load Distribution Scheme AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type Zone2 Fine Storage Direct Air, !- Zone Equipment 1 Name 1, !- Zone Equipment 1 Cooling Sequence 1; !- Zone Equipment 1 Heating or No-Load Sequence ZoneHVAC:EquipmentList, Zone3Equipment, !- Name SequentialLoad, !- Load Distribution Scheme ZoneHVAC:UnitHeater, !- Zone Equipment 1 Object Type Zone3UnitHeater, !- Zone Equipment 1 Name 1, !- Zone Equipment 1 Cooling Priority 1, !- Zone Equipment 1 Heating Priority ZoneHVAC:HighTemperatureRadiant, !- Zone Equipment 2 Object Type Zone3HiRadiant, !- Zone Equipment 2 Name 2, !- Zone Equipment 2 Cooling Priority 2; !- Zone Equipment 2 Heating Priority !- =========== ALL OBJECTS IN CLASS: UNIT HEATER =========== ZoneHVAC:UnitHeater, Zone3UnitHeater, !- Name UnitHeaterAvailability, !- availability schedule !- Availability Schedule Name Zone3UnitHeaterAirInletNode, !- Air Inlet Node Name Zone3UnitHeaterAirOutletNode, !- Air Outlet Node Name Fan:ConstantVolume, !- Supply Air Fan Object Type: August 12, 2013: Changed from Fan:ONOff to Fan:ConstantVolume during V6 to V8 upgrade Zone3UnitHeaterFan, !- Supply Air Fan Name autosize, !- Maximum Supply Air Flow Rate {m3/s} Coil:Heating:Fuel, !- Heating Coil Object Type Zone3UnitHeaterHeatingCoil, !- Heating Coil Name , !- Supply Air Fan Operating Mode Schedule Name No, !- Supply Air Fan Operation During No Heating , !- Maximum Hot Water or Steam Flow Rate {m3/s} , !- Minimum Hot Water or Steam Flow Rate {m3/s} 0.001, !- Heating Convergence Tolerance ; !- Availability Manager List Name !- =========== ALL OBJECTS IN CLASS: FURNACE:HEATCOOL =========== AirLoopHVAC:UnitarySystem, PSZ-Office_Unitary_Package_DX, !- Name Load, !- Control Type Zone1 Office, !- Controlling Zone or Thermostat Location None, !- Dehumidification Control Type COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name PSZ-Office Mixed Air Outlet, !- DX Cooling Coil System Inlet Node Name PSZ-Office Air Loop Outlet, !- DX Cooling Coil System Outlet Node Name Fan:SystemModel, !- Supply Fan Object Type PSZ-Office_addAQ Supply Fan, !- Supply Fan Name BlowThrough, !- Fan Placement FanSched, !- Supply Air Fan Operating Mode Schedule Name Coil:Heating:Fuel, !- Heating Coil Object Type PSZ-Office Heating Coil, !- Heating Coil Name 1, !- DX Heating Coil Sizing Ratio Coil:Cooling:DX:MultiSpeed, !- Cooling Coil Object Type PSZ-Office Cooling Coil, !- Cooling Coil Name No, !- Use DOAS DX Cooling Coil 2, !- Minimum Supply Air Temperature {C} SensibleOnlyLoadControl, !- Latent Load Control , !- Supplemental Heating Coil Object Type , !- Supplemental Heating Coil Name SupplyAirFlowRate, !- Cooling Supply Air Flow Rate Method AUTOSIZE, !- Cooling Supply Air Flow Rate {m3/s} , !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate , !- Cooling Supply Air Flow Rate Per Unit of Capacity {m3/s-W} SupplyAirFlowRate, !- Heating Supply Air Flow Rate Method AUTOSIZE, !- Heating Supply Air Flow Rate {m3/s} , !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Heating Fraction of Autosized Heating Supply Air Flow Rate , !- Heating Supply Air Flow Rate Per Unit of Capacity {m3/s-W} SupplyAirFlowRate, !- No Load Supply Air Flow Rate Method AUTOSIZE, !- No Load Supply Air Flow Rate {m3/s} , !- No Load Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- No Load Fraction of Autosized Cooling Supply Air Flow Rate , !- No Load Fraction of Autosized Heating Supply Air Flow Rate , !- No Load Supply Air Flow Rate Per Unit of Capacity During Cooling Operation {m3/s-W} , !- No Load Supply Air Flow Rate Per Unit of Capacity During Heating Operation {m3/s-W} AUTOSIZE, !- Maximum Supply Air Temperature {C} , !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C} , !- Outdoor Dry-Bulb Temperature Sensor Node Name , !- Maximum Cycling Rate {cycles/hr} , !- Heat Pump Time Constant {s} , !- Fraction of On-Cycle Power Use , !- Heat Pump Fan Delay Time {s} , !- Ancillary On-Cycle Electric Power {W} , !- Ancillary Off-Cycle Electric Power {W} , !- Design Heat Recovery Water Flow Rate {m3/s} , !- Maximum Temperature for Heat Recovery {C} , !- Heat Recovery Water Inlet Node Name , !- Heat Recovery Water Outlet Node Name UnitarySystemPerformance:Multispeed, !- Design Specification Multispeed Object Type PSZ-Office_Unitary_Package_DX_Perf; !- Design Specification Multispeed Object Name UnitarySystemPerformance:Multispeed, PSZ-Office_Unitary_Package_DX_Perf, !- Name 2, !- Number of Speeds for Heating 2, !- Number of Speeds for Cooling No, !- Single Mode Operation 1.0, !- No Load or Cooling Speed 1 Supply Air Flow Rate Ratio 1, !- Heating Speed 1 Supply Air Flow Ratio 1.0, !- No Load or Cooling Speed 1 Supply Air Flow Rate Ratio 1, !- Heating Speed 2 Supply Air Flow Ratio 1; !- Cooling Speed 2 Supply Air Flow Ratio AirLoopHVAC:UnitarySystem, PSZ-Fine_Unitary_Package_DX, !- Name Load, !- Control Type Zone2 Fine Storage, !- Controlling Zone or Thermostat Location None, !- Dehumidification Control Type COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name PSZ-Fine Storage Mixed Air Outlet, !- DX Cooling Coil System Inlet Node Name PSZ-Fine Storage Air Loop Outlet, !- DX Cooling Coil System Outlet Node Name Fan:SystemModel, !- Supply Fan Object Type PSZ-Fine Storage_addAQ Supply Fan, !- Supply Fan Name BlowThrough, !- Fan Placement FanSched, !- Supply Air Fan Operating Mode Schedule Name Coil:Heating:Fuel, !- Heating Coil Object Type PSZ-Fine Storage Heating Coil, !- Heating Coil Name 1, !- DX Heating Coil Sizing Ratio Coil:Cooling:DX:MultiSpeed, !- Cooling Coil Object Type PSZ-Fine Storage Cooling Coil, !- Cooling Coil Name No, !- Use DOAS DX Cooling Coil 2, !- Minimum Supply Air Temperature {C} SensibleOnlyLoadControl, !- Latent Load Control , !- Supplemental Heating Coil Object Type , !- Supplemental Heating Coil Name SupplyAirFlowRate, !- Cooling Supply Air Flow Rate Method AUTOSIZE, !- Cooling Supply Air Flow Rate {m3/s} , !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate , !- Cooling Supply Air Flow Rate Per Unit of Capacity {m3/s-W} SupplyAirFlowRate, !- Heating Supply Air Flow Rate Method AUTOSIZE, !- Heating Supply Air Flow Rate {m3/s} , !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- Heating Fraction of Autosized Heating Supply Air Flow Rate , !- Heating Supply Air Flow Rate Per Unit of Capacity {m3/s-W} SupplyAirFlowRate, !- No Load Supply Air Flow Rate Method AUTOSIZE, !- No Load Supply Air Flow Rate {m3/s} , !- No Load Supply Air Flow Rate Per Floor Area {m3/s-m2} , !- No Load Fraction of Autosized Cooling Supply Air Flow Rate , !- No Load Fraction of Autosized Heating Supply Air Flow Rate , !- No Load Supply Air Flow Rate Per Unit of Capacity During Cooling Operation {m3/s-W} , !- No Load Supply Air Flow Rate Per Unit of Capacity During Heating Operation {m3/s-W} AUTOSIZE, !- Maximum Supply Air Temperature {C} , !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C} , !- Outdoor Dry-Bulb Temperature Sensor Node Name , !- Maximum Cycling Rate {cycles/hr} , !- Heat Pump Time Constant {s} , !- Fraction of On-Cycle Power Use , !- Heat Pump Fan Delay Time {s} , !- Ancillary On-Cycle Electric Power {W} , !- Ancillary Off-Cycle Electric Power {W} , !- Design Heat Recovery Water Flow Rate {m3/s} , !- Maximum Temperature for Heat Recovery {C} , !- Heat Recovery Water Inlet Node Name , !- Heat Recovery Water Outlet Node Name UnitarySystemPerformance:Multispeed, !- Design Specification Multispeed Object Type PSZ-Fine_Unitary_Package_DX_Perf; !- Design Specification Multispeed Object Name UnitarySystemPerformance:Multispeed, PSZ-Fine_Unitary_Package_DX_Perf, !- Name 2, !- Number of Speeds for Heating 2, !- Number of Speeds for Cooling No, !- Single Mode Operation 1.0, !- No Load or Cooling Speed 1 Supply Air Flow Rate Ratio 1, !- Heating Speed 1 Supply Air Flow Ratio 1.0, !- No Load or Cooling Speed 1 Supply Air Flow Rate Ratio 1, !- Heating Speed 2 Supply Air Flow Ratio 1; !- Cooling Speed 2 Supply Air Flow Ratio !- =========== ALL OBJECTS IN CLASS: DIRECT AIR =========== AirTerminal:SingleDuct:Uncontrolled, Zone1 Office Direct Air, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name Zone1 Office Zone Equip Inlet, !- Zone Supply Air Node Name autosize; !- Maximum Air Flow Rate {m3/s} AirTerminal:SingleDuct:Uncontrolled, Zone2 Fine Storage Direct Air, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name Zone2 Fine Storage Zone Equip Inlet, !- Zone Supply Air Node Name autosize; !- Maximum Air Flow Rate {m3/s} !- =========== ALL OBJECTS IN CLASS: HIGH TEMP RADIANT SYSTEM =========== ZoneHVAC:HighTemperatureRadiant, Zone3HiRadiant, !- Name Always Off Schedule, !- availability schedule !- Availability Schedule Name Zone3 Bulk Storage, !- Zone Name HeatingDesignCapacity, !- Heating Design Capacity Method autosize, !- Maximum Power Input {W} , !- Heating Design Capacity Per Floor Area {W/m2} , !- Fraction of Autosized Heating Design Capacity NaturalGas, !- Fuel Type 0.7925, !- Combustion Efficiency 0.8, !- Fraction of Input Converted to Radiant Energy 0, !- Fraction of Input Converted to Latent Energy 0, !- Fraction of Input that Is Lost OperativeTemperature, !- Temperature Control Type 2, !- Heating Throttling Range {deltaC} Bulk Storage Heating Setpoint Schedule, !- Heating Setpoint Temperature Schedule Name 0.05, !- Fraction of Radiant Energy Incident on People Bulk Storage Right Wall, !- Surface 1 Name 0.05, !- Fraction of Radiant Energy to Surface 1 Bulk Storage Rear Wall, !- Surface 2 Name 0.05, !- Fraction of Radiant Energy to Surface 2 Bulk Storage Left Wall, !- Surface 3 Name 0.05, !- Fraction of Radiant Energy to Surface 3 Bulk Storage Floor, !- Surface 4 Name 0.8; !- Fraction of Radiant Energy to Surface 4 !- =========== ALL OBJECTS IN CLASS: ZONE CONTROL:THERMOSTATIC =========== ZoneControl:Thermostat, Zone1 Office Thermostat, !- Name Zone1 Office, !- Zone or ZoneList Name COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type Office Thermostat Dual SP Control; !- Control 1 Name ZoneControl:Thermostat, Zone2 Fine Storage Thermostat, !- Name Zone2 Fine Storage, !- Zone or ZoneList Name COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type Fine Storage Thermostat Dual SP Control; !- Control 1 Name ZoneControl:Thermostat, Zone 3 Thermostat, !- Name Zone3 Bulk Storage, !- Zone or ZoneList Name ZoneControlSchedule, !- Control Type Schedule Name ThermostatSetpoint:SingleHeating, !- Control 1 Object Type Heating Setpoint with SB;!- Control 1 Name !- =========== ALL OBJECTS IN CLASS: SINGLE HEATING SETPOINT =========== ThermostatSetpoint:SingleHeating, Heating Setpoint with SB,!- Name Bulk Storage Heating Setpoint Schedule; !- Setpoint Temperature Schedule Name !- =========== ALL OBJECTS IN CLASS: DUAL SETPOINT WITH DEADBAND =========== ThermostatSetpoint:DualSetpoint, Office Thermostat Dual SP Control, !- Name Office Heating Schedule, !- Heating Setpoint Temperature Schedule Name Office Cooling Schedule; !- Cooling Setpoint Temperature Schedule Name ThermostatSetpoint:DualSetpoint, Fine Storage Thermostat Dual SP Control, !- Name Fine Storage Heating Setpoint Schedule, !- Heating Setpoint Temperature Schedule Name Fine Storage Cooling Setpoint Schedule; !- Cooling Setpoint Temperature Schedule Name !- =========== ALL OBJECTS IN CLASS: ZONE SUPPLY AIR PATH =========== AirLoopHVAC:SupplyPath, PSZ-Office Supply Path, !- Name PSZ-Office Supply Path Inlet, !- Supply Air Path Inlet Node Name AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type PSZ-Office Zone Splitter;!- Component 1 Name AirLoopHVAC:SupplyPath, PSZ-Fine Storage Supply Path, !- Name PSZ-Fine Storage Supply Path Inlet, !- Supply Air Path Inlet Node Name AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type PSZ-Fine Storage Zone Splitter; !- Component 1 Name !- =========== ALL OBJECTS IN CLASS: ZONE RETURN AIR PATH =========== AirLoopHVAC:ReturnPath, PSZ-Office Return Path, !- Name PSZ-Office Return Air Outlet, !- Return Air Path Outlet Node Name AirLoopHVAC:ZoneMixer, !- Component 1 Object Type PSZ-Office Zone Mixer; !- Component 1 Name AirLoopHVAC:ReturnPath, PSZ-Fine Storage Return Path, !- Name PSZ-Fine Storage Return Air Outlet, !- Return Air Path Outlet Node Name AirLoopHVAC:ZoneMixer, !- Component 1 Object Type PSZ-Fine Storage Zone Mixer; !- Component 1 Name !- =========== ALL OBJECTS IN CLASS: ZONE SPLITTER =========== AirLoopHVAC:ZoneSplitter, PSZ-Office Zone Splitter,!- Name PSZ-Office Supply Path Inlet, !- Inlet Node Name Zone1 Office Zone Equip Inlet; !- Outlet 1 Node Name AirLoopHVAC:ZoneSplitter, PSZ-Fine Storage Zone Splitter, !- Name PSZ-Fine Storage Supply Path Inlet, !- Inlet Node Name Zone2 Fine Storage Zone Equip Inlet; !- Outlet 1 Node Name !- =========== ALL OBJECTS IN CLASS: ZONE MIXER =========== AirLoopHVAC:ZoneMixer, PSZ-Office Zone Mixer, !- Name PSZ-Office Return Air Outlet, !- Outlet Node Name Zone1 Office Return Outlet; !- Inlet 1 Node Name AirLoopHVAC:ZoneMixer, PSZ-Fine Storage Zone Mixer, !- Name PSZ-Fine Storage Return Air Outlet, !- Outlet Node Name Zone2 Fine Storage Return Outlet; !- Inlet 1 Node Name !- =========== ALL OBJECTS IN CLASS: WATER HEATER:MIXED =========== WaterHeater:Mixed, Electric Tank, !- Name 7.57082515247699E-02, !- Tank Volume {m3} Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name 2.00000005298191, !- Deadband Temperature Difference {deltaC} 82.2222244003673, !- Maximum Temperature Limit {C} Cycle, !- Heater Control Type 6154.74805507525, !- Heater Maximum Capacity {W} 0, !- Heater Minimum Capacity {W} , !- Heater Ignition Minimum Flow Rate {m3/s} , !- Heater Ignition Delay {s} Electricity, !- Heater Fuel Type 1, !- Heater Thermal Efficiency , !- Part Load Factor Curve Name 481, !- Off Cycle Parasitic Fuel Consumption Rate {W} (SWH Enhancement) August 31, 2012 Specify pipe loss for both Off and On cycle parasitic Electricity, !- Off Cycle Parasitic Fuel Type 0, !- Off Cycle Parasitic Heat Fraction to Tank 481, !- On Cycle Parasitic Fuel Consumption Rate {W} (SWH Enhancement) August 2, 2012 Changed from blank to 308 but/h (90.27 W) to model pipe losses , !- On Cycle Parasitic Fuel Type , !- On Cycle Parasitic Heat Fraction to Tank Zone, !- Ambient Temperature Indicator , !- Ambient Temperature Schedule Name Zone1 Office, !- Ambient Temperature Zone Name , !- Ambient Temperature Outdoor Air Node Name 0.798542707, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K} , !- Off Cycle Loss Fraction to Zone 0.798542707, !- On Cycle Loss Coefficient to Ambient Temperature {W/K} , !- On Cycle Loss Fraction to Zone 8.07469089073934E-06, !- Peak Use Flow Rate {m3/s} Office DHW Schedule; !- Use Flow Rate Fraction Schedule Name !- =========== ALL OBJECTS IN CLASS: COIL:GAS:HEATING =========== Coil:Heating:Fuel, PSZ-Office Heating Coil, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name NaturalGas, !- Fuel Type 0.81, !- Burner Efficiency autosize, !- Nominal Capacity {W} PSZ-Office Supply Fan Outlet, !- Air Inlet Node Name PSZ-Office Heating Coil Outlet, !- Air Outlet Node Name , !- Temperature Setpoint Node Name 0.0, !- Parasitic Electric Load {W} PSZ-Office Heating Coil PLF-FPLR, !- Part Load Fraction Correlation Curve Name 0.0; !- Parasitic Fuel Load {W} Coil:Heating:Fuel, PSZ-Fine Storage Heating Coil, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name NaturalGas, !- Fuel Type 0.81, !- Burner Efficiency autosize, !- Nominal Capacity {W} PSZ-Fine Storage Supply Fan Outlet, !- Air Inlet Node Name PSZ-Fine Storage Heating Coil Outlet, !- Air Outlet Node Name , !- Temperature Setpoint Node Name 0.0, !- Parasitic Electric Load {W} PSZ-Fine Storage Heating Coil PLF-FPLR, !- Part Load Fraction Correlation Curve Name 0.0; !- Parasitic Fuel Load {W} Coil:Heating:Fuel, Zone3UnitHeaterHeatingCoil, !- Name Zone3HeatingCoilAvailability, !- Availability Schedule Name NaturalGas, !- Fuel Type 0.8, !- Burner Efficiency autosize, !- Nominal Capacity {W} Zone3UnitHeaterFanOutletNode, !- Air Inlet Node Name Zone3UnitHeaterAirOutletNode, !- Air Outlet Node Name , !- Temperature Setpoint Node Name 0.0, !- Parasitic Electric Load {W} , !- Part Load Fraction Correlation Curve Name 0; !- Parasitic Fuel Load {W} !- =========== ALL OBJECTS IN CLASS: COIL:DX:COOLINGBYPASSFACTOREMPIRICAL =========== Coil:Cooling:DX:MultiSpeed, PSZ-Office Cooling Coil, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name PSZ-Office Heating Coil Outlet, !- Air Inlet Node Name PSZ-Office Air Loop Outlet, !- Air Outlet Node Name , !- Condenser Air Inlet Node Name AirCooled, !- Condenser Type , !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C} , !- Supply Water Storage Tank Name , !- Condensate Collection Water Storage Tank Name No, !- Apply Part Load Fraction to Speeds Greater than 1 No, !- Apply Latent Degradation to Speeds Greater than 1 , !- Crankcase Heater Capacity {W} 10, !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C} , !- Basin Heater Capacity {W/K} 2, !- Basin Heater Setpoint Temperature {C} , !- Basin Heater Operating Schedule Name Electricity, !- Fuel Type 2, !- Number of Speeds 7704.75, !- Speed 1 Gross Rated Total Cooling Capacity {W} 0.74835, !- Speed 1 Gross Rated Sensible Heat Ratio 4.11713235489972, !- Speed 1 Gross Rated Cooling COP {W/W} 0.535673333333333, !- Speed 1 Rated Air Flow Rate {m3/s} 0, !- Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} PSZ-AC_Unitary_PackagecoolCapFT, !- Speed 1 Total Cooling Capacity Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolFFF, !- Speed 1 Total Cooling Capacity Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolEIRFT, !- Speed 1 Energy Input Ratio Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolEIRFFF, !- Speed 1 Energy Input Ratio Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolPLR, !- Speed 1 Part Load Fraction Correlation Curve Name , !- Speed 1 Nominal Time for Condensate Removal to Begin {s} , !- Speed 1 Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless} , !- Speed 1 Maximum Cycling Rate {cycles/hr} , !- Speed 1 Latent Capacity Time Constant {s} 0.2, !- Speed 1 Rated Waste Heat Fraction of Power Input {dimensionless} , !- Speed 1 Waste Heat Function of Temperature Curve Name 0.9, !- Speed 1 Evaporative Condenser Effectiveness {dimensionless} , !- Speed 1 Evaporative Condenser Air Flow Rate {m3/s} , !- Speed 1 Rated Evaporative Condenser Pump Power Consumption {W} 15409.50, !- Speed 2 Gross Rated Total Cooling Capacity {W} 0.74835, !- Speed 2 Gross Rated Sensible Heat Ratio 4.11713235489972, !- Speed 2 Gross Rated Cooling COP {W/W} 0.80351, !- Speed 2 Rated Air Flow Rate {m3/s} 0, !- Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} PSZ-AC_Unitary_PackagecoolCapFT, !- Speed 2 Total Cooling Capacity Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolFFF, !- Speed 2 Total Cooling Capacity Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolEIRFT, !- Speed 2 Energy Input Ratio Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolEIRFFF, !- Speed 2 Energy Input Ratio Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolPLR, !- Speed 2 Part Load Fraction Correlation Curve Name , !- Speed 2 Nominal Time for Condensate Removal to Begin {s} , !- Speed 2 Ratio of Initial Moisture Evaporation Rate and steady state Latent Capacity {dimensionless} , !- Speed 2 Maximum Cycling Rate {cycles/hr} , !- Speed 2 Latent Capacity Time Constant {s} 0.2, !- Speed 2 Rated Waste Heat Fraction of Power Input {dimensionless} , !- Speed 2 Waste Heat Function of Temperature Curve Name 0.9, !- Speed 2 Evaporative Condenser Effectiveness {dimensionless} , !- Speed 2 Evaporative Condenser Air Flow Rate {m3/s} ; !- Speed 2 Rated Evaporative Condenser Pump Power Consumption {W} Coil:Cooling:DX:MultiSpeed, PSZ-Fine Storage Cooling Coil, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name PSZ-Fine Storage Heating Coil Outlet, !- Air Inlet Node Name PSZ-Fine Storage Air Loop Outlet, !- Air Outlet Node Name , !- Condenser Air Inlet Node Name AirCooled, !- Condenser Type , !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C} , !- Supply Water Storage Tank Name , !- Condensate Collection Water Storage Tank Name No, !- Apply Part Load Fraction to Speeds Greater than 1 No, !- Apply Latent Degradation to Speeds Greater than 1 , !- Crankcase Heater Capacity {W} 10, !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C} , !- Basin Heater Capacity {W/K} 2, !- Basin Heater Setpoint Temperature {C} , !- Basin Heater Operating Schedule Name Electricity, !- Fuel Type 2, !- Number of Speeds 18517.4, !- Speed 1 Gross Rated Total Cooling Capacity {W} 0.67608, !- Speed 1 Gross Rated Sensible Heat Ratio 3.7988306741603, !- Speed 1 Gross Rated Cooling COP {W/W} 0.99426, !- Speed 1 Rated Air Flow Rate {m3/s} 0, !- Speed 1 Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} PSZ-AC_Unitary_PackagecoolCapFT, !- Speed 1 Total Cooling Capacity Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolFFF, !- Speed 1 Total Cooling Capacity Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolEIRFT, !- Speed 1 Energy Input Ratio Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolEIRFFF, !- Speed 1 Energy Input Ratio Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolPLR, !- Speed 1 Part Load Fraction Correlation Curve Name , !- Speed 1 Nominal Time for Condensate Removal to Begin {s} , !- Speed 1 Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless} , !- Speed 1 Maximum Cycling Rate {cycles/hr} , !- Speed 1 Latent Capacity Time Constant {s} 0.2, !- Speed 1 Rated Waste Heat Fraction of Power Input {dimensionless} , !- Speed 1 Waste Heat Function of Temperature Curve Name 0.9, !- Speed 1 Evaporative Condenser Effectiveness {dimensionless} , !- Speed 1 Evaporative Condenser Air Flow Rate {m3/s} , !- Speed 1 Rated Evaporative Condenser Pump Power Consumption {W} 37034.80, !- Speed 2 Gross Rated Total Cooling Capacity {W} 0.67608, !- Speed 2 Gross Rated Sensible Heat Ratio 3.7988306741603, !- Speed 2 Gross Rated Cooling COP {W/W} 1.49139, !- Speed 2 Rated Air Flow Rate {m3/s} 0, !- Speed 2 Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)} PSZ-AC_Unitary_PackagecoolCapFT, !- Speed 2 Total Cooling Capacity Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolFFF, !- Speed 2 Total Cooling Capacity Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolEIRFT, !- Speed 2 Energy Input Ratio Function of Temperature Curve Name PSZ-AC_Unitary_PackagecoolEIRFFF, !- Speed 2 Energy Input Ratio Function of Flow Fraction Curve Name PSZ-AC_Unitary_PackagecoolPLR, !- Speed 2 Part Load Fraction Correlation Curve Name , !- Speed 2 Nominal Time for Condensate Removal to Begin {s} , !- Speed 2 Ratio of Initial Moisture Evaporation Rate and steady state Latent Capacity {dimensionless} , !- Speed 2 Maximum Cycling Rate {cycles/hr} , !- Speed 2 Latent Capacity Time Constant {s} 0.2, !- Speed 2 Rated Waste Heat Fraction of Power Input {dimensionless} , !- Speed 2 Waste Heat Function of Temperature Curve Name 0.9, !- Speed 2 Evaporative Condenser Effectiveness {dimensionless} , !- Speed 2 Evaporative Condenser Air Flow Rate {m3/s} ; !- Speed 2 Rated Evaporative Condenser Pump Power Consumption {W} !- =========== ALL OBJECTS IN CLASS: FAN:SIMPLE:ONOFF =========== Fan:SystemModel, PSZ-Office_addAQ Supply Fan, !- Name FanSched, !- Availability Schedule Name PSZ-Office Mixed Air Outlet, !- Air Inlet Node Name PSZ-Office Supply Fan Outlet, !- Air Outlet Node Name AUTOSIZE, !- Design Maximum Air Flow Rate Discrete, !- Speed Control Method 1, !- Electric Power Minimum Flow Rate Fraction 622.5, !- Design Pressure Rise {Pa} 0.865, !- Motor Efficiency 1.0, ! Motor In Air Stream Fraction AUTOSIZE, !- Design Electric Power Consumption TotalEfficiencyAndPressure, !- Design Power Sizing Method , !- Electric Power Per Unit Flow Rate , !- Electric Power Per Unit Flow Rate Per Pressure 0.56225, !- Fan Total Efficiency , !- Electric Power Function of Flow Fraction Curve Name 622.5, !- Night Ventilation Mode Pressure Rise , !- Night Ventilation Mode Flow Fraction , !- Motor Loss Zone Name , !- Motor Loss Radiative Fraction General, !- End-Use Subcategory 1, !- Number of Speeds 1, !- Speed Flow Fraction 1; !- Electric Power Fraction Fan:SystemModel, PSZ-Fine Storage_addAQ Supply Fan, !- Name FanSched, !- Availability Schedule Name PSZ-Fine Storage Mixed Air Outlet, !- Air Inlet Node Name PSZ-Fine Storage Supply Fan Outlet, !- Air Outlet Node Name AUTOSIZE, !- Design Maximum Air Flow Rate Discrete, !- Speed Control Method 1, !- Electric Power Minimum Flow Rate Fraction 622.5, !- Design Pressure Rise {Pa} 0.895, !- Motor Efficiency 1.0, ! Motor In Air Stream Fraction AUTOSIZE, !- Design Electric Power Consumption TotalEfficiencyAndPressure, !- Design Power Sizing Method , !- Electric Power Per Unit Flow Rate , !- Electric Power Per Unit Flow Rate Per Pressure 0.58175, !- Fan Total Efficiency , !- Electric Power Function of Flow Fraction Curve Name 622.5, !- Night Ventilation Mode Pressure Rise , !- Night Ventilation Mode Flow Fraction , !- Motor Loss Zone Name , !- Motor Loss Radiative Fraction General, !- End-Use Subcategory 1, !- Number of Speeds 1, !- Speed Flow Fraction 1; !- Electric Power Fraction Fan:ConstantVolume, ! August 12, 2013: Changed from Fan:ONOff to Fan:ConstantVolume during V6 to V8 upgrade Zone3UnitHeaterFan, !- Name COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name 0.536, !- Fan Total Efficiency 49.8, !- Pressure Rise {Pa} autosize, !- Maximum Flow Rate {m3/s} 0.825, !- Motor Efficiency 1.0, !- Motor In Airstream Fraction Zone3UnitHeaterAirInletNode, !- Air Inlet Node Name Zone3UnitHeaterFanOutletNode, !- Air Outlet Node Name General; !- End-Use Subcategory !No PV for this case !- =========== ALL OBJECTS IN CLASS: OUTPUT:VARIABLE =========== ! Output:Variable,MinOA_Sched,Schedule Value,Hourly; ! Output:Variable,*,Site Outdoor Air Drybulb Temperature,Hourly; ! Output:Variable,*,Site Outdoor Air Wetbulb Temperature,Hourly; ! ! !- Outdoor Air Flow Rate for each system ! ! Output:Variable,PSZ-Office Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly; ! Output:Variable,PSZ-Fine Storage Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly; ! ! ! Return Air Flow ! ! Output:Variable,PSZ-Office Air Loop Inlet,System Node Temperature,Hourly; ! Output:Variable,PSZ-Office Air Loop Inlet,System Node Wetbulb Temperature,Hourly; ! Output:Variable,PSZ-Office Air Loop Inlet,System Node Standard Density Volume Flow Rate,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Inlet,System Node Temperature,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Inlet,System Node Wetbulb Temperature,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Inlet,System Node Standard Density Volume Flow Rate,Hourly; ! ! ! Supply Air Flow ! ! Output:Variable,PSZ-Office Air Loop Outlet,System Node Temperature,Hourly; ! Output:Variable,PSZ-Office Air Loop Outlet,System Node Wetbulb Temperature,Hourly; ! Output:Variable,PSZ-Office Air Loop Outlet,System Node Standard Density Volume Flow Rate,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Outlet,System Node Temperature,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Outlet,System Node Wetbulb Temperature,Hourly; ! Output:Variable,PSZ-Fine Storage Air Loop Outlet,System Node Standard Density Volume Flow Rate,Hourly; ! ! ! Coil Load ! ! Output:Variable,*,Air System Cooling Coil Total Cooling Energy,Hourly; ! Output:Variable,*,Air System Heating Coil Total Heating Energy,Hourly; ! ! ! Fan and Pump ! ! Output:Variable,*,Fan Electric Power,hourly; !- HVAC Average W ! Output:Variable,*,Pump Electric Power,hourly; !- HVAC Average W ! Output:Variable,*,Humidifier Electric Power,hourly; !- HVAC Average W ! ! ! SHW ! ! Output:Variable,*,Water Heater Heating Rate,Hourly; ! ! ! Utility and Submeter ! ! Output:Meter,Electricity:Facility,Hourly; ! Output:Meter,Gas:Facility,Hourly; ! Output:Meter,InteriorLights:Electricity,Hourly; ! Output:Meter,ExteriorLights:Electricity,Hourly; ! Output:Meter,InteriorEquipment:Electricity,Hourly; ! Output:Meter,ExteriorEquipment:Electricity,Hourly; ! Output:Meter,Fans:Electricity,Hourly; ! Output:Meter,Pumps:Electricity,Hourly; ! Output:Meter,Heating:Electricity,Hourly; ! Output:Meter,Cooling:Electricity,Hourly; ! Output:Meter,HeatRejection:Electricity,Hourly; ! Output:Meter,Humidifier:Electricity,Hourly; ! Output:Meter,HeatRecovery:Electricity,Hourly; ! Output:Meter,DHW:Electricity,Hourly; ! Output:Meter,Cogeneration:Electricity,Hourly; ! Output:Meter,Refrigeration:Electricity,Hourly; ! Output:Meter,WaterSystems:Electricity,Hourly; ! ! Output:Meter,InteriorLights:Gas,Hourly; ! Output:Meter,ExteriorLights:Gas,Hourly; ! Output:Meter,InteriorEquipment:Gas,Hourly; ! Output:Meter,ExteriorEquipment:Gas,Hourly; ! Output:Meter,Fans:Gas,Hourly; ! Output:Meter,Pumps:Gas,Hourly; ! Output:Meter,Heating:Gas,Hourly; ! Output:Meter,Cooling:Gas,Hourly; ! Output:Meter,HeatRejection:Gas,Hourly; ! Output:Meter,Humidifier:Gas,Hourly; ! Output:Meter,HeatRecovery:Gas,Hourly; ! Output:Meter,DHW:Gas,Hourly; ! Output:Meter,Cogeneration:Gas,Hourly; ! Output:Meter,Refrigeration:Gas,Hourly; ! Output:Meter,WaterSystems:Gas,Hourly; ! !- =========== ALL OBJECTS IN CLASS: REPORT =========== Output:Surfaces:Drawing,DXF,Triangulate3DFace; Output:VariableDictionary,Regular; Output:Constructions,Constructions; !- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:STYLE =========== OutputControl:Table:Style, CommaAndHTML; !- Unit Conversion !- =========== ALL OBJECTS IN CLASS: OUTPUTCONTROL:REPORTINGTOLERANCES =========== Output:Meter:MeterFileOnly,Electricity:Facility,Hourly; Output:Meter:MeterFileOnly,ElectricityNet:Facility,Hourly; Output:Meter:MeterFileOnly,Gas:Facility,Hourly; Output:Meter:MeterFileOnly,Electricity:Facility,Hourly; Output:Meter:MeterFileOnly,ElectricityNet:Facility,Hourly; Output:Meter:MeterFileOnly,Gas:Facility,Hourly; OutputControl:ReportingTolerances, 0.556, !- Tolerance for Time Heating Setpoint Not Met {deltaC} 0.556; !- Tolerance for Time Cooling Setpoint Not Met {deltaC} !- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:PREDEFINED =========== Output:Table:SummaryReports, AllSummaryAndMonthly; !- Report 1 Name !- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:MONTHLY =========== Output:Table:Monthly, NameHolderMonthlySummary TaskPurpose ProgressIndicator, !- Name ProgressIndicator,ForDetermination2019, ... 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary CodeName ASHRAE901, !- Name ASHRAE901, ASHRAE1891, IECC, Title24, ORSC, IGCC, ... 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary CodeYear 2019, !- Name all years for ASHRAE90.1, IECC, ASHRAE189.1 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary CodeAmendment NoneAmend, !- Name StateAmend,EEM, NoneAmend for national or state without amendment 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary PrototypeName Warehouse, !- Name 16 Prototypes 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary TaskScope National, !- Name National, State, City 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary State National, !- Name National for national analysis, NewYork, Utah,... for state analysis, or city name for city analysis. Spell out the name of the state without space between words 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary ClimateZone 6A, !- Name 0-8 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 Output:Table:Monthly, NameHolderMonthlySummary RepresentCity USA_MN_Rochester, !- Name representative city like Honolulu for national, for each state, for city analysis. this is not the city of the weather file. The weather city will be extracted from epw file 3, !- Digits After Decimal Site Outdoor Air Drybulb, !- Variable or Meter 1 Name SumOrAverage, !- Aggregation Type for Variable or Meter 1 Heating:Gas, !- Variable or Meter 2 Name SumOrAverage; !- Aggregation Type for Variable or Meter 2 EnergyManagementSystem:Sensor, OAT_F, !- Name , !- Output:Variable or Output:Meter Index Key Name Site Outdoor Air Drybulb Temperature; !- Output:Variable or Output:Meter Name EnergyManagementSystem:Sensor, Zone1_Office_LSr, !- Name Zone1 Office, !- Output:Variable or Output:Meter Index Key Name Zone Lights Electric Power; !- Output:Variable or Output:Meter Name EnergyManagementSystem:Sensor, Zone1_Office_Occ_Sensor, !- Name Office People, !- Output:Variable or Output:Meter Index Key Name People Occupant Count; !- Output:Variable or Output:Meter Name EnergyManagementSystem:InternalVariable, Zone1_Office_Area, !- Name Zone1 Office, !- Internal Data Index Key Name Zone Floor Area; !- Internal Data Type EnergyManagementSystem:Actuator, Zone1_Office_Light_Actuator, !- Name Office Lights, !- Actuated Component Unique Name Lights, !- Actuated Component Type Electric Power Level; !- Actuated Component Control Type EnergyManagementSystem:Program, SET_Zone1_Office_Light_EMS_Program, !- Name SET Zone1_Office_LSr_IP=0.093*Zone1_Office_LSr/Zone1_Office_Area, ! Calculate the actual LPD for each hour IF (Zone1_Office_Occ_Sensor <= 0) && (Zone1_Office_LSr_IP >= 0.02), SET Zone1_Office_Light_Actuator = 0.02*Zone1_Office_Area/0.09290304, ELSE, SET Zone1_Office_Light_Actuator = NULL, ENDIF; EnergyManagementSystem:ProgramCallingManager, SET_Zone1_Office_Light_EMS_Program_Prog_Manager, !- Name BeginTimestepBeforePredictor, !- EnergyPlus Model Calling Point SET_Zone1_Office_Light_EMS_Program; !- Program Name 1 EnergyManagementSystem:Sensor, Zone2_Fine_Storage_LSr, !- Name Zone2 Fine Storage, !- Output:Variable or Output:Meter Index Key Name Zone Lights Electric Power; !- Output:Variable or Output:Meter Name EnergyManagementSystem:InternalVariable, Zone2_Fine_Storage_Area, !- Name Zone2 Fine Storage, !- Internal Data Index Key Name Zone Floor Area; !- Internal Data Type EnergyManagementSystem:Actuator, Zone2_Fine_Storage_Light_Actuator, !- Name Fine Storage Area Lights, !- Actuated Component Unique Name Lights, !- Actuated Component Type Electric Power Level; !- Actuated Component Control Type EnergyManagementSystem:Program, SET_Zone2_Fine_Storage_Light_EMS_Program, !- Name SET Zone2_Fine_Storage_LSr_IP=0.093*Zone2_Fine_Storage_LSr/Zone2_Fine_Storage_Area, ! Calculate the actual LPD for each hour IF (Zone1_Office_Occ_Sensor <= 0) && (Zone2_Fine_Storage_LSr_IP >= 0.02), SET Zone2_Fine_Storage_Light_Actuator = 0.02*Zone2_Fine_Storage_Area/0.09290304, ELSE, SET Zone2_Fine_Storage_Light_Actuator = NULL, ENDIF; EnergyManagementSystem:ProgramCallingManager, SET_Zone2_Fine_Storage_Light_EMS_Program_Prog_Manager, !- Name BeginTimestepBeforePredictor, !- EnergyPlus Model Calling Point SET_Zone2_Fine_Storage_Light_EMS_Program; !- Program Name 1 EnergyManagementSystem:Sensor, Zone3_Bulk_Storage_LSr, !- Name Zone3 Bulk Storage, !- Output:Variable or Output:Meter Index Key Name Zone Lights Electric Power; !- Output:Variable or Output:Meter Name EnergyManagementSystem:InternalVariable, Zone3_Bulk_Storage_Area, !- Name Zone3 Bulk Storage, !- Internal Data Index Key Name Zone Floor Area; !- Internal Data Type EnergyManagementSystem:Actuator, Zone3_Bulk_Storage_Light_Actuator, !- Name Bulk Storage Area Lights, !- Actuated Component Unique Name Lights, !- Actuated Component Type Electric Power Level; !- Actuated Component Control Type EnergyManagementSystem:Program, SET_Zone3_Bulk_Storage_Light_EMS_Program, !- Name SET Zone3_Bulk_Storage_LSr_IP=0.093*Zone3_Bulk_Storage_LSr/Zone3_Bulk_Storage_Area, ! Calculate the actual LPD for each hour IF (Zone1_Office_Occ_Sensor <= 0) && (Zone3_Bulk_Storage_LSr_IP >= 0.02), SET Zone3_Bulk_Storage_Light_Actuator = 0.02*Zone3_Bulk_Storage_Area/0.09290304, ELSE, SET Zone3_Bulk_Storage_Light_Actuator = NULL, ENDIF; EnergyManagementSystem:ProgramCallingManager, SET_Zone3_Bulk_Storage_Light_EMS_Program_Prog_Manager, !- Name BeginTimestepBeforePredictor, !- EnergyPlus Model Calling Point SET_Zone3_Bulk_Storage_Light_EMS_Program; !- Program Name 1