!The DOE Prototype Building Models were developed by Pacific Northwest National Laboratory (PNNL), under contract with the U.S.
!Department of Energy (DOE). These building models were derived from DOE's Commercial Reference Building Models with modifications
!based on input from the ASHRAE Standard 90.1 committee, the Advanced Energy Design Guide series, and building industry experts. The
!prototypes models were developed to quantify energy saving impacts from newly published editions of ASHRAE Standard 90.1, 189.1, IECC,
!and other energy codes and standards. The basic building descriptions can be found in the Scorecards posted at www.energycodes.gov
!website. The recommended citation of the prototype models is
!
!DOE and PNNL. 2020. Commercial Prototype Building Models, Richland, WA, Pacific Northwest National Laboratory. Available at https://www.energycodes.gov/development/commercial/prototype_models.
!
!Detailed descriptions of the prototype model development and addenda modeling strategies can be found in the following reports:
!DOE, 2020. Preliminary Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2019. Report prepared by Zhang, J., M. Rosenberg, J.
!Lerond, Y. Xie, Nambia, C., Y. Chen, R. Hart, M. Halverson, D. Maddox, and S. Goel, Richland, WA, Pacific Northwest National Laboratory.
!
!Zhang, J., Y. Chen, Y. Xie, M. Rosenberg, R. Hart. Energy and Energy Cost Savings Analysis of the 2018 IECC for Commercial Buildings.
!2018. PNNL-28125. Richland, WA: Pacific Northwest National Laboratory.
!
!DOE. 2017. Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2016. Prepared by Athalye, R.A, M.A. Halverson, M.I. Rosenberg, B. Liu,
!J. Zhang, R. Hart, V.V. Mendon, S. Goel, Y. Chen, Y. Xie, and M. Zhao, Richland, WA, Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/02202018_Standard_90.1-2016_Determination_TSD.pdf.
!
!Zhang, J., Y. Xie, R.A. Athalye, J. Zhuge, M. Rosenberg, R. Hart, and B. Liu. Energy and Energy Cost Savings Analysis of the 2015 IECC
!for Commercial Buildings. 2015. PNNL-24269 Rev. 1. Richland, WA: Pacific Northwest National
!Laboratory. https://www.energycodes.gov/sites/default/files/documents/2015_IECC_Commercial_Analysis.pdf.
!
!Halverson M.A., M.I. Rosenberg, W. Wang, J. Zhang, V.V. Mendon, R.A. Athalye, Y. Xie, R. Hart, S. Goel, 2014. ANSI/ASHRAE/IES Standard
!90.1-2013 Determination of Energy Savings: Quantitative Analysis, PNNL-23479. Richland, WA: Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/901-2013_finalCommercialDeterminationQuantitativeAnalysis_TSD_0.pdf.
!
!Goel S., R.A. Athalye, W. Wang, J. Zhang, M.I. Rosenberg, Y. Xie, and R. Hart, et al. 2014. Enhancements to ASHRAE Standard 90.1
!Prototype Building Models. PNNL-23269. Richland, WA: Pacific Northwest National Laboratory. https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-23269.pdf.
!
!Zhang J., R.A. Athalye, R. Hart, M.I. Rosenberg, Y. Xie, S. Goel, and V.V. Mendon, et al. 2013. Energy and Energy Cost Savings Analysis
!of the IECC for Commercial Buildings. PNNL-22760. Richland, WA: Pacific Northwest National Laboratory. http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-22760.pdf.
!
!Thornton B.A., M.I. Rosenberg, E.E. Richman, W. Wang, Y. Xie, J. Zhang, H. Cho, VV Mendon, R.A. Athalye, and B. Liu. 2011. Achieving
!the 30% Goal: Energy and Cost Savings Analysis of ASHRAE Standard 90.1-2010. PNNL-20405. Richland, WA: Pacific Northwest National
!Laboratory. https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf.
!
!
! WeatherFile: USA_MN_Rochester.Intl.AP.726440_TMY3.epw
! BEGIN ECONOMIZER MAP
! NOTE: no economizer map is created for this prototype due to water cooling
! END ECONOMIZER MAP
! GPARM parameters as input:
! Case = ASHRAE901_OfficeLarge_STD2019_Rochester
! SelectedCase =
! basement_tempt = Zone6A_nonres_R10_OfficeLarge_Rochester_STD2016_out.idf
! avg_oa_tempt_ip = 43.475
! maxdiff_oa_tempt_ip = 60.3
! ext_wall_type = MassWall
! nonres_ext_wall_ufactor = 0.45426104
! roof_type = MetalDeckRoof
! nonres_roof_ufactor = 0.181704416
! roof_solar_absorp = 0.7
! roof_emissivity = 0.9
! nonres_window =
! sidelighting_control = yes_AY
! LPD_office = 6.888902667
! exterior_lights_watts = 0
! exterior_lights_watts_a = 12979.2
! exterior_lights_watts_b = 968
! economizer = DifferentialDryBulb
! skip_economizer_control = Yes
! damper_sche = MinOA_MotorizedDamper_Sched
! cc_sa_humidity = 0.0085
! condenser_pump_head = 148556.6249
! chilledwater_pump_head = 44761.27683
! chilledwater_pump_secondary_head = 134283.8305
! avg_oa_tempt = 6.375
! maxdiff_oa_tempt = 33.5
! infil = 0.00056896
! oa_flow_per_area = 0.000431773
! SAT_reset_switch = Yes
! SAT_reset_T = 15.6
! CAV_bas_ERV = No
! economizer_lockout = LockoutWithHeating
! eco_max_temp_limit = na
! heating_damper_act = ReverseWithLimits
! add_ck_vav_bot = Yes
! add_ck_vav_mid = Yes
! add_ck_vav_top = Yes
! core_bottom_mdp = 0.2
! perimeter_bot_zn_1_mdp = 0.2
! perimeter_bot_zn_2_mdp = 0.2
! perimeter_bot_zn_3_mdp = 0.2
! perimeter_bot_zn_4_mdp = 0.2
! core_mid_mdp = 0.2
! perimeter_mid_zn_1_mdp = 0.2
! perimeter_mid_zn_2_mdp = 0.2
! perimeter_mid_zn_3_mdp = 0.2
! perimeter_mid_zn_4_mdp = 0.2
! core_top_mdp = 0.2
! perimeter_top_zn_1_mdp = 0.2
! perimeter_top_zn_2_mdp = 0.2
! perimeter_top_zn_3_mdp = 0.2
! perimeter_top_zn_4_mdp = 0.2
! vav_bot_oaf = autosize
! vav_mid_oaf = autosize
! vav_top_oaf = autosize
! BLDG_ELEVATORS_LIGHTS_FAN_SCH = ELEV_LIGHT_FAN_SCH_ADD_DF
! BLDG_ELEVATORS_LIGHTS_FAN_POWER = 752
! bsmt_new = National_OfficeLarge_ASHRAE901_STD2016_Zone6A_nonres_MN-Rochester-MN_out.idf
! osc_key_wall = surfPropOthSdCoefBasementAvgWall
! osc_key_floor = surfPropOthSdCoefBasementAvgFloor
! BLDG_EQUIP_SCH = BLDG_EQUIP_SCH_ADV
! addendum_cd = 2016AS
! PumpCurve_flag = pump_ride_on_curve
! pv_generator = no
! pv_surface_area = 0
! STD189_overhang = no
! swh_et = 0.803988738
! swh_ua = 11.25413987
! ext_lgt_sch = Exterior_Lgt_ALWAYS_ON
! VAV_bot_WITH_REHEAT_ERV = Yes
! VAV_mid_WITH_REHEAT_ERV = Yes
! VAV_top_WITH_REHEAT_ERV = Yes
! CAV_bas_ERV_power = 911.0574
! VAV_bot_WITH_REHEAT_ERV_power = 1506.812
! VAV_mid_WITH_REHEAT_ERV_power = 1506.812
! VAV_top_WITH_REHEAT_ERV_power = 1506.812
! LTG_SCH_SET = LTG_SET_STD2013
! transformer_size = 500000
! transformer_eff = 0.991
! economizer_coredatacenter = DifferentialDryBulb
! economizer_itcloset = NoEconomizer
! HtgSetP_Sch = HTGSETP_SCH_YES_OPTIMUM
! ClgSetP_Sch = CLGSETP_SCH_YES_OPTIMUM
! wwr = 0.4
! pipe_heat_loss = 7280.88
! add_as = yes
! preheatcoil_exists = no
! AddendumAF_TowerFan = Yes
! skip_EMSprogram = yes
! BoilerAM = Yes
! OA_BASED_OPTIMUM_START_EMS = yes
! OPTIMUM_START_SF_DEPENDENT_EMS = no
! HtgSetP_Sch_CAV_bas = HTGSETP_SCH_YES_OPTIMUM
! ClgSetP_Sch_CAV_bas = CLGSETP_SCH_YES_OPTIMUM
! Wfile_TMY3 = USA_MN_Rochester.Intl.AP.726440_TMY3.epw
! loadProfile = No
! addendum_DV = yes
! receptacle_ctrl_occ_reduction_frac = 0.949143263
! receptacle_ctrl_unocc_reduction_frac = 0.736941088
! HOTW_ST_Reset = No
! CHW_ST_Reset = No
! SHW_Pump_Head = 29891
! CodeName = ASHRAE90.1_STD2019
! CZ_City_Old = Burlington
! CZ_Label = 6A
! exterior_lights_watts_c = 26027
! Addendum_AH = Yes
! LPD_Ctrl = 0.02
! con_swingdoor_r = 0.475963827
! CHW_deltaT = 8.33
! HOTW_PumpCurve_flag = pump_ride_on_curve
! office_standby_mode = Yes
! DryClr_GpmperHp = 4.5
! CRAC_basement = 3.878739046
! CRAC_IT_closet = 4.005260634
! nonres_window_u_factor = 0.34
! nonres_window_shgc = 0.38
! nonresLSG = 1.1
! AnalysisPurpose = ProgressIndicator
! AnalysisCodeName = ASHRAE901
! AnalysisCodeYear = 2019
! AnalysisAmendment = NoneAmend
! AnalysisPrototype = OfficeLarge
! AnalysisScope = National
! AnalysisState = National
! AnalysisClimateZone = 6A
! AnalysisCity = USA_MN_Rochester
! var_Ffactor_IP = 0.51
! var_Cfactor_IP = 0.092
! Core_ZN_SWH_flow = 3.66667e-05
! specify overhang_pf for 1891 codes
Version,9.0;
!- =========== ALL OBJECTS IN CLASS: BUILDING ===========
Building,
OfficeLarge, !- Name
0.0000, !- North Axis {deg}
City, !- Terrain
0.0400, !- Loads Convergence Tolerance Value
0.2000, !- Temperature Convergence Tolerance Value {deltaC}
FullInteriorAndExterior, !- Solar Distribution
25, !- Maximum Number of Warmup Days
6; !- Minimum Number of Warmup Days
!- =========== ALL OBJECTS IN CLASS: TIMESTEP IN HOUR ===========
Timestep,6;
ConvergenceLimits,
1, !- Minimum System Timestep {minutes}
20; !- Maximum HVAC Iterations
!- =========== ALL OBJECTS IN CLASS: SYSTEM CONVERGENCE LIMITS ===========
!- =========== ALL OBJECTS IN CLASS: INSIDE CONVECTION ALGORITHM ===========
SurfaceConvectionAlgorithm:Inside,TARP;
!- =========== ALL OBJECTS IN CLASS: OUTSIDE CONVECTION ALGORITHM ===========
SurfaceConvectionAlgorithm:Outside,TARP;
!- =========== ALL OBJECTS IN CLASS: SOLUTION ALGORITHM ===========
HeatBalanceAlgorithm,ConductionTransferFunction;
!- =========== ALL OBJECTS IN CLASS: SHADOWING CALCULATIONS ===========
ShadowCalculation,
AverageOverDaysInFrequency, !- Calculation Method
30; !- Calculation Frequency
!- =========== ALL OBJECTS IN CLASS: RUN CONTROL ===========
SimulationControl,
Yes, !- Do Zone Sizing Calculation
Yes, !- Do System Sizing Calculation
Yes, !- Do Plant Sizing Calculation
No, !- Run Simulation for Sizing Periods
YES; !- Run Simulation for Weather File Run Periods
!- =========== ALL OBJECTS IN CLASS: RUNPERIOD ===========
RunPeriod,
, !- Name
1, !- Begin Month
1, !- Begin Day of Month
, !- Begin Year
12, !- End Month
31, !- End Day of Month
, !- End Year
Sunday, !- Day of Week for Start Day
No, !- Use Weather File Holidays and Special Days
No, !- Use Weather File Daylight Saving Period
No, !- Apply Weekend Holiday Rule
Yes, !- Use Weather File Rain Indicators
Yes; !- Use Weather File Snow Indicators
!- =========== ALL OBJECTS IN CLASS: SPECIALDAYPERIOD ===========
RunPeriodControl:SpecialDays,
New Years Day, !- Name
January 1, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Veterans Day, !- Name
November 11, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Christmas, !- Name
December 25, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Independence Day, !- Name
July 4, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
MLK Day, !- Name
3rd Monday in January, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Presidents Day, !- Name
3rd Monday in February, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Memorial Day, !- Name
Last Monday in May, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Labor Day, !- Name
1st Monday in September, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Columbus Day, !- Name
2nd Monday in October, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Thanksgiving, !- Name
4th Thursday in November,!- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
!- =========== ALL OBJECTS IN CLASS: DAYLIGHTSAVINGPERIOD ===========
RunPeriodControl:DaylightSavingTime,
2nd Sunday in March, !- Start Date
1st Sunday in November; !- End Date
!- =========== ALL OBJECTS IN CLASS: LOCATION ===========
! Site:Location and design-day objects created by:
! ../../_p.bin/ddy2idf /projects/bigsim/weather/EnergyPlus/tmy3.new/all/USA_MN_Rochester.Intl.AP.726440_TMY3.ddy
!
Site:Location,
Rochester International Arpt_MN_USA Design_Conditions, !- Site:Location Name
43.90, !- Latitude {N+ S-}
-92.50, !- Longitude {W- E+}
-6.00, !- Time Zone Relative to GMT {GMT+/-}
398.00; !- Elevation {m}
SizingPeriod:DesignDay,
Rochester International Arpt Ann Htg 99.6% Condns DB, !- Name
1, !- Month
21, !- Day of Month
WinterDesignDay,!- Day Type
-26.2, !- Maximum Dry-Bulb Temperature {C}
0.0, !- Daily Dry-Bulb Temperature Range {C}
DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type
, !- Dry-Bulb Temperature Range Modifier Schedule Name
Wetbulb, !- Humidity Condition Type
-26.2, !- Wetbulb at Maximum Dry-Bulb {C}
, !- Humidity Indicating Day Schedule Name
, !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir}
, !- Enthalpy at Maximum Dry-Bulb {J/kg}
, !- Daily WetBulb Temperature Range {deltaC}
96634., !- Barometric Pressure {Pa}
5.7, !- Wind Speed {m/s} design conditions vs. traditional 6.71 m/s (15 mph)
310, !- Wind Direction {Degrees; N=0, S=180}
No, !- Rain {Yes/No}
No, !- Snow on ground {Yes/No}
No, !- Daylight Savings Time Indicator
ASHRAEClearSky, !- Solar Model Indicator
, !- Beam Solar Day Schedule Name
, !- Diffuse Solar Day Schedule Name
, !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub)
, !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud)
0.00; !- Clearness {0.0 to 1.1}
SizingPeriod:DesignDay,
Rochester International Arpt Ann Clg .4% Condns DB=>MWB, !- Name
7, !- Month
21, !- Day of Month
SummerDesignDay,!- Day Type
31.2, !- Maximum Dry-Bulb Temperature {C}
10.6, !- Daily Dry-Bulb Temperature Range {C}
DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type
, !- Dry-Bulb Temperature Range Modifier Schedule Name
Wetbulb, !- Humidity Condition Type
23.1, !- Wetbulb at Maximum Dry-Bulb {C}
, !- Humidity Indicating Day Schedule Name
, !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir}
, !- Enthalpy at Maximum Dry-Bulb {J/kg}
, !- Daily WetBulb Temperature Range {deltaC}
96634., !- Barometric Pressure {Pa}
6.7, !- Wind Speed {m/s} design conditions vs. traditional 3.35 m/s (7mph)
200, !- Wind Direction {Degrees; N=0, S=180}
No, !- Rain {Yes/No}
No, !- Snow on ground {Yes/No}
No, !- Daylight Savings Time Indicator
ASHRAETau, !- Solar Model Indicator
, !- Beam Solar Day Schedule Name
, !- Diffuse Solar Day Schedule Name
0.404, !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub)
2.226; !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud)
!- =========== ALL OBJECTS IN CLASS: WATER MAINS TEMPERATURES ===========
Site:WaterMainsTemperature,
Correlation, !- Calculation Method
, !- Temperature Schedule Name
6.375, !- Annual average outdoor air temperature {C}
33.5; !- Maximum difference in monthly average outdoor air temperatures {C}
!- =========== ALL OBJECTS IN CLASS: Site:GroundTemperature:FCfactorMethod ===========
Site:GroundTemperature:FCfactorMethod,
7.4, !- January Ground Temperature {C}
-0.0, !- February Ground Temperature {C}
-7.6, !- March Ground Temperature {C}
-12.6, !- April Ground Temperature {C}
-7.7, !- May Ground Temperature {C}
0.3, !- June Ground Temperature {C}
7.0, !- July Ground Temperature {C}
14.2, !- August Ground Temperature {C}
19.2, !- September Ground Temperature {C}
20.9, !- October Ground Temperature {C}
20.0, !- November Ground Temperature {C}
15.4; !- December Ground Temperature {C}
!- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR-R ===========
Material:NoMass,
Opaque Door panel_con, !- Name
MediumRough, !- Roughness
0.475963827, !- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
!- =========== ALL OBJECTS IN CLASS: CONSTRUCTION ===========
Construction,
Swinging Door_con, !- Name
Opaque Door panel_con; !- Outside Layer
!- =========== Opaque Constructions ===========
!
!- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR ===========
Material,
Std Wood 6inch, !- Name
MediumSmooth, !- Roughness
0.15, !- Thickness {m}
0.12, !- Conductivity {W/m-K}
540.0000, !- Density {kg/m3}
1210, !- Specific Heat {J/kg-K}
0.9000000, !- Thermal Absorptance
0.7000000, !- Solar Absorptance
0.7000000; !- Visible Absorptance
Material,
AC02 Acoustic Ceiling, !- Name
MediumSmooth, !- Roughness
1.2700000E-02, !- Thickness {m}
5.7000000E-02, !- Conductivity {W/m-K}
288.0000, !- Density {kg/m3}
1339.000, !- Specific Heat {J/kg-K}
0.9000000, !- Thermal Absorptance
0.7000000, !- Solar Absorptance
0.2000000; !- Visible Absorptance
Material,
F07 25mm stucco, !- Name
Smooth, !- Roughness
0.0254, !- Thickness {m}
0.72, !- Conductivity {W/m-K}
1856, !- Density {kg/m3}
840, !- Specific Heat {J/kg-K}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material,
F08 Metal surface, !- Name
Smooth, !- Roughness
0.0008, !- Thickness {m}
45.28, !- Conductivity {W/m-K}
7824, !- Density {kg/m3}
500; !- Specific Heat {J/kg-K}
Material,
F08 Metal roof surface, !- Name
Smooth, !- Roughness
0.0008, !- Thickness {m}
45.28, !- Conductivity {W/m-K}
7824, !- Density {kg/m3}
500, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
F12 Asphalt shingles, !- Name
VeryRough, !- Roughness
0.0032, !- Thickness {m}
0.04, !- Conductivity {W/m-K}
1120, !- Density {kg/m3}
1260, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
F13 Built-up roofing, !- Name
Rough, !- Roughness
0.0095, !- Thickness {m}
0.16, !- Conductivity {W/m-K}
1120, !- Density {kg/m3}
1460, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
G01 13mm gypsum board, !- Name
Smooth, !- Roughness
0.0127, !- Thickness {m}
0.1600, !- Conductivity {W/m-K}
800.0000, !- Density {kg/m3}
1090.0000, !- Specific Heat {J/kg-K}
0.9000, !- Absorptance:Thermal
0.7000, !- Absorptance:Solar
0.5000; !- Absorptance:Visible
Material,
G01 16mm gypsum board, !- Name
MediumSmooth, !- Roughness
0.0159, !- Thickness {m}
0.16, !- Conductivity {W/m-K}
800, !- Density {kg/m3}
1090; !- Specific Heat {J/kg-K}
Material,
G02 16mm plywood, !- Name
Smooth, !- Roughness
0.0159, !- Thickness {m}
0.12, !- Conductivity {W/m-K}
544, !- Density {kg/m3}
1210; !- Specific Heat {J/kg-K}
Material,
M14 150mm heavyweight concrete roof, !- Name
MediumRough, !- Roughness
0.1524, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
100mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1016, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
200mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.2032, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
100mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1016, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
150mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1524, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
200mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.2032, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
M10 200mm concrete block wall, !- Name
MediumRough, !- Roughness
0.2032, !- Thickness {m}
0.72, !- Conductivity {W/m-K}
800, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
M10 200mm concrete block basement wall, !- Name
MediumRough, !- Roughness
0.2032, !- Thickness {m}
1.326, !- Conductivity {W/m-K}
1842, !- Density {kg/m3}
912; !- Specific Heat {J/kg-K}
Material:NoMass,
CP02 CARPET PAD, !- Name
VeryRough, !- Roughness
0.21648, !- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.8; !- Visible Absorptance
Material:NoMass,
Air_Wall_Material, !- Name
Rough, !- Roughness
0.2079491, !- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7; !- Solar Absorptance
Material:NoMass,
Nonres_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
5.30668495131472,
!- Thermal Resistance {m2-K/W}
0.9, !- Absorptance:Thermal
0.7, !- Absorptance:Solar
0.7; !- Absorptance:Visible
Material:NoMass,
Res_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Nonres_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
1.88434339518544,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Res_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Nonres_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Res_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Std Opaque Door Panel, !- Name
MediumRough, !- Roughness
0.123456790123457, !- (corresponds to default RSI-0.12327 or R-0.7) Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
!- =========== ALL OBJECTS IN CLASS: CONSTRUCTION ===========
Construction,
InteriorFurnishings, !- Name
Std Wood 6inch; !- Outside Layer
Construction,
Air_Wall, !- Name
Air_Wall_Material; !- Outside Layer
Construction,
DropCeiling, !- Name
AC02 Acoustic Ceiling; !- Outside Layer
Construction,
OpaqueDoor, !- Name
Std Opaque Door Panel; !- Outside Layer
Construction,
AtticRoofDeck, !- Name
F12 Asphalt shingles, !- Outside Layer
G02 16mm plywood; !- Layer 2
Construction,
int_wall, !- Name
G01 13mm gypsum board, !- Outside Layer
G01 13mm gypsum board; !- Layer 2
Construction,
ext_slab_8in_with_carpet,!- Name
200mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
ext_slab_8in, !- Name
200mm Normalweight concrete floor; !- Outside Layer
Construction,
ext_slab_6in_with_carpet,!- Name
150mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
ext_slab_6in, !- Name
150mm Normalweight concrete floor; !- Outside Layer
Construction,
int_slab_floor, !- Name
100mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
int_slab_ceiling, !- Name
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor; !- Layer 2
Construction,
basement_wall, !- Name
M10 200mm concrete block basement wall; !- Outside Layer
Construction,
int_wood_floor, !- Name
AC02 Acoustic Ceiling, !- Outside Layer
G02 16mm plywood, !- Layer 2
CP02 CARPET PAD; !- Layer 3
Construction,
ext_soffit_floor, !- Name
G02 16mm plywood; !- Outside Layer
Construction,
nonres_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Nonres_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
res_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Res_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
semiheated_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Semiheated_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
nonres_ext_wall, !- Name
200mm Normalweight concrete wall, !- Outside Layer
Nonres_Exterior_Wall_Insulation, !- Layer #2
G01 13mm gypsum board; !- Layer #3
Construction,
res_ext_wall, !- Name
200mm Normalweight concrete wall, !- Outside Layer
Res_Exterior_Wall_Insulation, !- Layer #2
G01 13mm gypsum board; !- Layer #3
Construction,
semiheated_ext_wall, !- Name
200mm Normalweight concrete wall, !- Outside Layer
Semiheated_Exterior_Wall_Insulation, !- Layer #2
G01 13mm gypsum board; !- Layer #3
Construction,
nonres_floor, !- Name
Nonres_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
res_floor, !- Name
Res_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
semiheated_floor, !- Name
Semiheated_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
nonres_floor_ceiling, !- Name - reverse ordered layers for nonres_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Nonres_Floor_Insulation; !- Layer #2
Construction,
res_floor_ceiling, !- Name - reverse ordered layers for res_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Res_Floor_Insulation; !- Layer #2
Construction,
semiheated_floor_ceiling, !- Name - reverse ordered layers for semiheated_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Semiheated_Floor_Insulation; !- Layer #2
!- =========== ALL OBJECTS IN CLASS: WINDOWMATERIAL:SIMPLEGLAZINGSYSTEM ===========
WindowMaterial:SimpleGlazingSystem,
Glazing Layer, !- Name
1.9306084, !- U-Factor {W/m2-K}
0.38, !- Solar Heat Gain Coefficient
0.418; !- Visible Transmittance
Construction,
Window_U_0.34_SHGC_0.38, !- Name
Glazing Layer; !- Outside Layer
Construction:CfactorUndergroundWall,
Basement_Wall_East_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
Construction:CfactorUndergroundWall,
Basement_Wall_South_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
Construction:CfactorUndergroundWall,
Basement_Wall_North_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
Construction:CfactorUndergroundWall,
DataCenter_basement_ZN_6_Wall_North_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
Construction:CfactorUndergroundWall,
DataCenter_basement_ZN_6_Wall_South_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
Construction:CfactorUndergroundWall,
DataCenter_basement_ZN_6_Wall_West_Cfactor, !- Name
0.522376, !- C-Factor
2.439; !- Height
!- =========== ALL OBJECTS IN CLASS: ZONE ===========
Zone,
Basement, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Core_bottom, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Core_mid, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
10.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Core_top, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_bot_ZN_3, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_bot_ZN_2, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_bot_ZN_1, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_bot_ZN_4, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_mid_ZN_3, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
10.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_mid_ZN_2, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
10.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_mid_ZN_1, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
10.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_mid_ZN_4, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
10.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_top_ZN_3, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_top_ZN_2, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_top_ZN_1, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
Perimeter_top_ZN_4, !- Name
0.0000, !- Direction of Relative North {deg}
0.0000, !- X Origin {m}
0.0000, !- Y Origin {m}
0.0000, !- Z Origin {m}
1, !- Type
1.0000, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
YES; !- Part of Total Floor Area
Zone,
GroundFloor_Plenum, !- Name
0.0, !- Direction of Relative North {deg}
0.0, !- X Origin {m}
0.0, !- Y Origin {m}
0, !- Z Origin {m}
, !- Type
1, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
No; !- Part of Total Floor Area
Zone,
MidFloor_Plenum, !- Name
0.0, !- Direction of Relative North {deg}
0.0, !- X Origin {m}
0.0, !- Y Origin {m}
0, !- Z Origin {m}
, !- Type
10, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
No; !- Part of Total Floor Area
Zone,
TopFloor_Plenum, !- Name
0.0, !- Direction of Relative North {deg}
0.0, !- X Origin {m}
0.0, !- Y Origin {m}
0, !- Z Origin {m}
, !- Type
1, !- Multiplier
autocalculate, !- Ceiling Height {m}
autocalculate, !- Volume {m3}
autocalculate, !- Floor Area {m2}
, !- Zone Inside Convection Algorithm
, !- Zone Outside Convection Algorithm
No; !- Part of Total Floor Area
Zone,
DataCenter_bot_ZN_6, !- Name
0.0, !- Direction of Relative North {deg}
5.4876, !- X Origin {m}
44.165, !- Y Origin {m}
0.0, !- Z Origin {m}
, !- Type
1; !- Multiplier
Zone,
DataCenter_mid_ZN_6, !- Name
0.0, !- Direction of Relative North {deg}
4.5732, !- X Origin {m}
4.5732, !- Y Origin {m}
16.7683, !- Z Origin {m}
, !- Type
10; !- Multiplier
Zone,
DataCenter_top_ZN_6, !- Name
0.0, !- Direction of Relative North {deg}
4.5732, !- X Origin {m}
4.5732, !- Y Origin {m}
33.5366, !- Z Origin {m}
, !- Type
1; !- Multiplier
Zone,
DataCenter_basement_ZN_6,!- Name
0.0, !- Direction of Relative North {deg}
16.0794, !- X Origin {m}
0.0, !- Y Origin {m}
-2.439, !- Z Origin {m}
, !- Type
1; !- Multiplier
!- =========== ALL OBJECTS IN CLASS: SURFACEGEOMETRY ===========
GlobalGeometryRules,
ULC, !- Starting Vertex Position
CCW, !- Vertex Entry Direction
Relative; !- Coordinate System
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER ===========
!- =========== ALL OBJECTS IN CLASS: BUILDINGSURFACE:DETAILED ===========
BuildingSurface:Detailed,
Basement_Wall_East, !- Name
Wall, !- Surface Type
Basement_Wall_East_Cfactor, !- Construction Name
Basement, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,-2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
Basement, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_2_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
Basement, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_1_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.079400000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.079400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Core_bottom, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Ceiling-Core_bot_ZN_5-PPAutoCreateOther, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Ceiling-Core_bot_ZN_5, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.078200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.078200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_South,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_North,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Core_mid, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Core_mid, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,16.768300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_South,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_mid, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_mid, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_North,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_mid, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_mid, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Core_top, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Core_top, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,33.536600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_South,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_top, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_top, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_North,!- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_top, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Core_top, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_3_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
16.078200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
16.078200000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_3_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_North,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_2_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_2_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_2_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_2_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_1_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6-Perimeter_bot_ZN_1-PPAutoCreateOther, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_1, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.078200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.078200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_1_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_4_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_4_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_4_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_3_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_3_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_3_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_3_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_3_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,16.768300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_3_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_3_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_North,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_2_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_2_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_2_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_2_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_2_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_2_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,16.768300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_2_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_2_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_1_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_1_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_1_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_1_Wall_East-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_1_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_1_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_1_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_1_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,16.768300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_4_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_4_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_4_Wall_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_4_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_4_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_4_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,16.768300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_4_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_4_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_mid_ZN_3_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_mid_ZN_3_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_3_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_3_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_3_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_3_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,33.536600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_3_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_3_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_North,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_2_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_2_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_2_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_2_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_2_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_2_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,33.536600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_2_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_2_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Int-Per3S-NE-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
Surface, !- Outside Boundary Condition
Int-Per3S-NE, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_1_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_1_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_1_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_1_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,33.536600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Int-Per3S-NE, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Int-Per3S-NE-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
5.487600000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
5.487600000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_4_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_4_Wall_South, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_4_Wall_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_4_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_4_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_4_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,33.536600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_4_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_4_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
4.573200000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_top_ZN_3_Wall_West-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_top_ZN_3_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
AutoCalculate, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
GroundFloor_Plenum_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
GroundFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,3.963200000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,3.963200000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
GroundFloor_Plenum_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
GroundFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,3.963200000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,3.963200000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
GroundFloor_Plenum_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
GroundFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,3.963200000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,3.963200000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
GroundFloor_Plenum_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
GroundFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WINDEXPOSED, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,3.963200000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,3.963200000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
MidFloor_Plenum_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
MidFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,20.731500000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,20.731500000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
MidFloor_Plenum_Wall_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
MidFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,20.731500000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,20.731500000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
MidFloor_Plenum_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
MidFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,20.731500000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,20.731500000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
MidFloor_Plenum_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
MidFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,20.731500000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,19.512300000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,19.512300000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,20.731500000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
TopFloor_Plenum_Wall_North, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
TopFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,37.499800000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,37.499800000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
TopFloor_Plenum_Wall_East, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
TopFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,0.000000000000,37.499800000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,37.499800000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Building_Roof, !- Name
Roof, !- Surface Type
nonres_roof, !- Construction Name
TopFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,37.499800000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,37.499800000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,37.499800000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,37.499800000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
TopFloor_Plenum_Wall_West, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
TopFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,37.499800000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,37.499800000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
TopFloor_Plenum_Wall_South, !- Name
Wall, !- Surface Type
nonres_ext_wall, !- Construction Name
TopFloor_Plenum, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,37.499800000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,36.280600000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,37.499800000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
GroundFloor_Plenum_Ceiling, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
GroundFloor_Plenum, !- Zone Name
Surface, !- Outside Boundary Condition
GroundFloor_Plenum_Ceiling, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,3.963200000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,3.963200000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,3.963200000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,3.963200000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
MidFloor_Plenum_Ceiling, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
MidFloor_Plenum, !- Zone Name
Surface, !- Outside Boundary Condition
MidFloor_Plenum_Ceiling, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,20.731500000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,20.731500000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,20.731500000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,20.731500000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-0.914400000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-0.914400000000,0.000000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-0.914400000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-0.914400000000,-39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
-0.914400000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,-39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_East-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,-39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Zone, !- Outside Boundary Condition
GroundFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
-0.914400000000,-39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,-39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_bot_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
-0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-0.914400000000,-39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-0.914400000000,-39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Wall_South,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,39.591800000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
DataCenter_mid_ZN_6, !- Zone Name
Zone, !- Outside Boundary Condition
MidFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_mid_ZN_5_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Core_mid_ZN_5_Wall_South,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_mid_ZN_6_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_mid_ZN_6_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,19.512300000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,16.768300000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,19.512300000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_North-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_North, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
4.573200000000,44.165000000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
4.573200000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,44.165000000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,44.165000000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_top_ZN_5_Wall_South-PPAutoCreateOther, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_South,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,36.280600000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 2 {m}
5.487600000000,4.573200000000,33.536600000000, !- X,Y,Z ==> Vertex 3 {m}
5.487600000000,4.573200000000,36.280600000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,39.591800000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
Core_top_ZN_5_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_West-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_South, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_South-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,0.000000000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_ceiling, !- Name
Ceiling, !- Surface Type
DropCeiling, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Zone, !- Outside Boundary Condition
TopFloor_Plenum, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 2 {m}
0.914400000000,0.000000000000,2.744000000000, !- X,Y,Z ==> Vertex 3 {m}
0.914400000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_top_ZN_6_Wall_North, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_top_ZN_6, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_top_ZN_6_Wall_North-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.914400000000,39.591800000000,2.744000000000, !- X,Y,Z ==> Vertex 1 {m}
0.914400000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,39.591800000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,39.591800000000,2.744000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
Basement, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.079400000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.079400000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
68.534000000000,44.165000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Core_bot_ZN_5_Floor, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Core_bottom, !- Zone Name
Surface, !- Outside Boundary Condition
Core_bot_ZN_5_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
16.078200000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
16.078200000000,44.165000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_3_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
Basement, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_3_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.079400000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.079400000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
68.534000000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Basement_Wall_South, !- Name
Wall, !- Surface Type
Basement_Wall_South_Cfactor, !- Construction Name
Basement, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.079400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.079400000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,0.000000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Basement_Floor, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
Basement, !- Zone Name
Adiabatic, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,-2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
16.079400000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
16.079400000000,48.738100000000,-2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Basement_Wall_North, !- Name
Wall, !- Surface Type
Basement_Wall_North_Cfactor, !- Construction Name
Basement, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
73.107200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,48.738100000000,-2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
16.079400000000,48.738100000000,-2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
16.079400000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Basement_Wall_West, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Basement, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Wall_East, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.079400000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.079400000000,48.738100000000,-2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
16.079400000000,0.000000000000,-2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
16.079400000000,0.000000000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Floor, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Adiabatic, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-16.079400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-16.079400000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Wall_North, !- Name
Wall, !- Surface Type
DataCenter_basement_ZN_6_Wall_North_Cfactor, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-0.001200000000,48.738100000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-16.079400000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-16.079400000000,48.738100000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Wall_South, !- Name
Wall, !- Surface Type
DataCenter_basement_ZN_6_Wall_South_Cfactor, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-16.079400000000,0.000000000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-16.079400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Wall_West, !- Name
Wall, !- Surface Type
DataCenter_basement_ZN_6_Wall_West_Cfactor, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-16.079400000000,48.738100000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-16.079400000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
-16.079400000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
-16.079400000000,0.000000000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_bot_ZN_6_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_bot_ZN_6_Floor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-11.506200000000,44.165000000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-11.506200000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
-10.591800000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
-10.591800000000,44.165000000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Ceiling-Core_bot_ZN_5, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Ceiling-Core_bot_ZN_5-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-10.591800000000,44.165000000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-10.591800000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,44.165000000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_4_Floor-PPAutoCreateOther, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_4_Floor,!- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-16.079400000000,48.738100000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-16.079400000000,0.000000000000,2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
-11.506200000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
-11.506200000000,44.165000000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_1, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6-Perimeter_bot_ZN_1-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-11.506200000000,4.573200000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-16.079400000000,0.000000000000,2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,0.000000000000,2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,4.573200000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_3, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_3-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
-16.079400000000,48.738100000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
-11.506200000000,44.165000000000,2.439000000000, !- X,Y,Z ==> Vertex 2 {m}
-0.001200000000,44.165000000000,2.439000000000, !- X,Y,Z ==> Vertex 3 {m}
-0.001200000000,48.738100000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
Perimeter_bot_ZN_1_Floor,!- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
Surface, !- Outside Boundary Condition
Perimeter_bot_ZN_1_Floor-PPAutoCreateOther, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
68.534000000000,4.573200000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
16.078200000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
16.078200000000,4.573200000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_3-PPAutoCreateOther, !- Name
Floor, !- Surface Type
int_slab_floor, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
Surface, !- Outside Boundary Condition
DataCenter_basement_ZN_6_Ceiling-Perimeter_bot_ZN_3, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
16.078200000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 1 {m}
16.078200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
4.573200000000,44.165000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,0.000000000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
DataCenter_basement_ZN_6_Wall_East, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
DataCenter_basement_ZN_6,!- Zone Name
Surface, !- Outside Boundary Condition
Basement_Wall_West, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
0.0, !- View Factor to Ground
4, !- Number of Vertices
0.000000000000,0.000000000000,2.439000000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,2.439000000000; !- X,Y,Z ==> Vertex 4 {m}
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:SUB ===========
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Window1, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107000000000,48.738100000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
73.10700,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
59.46085,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
59.460850000000,48.738100000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Window2, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
58.241650000000,48.738100000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
58.24165,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
44.59550,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
44.595500000000,48.738100000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Window3, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
43.376300000000,48.738100000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
43.37630,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
29.73015,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
29.730150000000,48.738100000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Window4, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
28.510950000000,48.738100000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
28.51095,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
14.86480,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
14.864800000000,48.738100000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Window5, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
13.645600000000,48.738100000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
13.64560,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
0.00000,48.73810,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,48.738100000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East_Window1, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107200000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
73.10720,0.00000,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
73.10720,15.433294,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,15.433294000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East_Window2, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107200000000,16.652494000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
73.10720,16.652494,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
73.10720,32.085788,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,32.085788000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East_Window3, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107200000000,33.304988000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
73.10720,33.304988,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
73.10720,48.73800,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,48.738000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Window1, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
0.00000,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
13.64615,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
13.646150000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Window2, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
14.865350000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
14.86535,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
28.51150,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
28.511500000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Window3, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
29.730700000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
29.73070,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
43.37685,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
43.376850000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Window4, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
44.596050000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
44.59605,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
58.24220,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
58.242200000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Window5, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
59.461400000000,0.000000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
59.46140,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 2 {m}
73.10700,0.00000,0.8014041856, !- X,Y,Z ==> Vertex 3 {m}
73.107000000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West_Window1, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000000000,48.738000000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
0.00000,48.73800,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
0.00000,33.304706,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,33.304706000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West_Window2, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000000000,32.085506000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
0.00000,32.085506,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
0.00000,16.652212,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,16.652212000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West_Window3, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_bot_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000000000,15.433012000000,2.500000000000, !- X,Y,Z ==> Vertex 1 {m}
0.00000,15.433012,0.8312233024, !- X,Y,Z ==> Vertex 2 {m}
0.00000,0.00000,0.8312233024, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,0.000000000000,2.500000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_mid_ZN_3_Wall_North_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_mid_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107000,48.738100,19.268300, !- X,Y,Z ==> Vertex 1 {m}
73.107000,48.738100,17.68302, !- X,Y,Z ==> Vertex 2 {m}
0.0000,48.738100,17.68302, !- X,Y,Z ==> Vertex 3 {m}
0.000000,48.738100,19.268300; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_mid_ZN_2_Wall_East_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_mid_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107200,0.000000,19.268300, !- X,Y,Z ==> Vertex 1 {m}
73.107200,0.0000,17.68302, !- X,Y,Z ==> Vertex 2 {m}
73.107200,48.738000,17.68302, !- X,Y,Z ==> Vertex 3 {m}
73.107200,48.738000,19.268300; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_mid_ZN_1_Wall_South_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_mid_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000,0.000000,19.268300, !- X,Y,Z ==> Vertex 1 {m}
0.0000,0.0000,17.68302, !- X,Y,Z ==> Vertex 2 {m}
73.107000,0.0000,17.68302, !- X,Y,Z ==> Vertex 3 {m}
73.107000,0.000000,19.268300; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_mid_ZN_4_Wall_West_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_mid_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000,48.738000,19.268300, !- X,Y,Z ==> Vertex 1 {m}
0.0000,48.738000,17.68302, !- X,Y,Z ==> Vertex 2 {m}
0.0000,0.0000,17.68302, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,19.268300; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_top_ZN_3_Wall_North_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_top_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107000,48.738100,36.036600, !- X,Y,Z ==> Vertex 1 {m}
73.107000,48.738100,34.45132, !- X,Y,Z ==> Vertex 2 {m}
0.000000,48.738100,34.45132, !- X,Y,Z ==> Vertex 3 {m}
0.000000,48.738100,36.036600; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_top_ZN_2_Wall_East_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_top_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
73.107200,0.000000,36.036600, !- X,Y,Z ==> Vertex 1 {m}
73.107200,0.000000,34.45132, !- X,Y,Z ==> Vertex 2 {m}
73.107200,48.738000,34.45132, !- X,Y,Z ==> Vertex 3 {m}
73.107200,48.738000,36.036600; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_top_ZN_1_Wall_South_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_top_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000,0.000000,36.036600, !- X,Y,Z ==> Vertex 1 {m}
0.0000,0.0000,34.45132, !- X,Y,Z ==> Vertex 2 {m}
73.107000,0.0000,34.45132, !- X,Y,Z ==> Vertex 3 {m}
73.107000,0.000000,36.036600; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_top_ZN_4_Wall_West_Window, !- Name
Window, !- Surface Type
Window_U_0.34_SHGC_0.38, !- Construction Name
Perimeter_top_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
AutoCalculate, !- View Factor to Ground
, !- Frame and Divider Name
1.0000, !- Multiplier
4, !- Number of Vertices
0.000000,48.738000,36.036600, !- X,Y,Z ==> Vertex 1 {m}
0.0000,48.738000,34.45132, !- X,Y,Z ==> Vertex 2 {m}
0.0000,0.0000,34.45132, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,36.036600; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West_Door1, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
0.000000000000,33.185179805763,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,33.185179805763,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,32.270779805763,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,32.270779805763,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_4_Wall_West_Door2, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_4_Wall_West, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
0.000000000000,16.552817982567,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000000000,16.552817982567,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
0.000000000000,15.638417982567,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000000000,15.638417982567,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Door1, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
13.810736114328,0.000000000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
13.810736114328,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
14.725136114328,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
14.725136114328,0.000000000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Door2, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
28.643695630079,0.000000000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
28.643695630079,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
29.558095630079,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
29.558095630079,0.000000000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Door3, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
43.526278450605,0.000000000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
43.526278450605,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
44.440678450605,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
44.440678450605,0.000000000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_1_Wall_South_Door4, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_1_Wall_South, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
58.430380500539,0.000000000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
58.430380500539,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
59.344780500539,0.000000000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
59.344780500539,0.000000000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East_Door1, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
73.107200000000,15.598040704848,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,15.598040704848,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,16.512440704848,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,16.512440704848,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_2_Wall_East_Door2, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_2_Wall_East, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
73.107200000000,32.208787109866,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
73.107200000000,32.208787109866,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
73.107200000000,33.123187109866,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
73.107200000000,33.123187109866,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Door1, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
59.294409384709,48.738100000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
59.294409384709,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
58.380009384709,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
58.380009384709,48.738100000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Door2, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
44.438376131067,48.738100000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
44.438376131067,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
43.523976131067,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
43.523976131067,48.738100000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Door3, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
29.612533284962,48.738100000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
29.612533284962,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
28.698133284962,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
28.698133284962,48.738100000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
Perimeter_bot_ZN_3_Wall_North_Door4, !- Name
Door, !- Surface Type
Swinging Door_con, !- Construction Name
Perimeter_bot_ZN_3_Wall_North, !- Building Surface Name
, !- Outside Boundary Condition Object
, !- View Factor to Ground
, !- Frame and Divider Name
, !- Multiplier
4, !- Number of Vertices
14.737252885612,48.738100000000,2.133600000000, !- X,Y,Z ==> Vertex 1 {m}
14.737252885612,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 2 {m}
13.822852885612,48.738100000000,0.000000000000, !- X,Y,Z ==> Vertex 3 {m}
13.822852885612,48.738100000000,2.133600000000; !- X,Y,Z ==> Vertex 4 {m}
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:INTERNALMASS ===========
InternalMass,
Basement_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Basement, !- Zone Name
7126.2120; !- Surface Area {m2}
InternalMass,
Core_bottom_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Core_bottom, !- Zone Name
5064.6526; !- Surface Area {m2}
InternalMass,
Core_mid_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Core_mid, !- Zone Name
5064.6526; !- Surface Area {m2}
InternalMass,
Core_top_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Core_top, !- Zone Name
5064.6526; !- Surface Area {m2}
InternalMass,
Perimeter_bot_ZN_3_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_bot_ZN_3, !- Zone Name
626.8258; !- Surface Area {m2}
InternalMass,
Perimeter_bot_ZN_2_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_bot_ZN_2, !- Zone Name
403.9504; !- Surface Area {m2}
InternalMass,
Perimeter_bot_ZN_1_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_bot_ZN_1, !- Zone Name
626.8354; !- Surface Area {m2}
InternalMass,
Perimeter_bot_ZN_4_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_bot_ZN_4, !- Zone Name
403.9478; !- Surface Area {m2}
InternalMass,
Perimeter_mid_ZN_3_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_mid_ZN_3, !- Zone Name
626.8258; !- Surface Area {m2}
InternalMass,
Perimeter_mid_ZN_2_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_mid_ZN_2, !- Zone Name
403.9504; !- Surface Area {m2}
InternalMass,
Perimeter_mid_ZN_1_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_mid_ZN_1, !- Zone Name
626.8354; !- Surface Area {m2}
InternalMass,
Perimeter_mid_ZN_4_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_mid_ZN_4, !- Zone Name
403.9478; !- Surface Area {m2}
InternalMass,
Perimeter_top_ZN_3_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_top_ZN_3, !- Zone Name
626.8258; !- Surface Area {m2}
InternalMass,
Perimeter_top_ZN_2_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_top_ZN_2, !- Zone Name
403.9504; !- Surface Area {m2}
InternalMass,
Perimeter_top_ZN_1_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_top_ZN_1, !- Zone Name
626.8354; !- Surface Area {m2}
InternalMass,
Perimeter_top_ZN_4_InternalMass_1, !- Name
InteriorFurnishings, !- Construction Name
Perimeter_top_ZN_4, !- Zone Name
403.9478; !- Surface Area {m2}
!- =========== ALL OBJECTS IN CLASS: SCHEDULETYPE ===========
ScheduleTypeLimits,
Any Number; !- Name
ScheduleTypeLimits,
Fraction, !- Name
0.0, !- Lower Limit Value
1.0, !- Upper Limit Value
Continuous; !- Numeric Type
ScheduleTypeLimits,
Temperature, !- Name
-60, !- Lower Limit Value
200, !- Upper Limit Value
Continuous; !- Numeric Type
ScheduleTypeLimits,
On/Off, !- Name
0, !- Lower Limit Value
1, !- Upper Limit Value
Discrete; !- Numeric Type
ScheduleTypeLimits,
Control Type, !- Name
0, !- Lower Limit Value
4, !- Upper Limit Value
Discrete; !- Numeric Type
ScheduleTypeLimits,
Humidity, !- Name
10, !- Lower Limit Value
90, !- Upper Limit Value
Continuous; !- Numeric Type
ScheduleTypeLimits,
Number; !- Name
!- =========== ALL OBJECTS IN CLASS: SCHEDULE:COMPACT ===========
Schedule:Compact,
DataCenter_ExtraElecHeatC_Sch, !- Name
On/Off, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0; !- Field 3
Schedule:Compact,
DataCenter_ExtraWaterHeatC_Sch, !- Name
On/Off, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
Exterior_lighting_schedule_a, !- Name
fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:AllDays, !- Field 2
Until: 06:00,0, !- Field 3
Until: 24:00,1; !- Field 5
Schedule:Compact,
Exterior_lighting_schedule_b, !- Name
fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:AllDays, !- Field 2
Until: 06:00,0.7, !- Field 3
Until: 24:00,1; !- Field 5
Schedule:Compact,
Exterior_lighting_schedule_a_IECC2015, !- Name
fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:Weekdays SummerDesignDay, !- Field 2
Until: 07:00,0, !- Field 3
Until: 22:00,1, !- Field 5
Until: 24:00,0, !- Field 7
For:Saturdays, !- Field 9
Until: 07:00,0, !- Field 10
Until: 18:00,1, !- Field 12
Until: 24:00,0, !- Field 14
For:AllOtherDays, !- Field 16
Until: 24:00,0; !- Field 17
Schedule:Compact,
Exterior_lighting_schedule_b_2016, !- Name
fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:AllDays, !- Field 2
Until: 06:00,0.5, !- Field 3
Until: 24:00,1; !- Field 5
Schedule:Compact,
Exterior_lighting_schedule_c_2016, !- Name
fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:AllDays, !- Field 2
Until: 06:00,0.5, !- Field 3
Until: 19:00,1, !- Field 5
Until: 24:00,0.5; !- Field 7
Schedule:Compact,
Hours_of_operation, !- Name
on/off, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 06:00,0.0, !- Field 3
Until: 22:00,1.0, !- Field 5
Until: 24:00,0.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 06:00,0.0, !- Field 10
Until: 18:00,1.0, !- Field 12
Until: 24:00,0.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,0.0; !- Field 17
Schedule:Compact,
ALWAYS_ON, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
Exterior_Lgt_ALWAYS_ON, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
Exterior_Lgt_189_1, !- Name
Fraction, !- Schedule Type Limits Name
Through:12/31, !- Field 1
For:Weekdays, !- Field 2
Until: 9:00,0.5, !- Field 3
Until: 24:00,1.0, !- Field 5
For:Saturday, !- Field 7
Until: 9:00,0.5, !- Field 8
Until: 19:00,1.0, !- Field 10
Until: 24:00,0.5, !- Field 12
FOR: Sunday Holidays AllOtherDays, !- Field 14
Until: 9:00,0.5, !- Field 15
Until: 18:00,1.0, !- Field 17
Until: 24:00,0.5; !- Field 19
Schedule:Compact,
ALWAYS_OFF, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.0; !- Field 3
Schedule:Compact,
HVACOperationSchd, !- Name
on/off, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 06:00,0.0, !- Field 3
Until: 22:00,1.0, !- Field 5
Until: 24:00,0.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 06:00,0.0, !- Field 10
Until: 18:00,1.0, !- Field 12
Until: 24:00,0.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,0.0; !- Field 17
Schedule:Compact,
BLDG_LIGHT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays, !- Field 2
Until: 5:00,0.05, !- Field 3
Until: 6:00,0.1, !- Field 5
Until: 7:00,0.090560114, !- Field 7
Until: 8:00,0.271680342, !- Field 9
Until: 17:00,0.815041026,!- Field 11
Until: 18:00,0.45280057, !- Field 13
Until: 20:00,0.271680342,!- Field 15
Until: 22:00,0.181120228,!- Field 17
Until: 23:00,0.090560114,!- Field 19
Until: 24:00,0.045280057,!- Field 21
For: SummerDesignDay, !- Field 23
Until: 24:00,1, !- Field 24
For: Saturday, !- Field 26
Until: 6:00,0.05, !- Field 27
Until: 8:00,0.090560114, !- Field 29
Until: 12:00,0.271680342,!- Field 31
Until: 17:00,0.135840171,!- Field 33
Until: 19:00,0.045280057,!- Field 35
Until: 24:00,0.05, !- Field 37
For: WinterDesignDay, !- Field 39
Until: 24:00,0, !- Field 40
For: Sunday Holidays AllOtherDays, !- Field 42
Until: 6:00,0.05, !- Field 43
Until: 18:00,0.045280057,!- Field 45
Until: 24:00,0.05; !- Field 47
Schedule:Compact,
EXTERIOR_LIGHT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 07:00,1.0, !- Field 3
Until: 19:00,0.0, !- Field 5
Until: 24:00,1.0; !- Field 7
Schedule:Compact,
BLDG_EQUIP_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays, !- Field 2
Until: 06:00,0.2947764352, !- Field 3
Until: 08:00,0.3796573052, !- Field 5
Until: 12:00,0.8542289367, !- Field 7
Until: 13:00,0.7593146104, !- Field 9
Until: 17:00,0.8542289367, !- Field 11
Until: 18:00,0.4745716315, !- Field 13
Until: 24:00,0.3796573052, !- Field 15
For: SummerDesignDay, !- Field 17
Until: 24:00,1.0, !- Field 18
For: Saturday, !- Field 20
Until: 06:00,0.2210823264, !- Field 21
Until: 08:00,0.3796573052, !- Field 23
Until: 12:00,0.4745716315, !- Field 25
Until: 17:00,0.33220014205, !- Field 27
Until: 19:00,0.2847429789, !- Field 29
Until: 24:00,0.2210823264, !- Field 31
For: WinterDesignDay, !- Field 33
Until: 24:00,0.0, !- Field 34
For: Sunday Holidays AllOtherDays, !- Field 36
Until: 06:00,0.2210823264, !- Field 37
Until: 18:00,0.2847429789, !- Field 39
Until: 24:00,0.2210823264; !- Field 41
Schedule:Compact,
DataCenter_EQUIP_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 1/31, !- Field 1
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 2
Until: 24:00, !- Field 3
0.25, !- Field 4
Through: 2/28, !- Field 5
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 6
Until: 24:00, !- Field 7
0.5, !- Field 8
Through: 3/31, !- Field 9
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 10
Until: 24:00, !- Field 11
0.75, !- Field 12
Through: 4/30, !- Field 13
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 14
Until: 24:00, !- Field 15
1, !- Field 16
Through: 5/31, !- Field 17
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 18
Until: 24:00, !- Field 19
0.25, !- Field 20
Through: 6/30, !- Field 21
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 22
Until: 24:00, !- Field 23
0.5, !- Field 24
Through: 7/31, !- Field 25
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 26
Until: 24:00, !- Field 27
0.75, !- Field 28
Through: 8/31, !- Field 29
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 30
Until: 24:00, !- Field 31
1, !- Field 32
Through: 9/30, !- Field 33
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 34
Until: 24:00, !- Field 35
0.25, !- Field 36
Through: 10/31, !- Field 37
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 38
Until: 24:00, !- Field 39
0.5, !- Field 40
Through: 11/30, !- Field 41
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 42
Until: 24:00, !- Field 43
0.75, !- Field 44
Through: 12/31, !- Field 45
For: SummerDesignDay, !- Field 49
Until: 24:00, !- Field 50
1.0, !- Field 51
For: WinterDesignDay, !- Field 52
Until: 24:00, !- Field 53
0.25, !- Field 54
For: AllOtherDays, !- Field 46
Until: 24:00, !- Field 47
1; !- Field 48
Schedule:Compact,
BLDG_OCC_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays, !- Field 2
Until: 06:00,0.0, !- Field 3
Until: 07:00,0.1, !- Field 5
Until: 08:00,0.2, !- Field 7
Until: 12:00,0.95, !- Field 9
Until: 13:00,0.5, !- Field 11
Until: 17:00,0.95, !- Field 13
Until: 18:00,0.3, !- Field 15
Until: 22:00,0.1, !- Field 17
Until: 24:00,0.05, !- Field 19
For: SummerDesignDay, !- Field 21
Until: 06:00,0.000000001,!- Field 22
Until: 22:00,1.0, !- Field 24
Until: 24:00,0.05, !- Field 26
For: Saturday, !- Field 28
Until: 06:00,0.0, !- Field 29
Until: 08:00,0.1, !- Field 31
Until: 12:00,0.3, !- Field 33
Until: 17:00,0.1, !- Field 35
Until: 19:00,0.05, !- Field 37
Until: 24:00,0.0, !- Field 39
For: WinterDesignDay, !- Field 41
Until: 24:00,0.0, !- Field 42
For: Sunday Holidays AllOtherDays, !- Field 44
Until: 06:00,0.0, !- Field 45
Until: 18:00,0.05, !- Field 47
Until: 24:00,0.0; !- Field 49
Schedule:Compact,
BLDG_OCC_SCH_w_SB, !-Name
Fraction, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0.1,
Until: 08:00, 0.2,
Until: 09:00, 0.95,
Until: 10:00, 0.95,
Until: 11:00, 0,
Until: 12:00, 0.95,
Until: 13:00, 0,
Until: 14:00, 0.95,
Until: 15:00, 0,
Until: 16:00, 0.95,
Until: 17:00, 0.95,
Until: 18:00, 0.3,
Until: 19:00, 0.1,
Until: 20:00, 0.1,
Until: 21:00, 0.1,
Until: 22:00, 0.1,
Until: 23:00, 0.05,
Until: 24:00, 0.05,
For: Saturday,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0.1,
Until: 08:00, 0.1,
Until: 09:00, 0.3,
Until: 10:00, 0.3,
Until: 11:00, 0,
Until: 12:00, 0.3,
Until: 13:00, 0,
Until: 14:00, 0.1,
Until: 15:00, 0,
Until: 16:00, 0.1,
Until: 17:00, 0.1,
Until: 18:00, 0.05,
Until: 19:00, 0.05,
Until: 20:00, 0,
Until: 21:00, 0,
Until: 22:00, 0,
Until: 23:00, 0,
Until: 24:00, 0,
For: SummerDesignDay,
Until: 06:00,0.000000001,
Until: 22:00,1.0,
Until: 24:00,0.05,
For: WinterDesignDay,
Until: 24:00,0.0,
For:Sunday Holidays AllOtherDays,
Until: 06:00,0.0,
Until: 18:00,0.05,
Until: 24:00,0.0;
Schedule:Compact,
BLDG_OCC_SCH_wo_SB, !-Name
Fraction, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0.1,
Until: 08:00, 0.2,
Until: 09:00, 0.95,
Until: 10:00, 0.95,
Until: 11:00, 0.993313428402066,
Until: 12:00, 0.95,
Until: 13:00, 0.522796541264245,
Until: 14:00, 0.95,
Until: 15:00, 0.993313428402066,
Until: 16:00, 0.95,
Until: 17:00, 0.95,
Until: 18:00, 0.3,
Until: 19:00, 0.1,
Until: 20:00, 0.1,
Until: 21:00, 0.1,
Until: 22:00, 0.1,
Until: 23:00, 0.05,
Until: 24:00, 0.05,
For: Saturday,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0.1,
Until: 08:00, 0.1,
Until: 09:00, 0.3,
Until: 10:00, 0.3,
Until: 11:00, 0.313677924758547,
Until: 12:00, 0.3,
Until: 13:00, 0.104559308252849,
Until: 14:00, 0.1,
Until: 15:00, 0.104559308252849,
Until: 16:00, 0.1,
Until: 17:00, 0.1,
Until: 18:00, 0.05,
Until: 19:00, 0.05,
Until: 20:00, 0,
Until: 21:00, 0,
Until: 22:00, 0,
Until: 23:00, 0,
Until: 24:00, 0,
For: SummerDesignDay,
Until: 06:00,0.000000001,
Until: 22:00,1.0,
Until: 24:00,0.05,
For: WinterDesignDay,
Until: 24:00,0.0,
For:Sunday Holidays AllOtherDays,
Until: 06:00,0.0,
Until: 18:00,0.05,
Until: 24:00,0.0;
Schedule:Compact,
BLDG_ELEVATORS, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 24:00,0.5, !- Field 3
For: WinterDesignDay, !- Field 5
Until: 24:00,0.05, !- Field 6
For: AllOtherDays, !- Field 8
Until: 04:00,0.05, !- Field 9
Until: 05:00,0.10, !- Field 11
Until: 06:00,0.20, !- Field 13
Until: 07:00,0.40, !- Field 15
Until: 09:00,0.50, !- Field 17
Until: 10:00,0.35, !- Field 19
Until: 16:00,0.15, !- Field 21
Until: 17:00,0.35, !- Field 23
Until: 19:00,0.50, !- Field 25
Until: 21:00,0.40, !- Field 27
Until: 22:00,0.30, !- Field 29
Until: 23:00,0.20, !- Field 31
Until: 24:00,0.10; !- Field 33
Schedule:Compact,
ELEV_LIGHT_FAN_SCH_24_7, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
ELEV_LIGHT_FAN_SCH_ADD_DF, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 24:00,0.5, !- Field 3
For: WinterDesignDay, !- Field 5
Until: 24:00,0.05, !- Field 6
For: AllOtherDays, !- Field 8
Until: 04:00,0.05, !- Field 9
Until: 05:00,0.10, !- Field 11
Until: 06:00,0.20, !- Field 13
Until: 07:00,0.40, !- Field 15
Until: 09:00,0.50, !- Field 17
Until: 10:00,0.35, !- Field 19
Until: 16:00,0.15, !- Field 21
Until: 17:00,0.35, !- Field 23
Until: 19:00,0.50, !- Field 25
Until: 21:00,0.40, !- Field 27
Until: 22:00,0.30, !- Field 29
Until: 23:00,0.20, !- Field 31
Until: 24:00,0.10; !- Field 33
Schedule:Compact,
BLDG_SWH_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 05:00,0.00, !- Field 3
Until: 06:00,0.00, !- Field 5
Until: 07:00,0.07, !- Field 7
Until: 08:00,0.19, !- Field 9
Until: 09:00,0.35, !- Field 11
Until: 10:00,0.38, !- Field 13
Until: 11:00,0.39, !- Field 15
Until: 12:00,0.47, !- Field 17
Until: 13:00,0.57, !- Field 19
Until: 14:00,0.54, !- Field 21
Until: 15:00,0.34, !- Field 23
Until: 16:00,0.33, !- Field 25
Until: 17:00,0.44, !- Field 27
Until: 18:00,0.26, !- Field 29
Until: 19:00,0.21, !- Field 31
Until: 20:00,0.15, !- Field 33
Until: 21:00,0.17, !- Field 35
Until: 22:00,0.08, !- Field 37
Until: 24:00,0.05, !- Field 39
For: Saturday WinterDesignDay, !- Field 41
Until: 05:00,0.00, !- Field 42
Until: 06:00,0.00, !- Field 44
Until: 07:00,0.07, !- Field 46
Until: 08:00,0.11, !- Field 48
Until: 09:00,0.15, !- Field 50
Until: 10:00,0.21, !- Field 52
Until: 11:00,0.19, !- Field 54
Until: 12:00,0.23, !- Field 56
Until: 13:00,0.20, !- Field 58
Until: 14:00,0.19, !- Field 60
Until: 15:00,0.15, !- Field 62
Until: 16:00,0.13, !- Field 64
Until: 17:00,0.14, !- Field 66
Until: 21:00,0.07, !- Field 68
Until: 22:00,0.09, !- Field 70
Until: 24:00,0.05, !- Field 72
For: Sunday Holidays AllOtherDays, !- Field 74
Until: 06:00,0.00, !- Field 75
Until: 07:00,0.07, !- Field 77
Until: 11:00,0.04, !- Field 79
Until: 13:00,0.06, !- Field 81
Until: 14:00,0.09, !- Field 83
Until: 15:00,0.06, !- Field 85
Until: 21:00,0.04, !- Field 87
Until: 22:00,0.07, !- Field 89
Until: 24:00,0.04; !- Field 91
Schedule:Compact,
ACTIVITY_SCH, !- Name
Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,120.; !- Field 3
Schedule:Compact,
WORK_EFF_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.0; !- Field 3
Schedule:Compact,
AIR_VELO_SCH, !- Name
Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.2; !- Field 3
Schedule:Compact,
CLOTHING_SCH, !- Name
Any Number, !- Schedule Type Limits Name
Through: 04/30, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0, !- Field 3
Through: 09/30, !- Field 5
For: AllDays, !- Field 6
Until: 24:00,0.5, !- Field 7
Through: 12/31, !- Field 9
For: AllDays, !- Field 10
Until: 24:00,1.0; !- Field 11
Schedule:Compact,
INFIL_SCH, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 06:00,1.0, !- Field 3
Until: 22:00,0.0, !- Field 5
Until: 24:00,1.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 06:00,1.0, !- Field 10
Until: 18:00,0.0, !- Field 12
Until: 24:00,1.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,1.0; !- Field 17
Schedule:Compact,
INFIL_SCH_PNNL, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 06:00,1.0, !- Field 3
Until: 22:00,0.25, !- Field 5
Until: 24:00,1.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 06:00,1.0, !- Field 10
Until: 18:00,0.25, !- Field 12
Until: 24:00,1.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,1.0; !- Field 17
Schedule:Compact,
INFIL_HALF_ON_SCH, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 06:00,1.0, !- Field 3
Until: 22:00,0.5, !- Field 5
Until: 24:00,1.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 06:00,1.0, !- Field 10
Until: 18:00,0.5, !- Field 12
Until: 24:00,1.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,1.0; !- Field 17
Schedule:Compact,
SHADING_SCH, !- Name
Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.0; !- Field 3
Schedule:Compact,
PlantOnSched, !- Name
On/Off, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
FAN_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
ReheatCoilAvailSched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
CoolingCoilAvailSched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
HTGSETP_SCH_YES_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 05:00,15.6, !- Field 3
Until: 06:00,17.6, !- Field 5
Until: 07:00,19.6, !- Field 7
Until: 22:00,21.0, !- Field 9
Until: 24:00,15.6, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,15.6, !- Field 14
Until: 05:00,17.8, !- Field 16
Until: 06:00,20.0, !- Field 18
Until: 22:00,21.0, !- Field 20
Until: 24:00,15.6, !- Field 22
For SummerDesignDay, !- Field 24
Until: 24:00,15.6, !- Field 25
For: Saturday, !- Field 27
Until: 04:00,15.6, !- Field 28
Until: 05:00,17.8, !- Field 30
Until: 06:00,20.0, !- Field 32
Until: 17:00,21.0, !- Field 34
Until: 24:00,15.6, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,15.6; !- Field 39
Schedule:Compact,
HTGSETP_SCH_YES_OPTIMUM_w_SB, !-Name
Temperature, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 15.6,
Until: 02:00, 15.6,
Until: 03:00, 15.6,
Until: 04:00, 15.6,
Until: 05:00, 17.8,
Until: 06:00, 20,
Until: 07:00, 21,
Until: 08:00, 21,
Until: 09:00, 21,
Until: 10:00, 21,
Until: 11:00, 20.4444444444444,
Until: 12:00, 21,
Until: 13:00, 20.4444444444444,
Until: 14:00, 21,
Until: 15:00, 20.4444444444444,
Until: 16:00, 21,
Until: 17:00, 21,
Until: 18:00, 21,
Until: 19:00, 21,
Until: 20:00, 21,
Until: 21:00, 21,
Until: 22:00, 21,
Until: 23:00, 15.6,
Until: 24:00, 15.6,
For: Saturday,
Until: 01:00, 15.6,
Until: 02:00, 15.6,
Until: 03:00, 15.6,
Until: 04:00, 15.6,
Until: 05:00, 17.8,
Until: 06:00, 20,
Until: 07:00, 21,
Until: 08:00, 21,
Until: 09:00, 21,
Until: 10:00, 21,
Until: 11:00, 20.4444444444444,
Until: 12:00, 21,
Until: 13:00, 20.4444444444444,
Until: 14:00, 21,
Until: 15:00, 20.4444444444444,
Until: 16:00, 21,
Until: 17:00, 21,
Until: 18:00, 15.6,
Until: 19:00, 15.6,
Until: 20:00, 15.6,
Until: 21:00, 15.6,
Until: 22:00, 15.6,
Until: 23:00, 15.6,
Until: 24:00, 15.6,
For: WinterDesignDay,
Until: 05:00,15.6,
Until: 06:00,17.6,
Until: 07:00,19.6,
Until: 22:00,21.0,
Until: 24:00,15.6,
For SummerDesignDay,
Until: 24:00,15.6,
For:Sunday Holidays AllOtherDays,
Until: 24:00,15.6;
Schedule:Compact,
HTGSETP_SCH_YES_OPTIMUM_original, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 05:00,15.6, !- Field 3
Until: 06:00,17.6, !- Field 5
Until: 07:00,19.6, !- Field 7
Until: 22:00,21.0, !- Field 9
Until: 24:00,15.6, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,15.6, !- Field 14
Until: 05:00,17.8, !- Field 16
Until: 06:00,20.0, !- Field 18
Until: 22:00,21.0, !- Field 20
Until: 24:00,15.6, !- Field 22
For SummerDesignDay, !- Field 24
Until: 24:00,15.6, !- Field 25
For: Saturday, !- Field 27
Until: 04:00,15.6, !- Field 28
Until: 05:00,17.8, !- Field 30
Until: 06:00,20.0, !- Field 32
Until: 17:00,21.0, !- Field 34
Until: 24:00,15.6, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,15.6; !- Field 39
Schedule:Compact,
HTGSETP_SCH_NO_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 05:00,15.6, !- Field 3
Until: 06:00,17.6, !- Field 5
Until: 07:00,19.6, !- Field 7
Until: 22:00,21.0, !- Field 9
Until: 24:00,15.6, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,15.6, !- Field 14
Until: 05:00,21.0, !- Field 16
Until: 06:00,21.0, !- Field 18
Until: 22:00,21.0, !- Field 20
Until: 24:00,15.6, !- Field 22
For SummerDesignDay, !- Field 24
Until: 24:00,15.6, !- Field 25
For: Saturday, !- Field 27
Until: 04:00,15.6, !- Field 28
Until: 05:00,21.0, !- Field 30
Until: 06:00,21.0, !- Field 32
Until: 17:00,21.0, !- Field 34
Until: 24:00,15.6, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,15.6; !- Field 39
Schedule:Compact,
HTGSETP_SCH_CAV_bas, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 05:00,15.6, !- Field 3
Until: 06:00,17.6, !- Field 5
Until: 07:00,19.6, !- Field 7
Until: 22:00,21.0, !- Field 9
Until: 24:00,15.6, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,15.6, !- Field 14
Until: 05:00,21.0, !- Field 16
Until: 06:00,21.0, !- Field 18
Until: 22:00,21.0, !- Field 20
Until: 24:00,15.6, !- Field 22
For SummerDesignDay, !- Field 24
Until: 24:00,15.6, !- Field 25
For: Saturday, !- Field 27
Until: 04:00,15.6, !- Field 28
Until: 05:00,21.0, !- Field 30
Until: 06:00,21.0, !- Field 32
Until: 17:00,21.0, !- Field 34
Until: 24:00,15.6, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,15.6; !- Field 39
Schedule:Compact,
CLGSETP_SCH_YES_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 05:00,26.7, !- Field 3
Until: 06:00,25.7, !- Field 5
Until: 07:00,25.0, !- Field 7
Until: 22:00,24.0, !- Field 9
Until: 24:00,26.7, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,26.7, !- Field 14
Until: 05:00,25.6, !- Field 16
Until: 06:00,25.0, !- Field 18
Until: 22:00,24.0, !- Field 20
Until: 24:00,26.7, !- Field 22
For: Saturday, !- Field 24
Until: 04:00,26.7, !- Field 25
Until: 05:00,25.6, !- Field 27
Until: 06:00,25.0, !- Field 29
Until: 17:00,24.0, !- Field 31
Until: 24:00,26.7, !- Field 33
For WinterDesignDay, !- Field 35
Until: 24:00,26.7, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,26.7; !- Field 39
Schedule:Compact,
CLGSETP_SCH_YES_OPTIMUM_w_SB, !-Name
Temperature, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 26.7,
Until: 02:00, 26.7,
Until: 03:00, 26.7,
Until: 04:00, 26.7,
Until: 05:00, 25.6,
Until: 06:00, 25,
Until: 07:00, 24,
Until: 08:00, 24,
Until: 09:00, 24,
Until: 10:00, 24,
Until: 11:00, 24.5555555555556,
Until: 12:00, 24,
Until: 13:00, 24.5555555555556,
Until: 14:00, 24,
Until: 15:00, 24.5555555555556,
Until: 16:00, 24,
Until: 17:00, 24,
Until: 18:00, 24,
Until: 19:00, 24,
Until: 20:00, 24,
Until: 21:00, 24,
Until: 22:00, 24,
Until: 23:00, 26.7,
Until: 24:00, 26.7,
For: Saturday,
Until: 01:00, 26.7,
Until: 02:00, 26.7,
Until: 03:00, 26.7,
Until: 04:00, 26.7,
Until: 05:00, 25.6,
Until: 06:00, 25,
Until: 07:00, 24,
Until: 08:00, 24,
Until: 09:00, 24,
Until: 10:00, 24,
Until: 11:00, 24.5555555555556,
Until: 12:00, 24,
Until: 13:00, 24.5555555555556,
Until: 14:00, 24,
Until: 15:00, 24.5555555555556,
Until: 16:00, 24,
Until: 17:00, 24,
Until: 18:00, 26.7,
Until: 19:00, 26.7,
Until: 20:00, 26.7,
Until: 21:00, 26.7,
Until: 22:00, 26.7,
Until: 23:00, 26.7,
Until: 24:00, 26.7,
For: SummerDesignDay,
Until: 05:00,26.7,
Until: 06:00,25.7,
Until: 07:00,25.0,
Until: 22:00,24.0,
Until: 24:00,26.7,
For WinterDesignDay,
Until: 24:00,26.7,
For:Sunday Holidays AllOtherDays,
Until: 24:00,26.7;
Schedule:Compact,
CLGSETP_SCH_YES_OPTIMUM_original, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 05:00,26.7, !- Field 3
Until: 06:00,25.7, !- Field 5
Until: 07:00,25.0, !- Field 7
Until: 22:00,24.0, !- Field 9
Until: 24:00,26.7, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,26.7, !- Field 14
Until: 05:00,25.6, !- Field 16
Until: 06:00,25.0, !- Field 18
Until: 22:00,24.0, !- Field 20
Until: 24:00,26.7, !- Field 22
For: Saturday, !- Field 24
Until: 04:00,26.7, !- Field 25
Until: 05:00,25.6, !- Field 27
Until: 06:00,25.0, !- Field 29
Until: 17:00,24.0, !- Field 31
Until: 24:00,26.7, !- Field 33
For WinterDesignDay, !- Field 35
Until: 24:00,26.7, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,26.7; !- Field 39
Schedule:Compact,
CLGSETP_SCH_NO_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 05:00,26.7, !- Field 3
Until: 06:00,25.7, !- Field 5
Until: 07:00,25.0, !- Field 7
Until: 22:00,24.0, !- Field 9
Until: 24:00,26.7, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,26.7, !- Field 14
Until: 05:00,24.0, !- Field 16
Until: 06:00,24.0, !- Field 18
Until: 22:00,24.0, !- Field 20
Until: 24:00,26.7, !- Field 22
For: Saturday, !- Field 24
Until: 04:00,26.7, !- Field 25
Until: 05:00,24.0, !- Field 27
Until: 06:00,24.0, !- Field 29
Until: 17:00,24.0, !- Field 31
Until: 24:00,26.7, !- Field 33
For WinterDesignDay, !- Field 35
Until: 24:00,26.7, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,26.7; !- Field 39
Schedule:Compact,
CLGSETP_SCH_NO_SETBACK, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 05:00,26.7, !- Field 3
Until: 06:00,25.7, !- Field 5
Until: 07:00,25.0, !- Field 7
Until: 22:00,24.0, !- Field 9
Until: 24:00,26.7, !- Field 11
For: Weekdays, !- Field 13
Until: 05:00,24.0, !- Field 14
Until: 06:00,24.0, !- Field 16
Until: 07:00,24.0, !- Field 18
Until: 22:00,24.0, !- Field 20
Until: 24:00,24.0, !- Field 22
For: Saturday, !- Field 24
Until: 05:00,24.0, !- Field 25
Until: 06:00,24.0, !- Field 27
Until: 07:00,24.0, !- Field 29
Until: 17:00,24.0, !- Field 31
Until: 24:00,24.0, !- Field 33
For WinterDesignDay, !- Field 35
Until: 24:00,24.0, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,24.0; !- Field 39
Schedule:Compact,
CLGSETP_SCH_CAV_bas, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 05:00,26.7, !- Field 3
Until: 06:00,25.7, !- Field 5
Until: 07:00,25.0, !- Field 7
Until: 22:00,24.0, !- Field 9
Until: 24:00,26.7, !- Field 11
For: Weekdays, !- Field 13
Until: 04:00,26.7, !- Field 14
Until: 05:00,24.0, !- Field 16
Until: 06:00,24.0, !- Field 18
Until: 22:00,24.0, !- Field 20
Until: 24:00,26.7, !- Field 22
For: Saturday, !- Field 24
Until: 04:00,26.7, !- Field 25
Until: 05:00,24.0, !- Field 27
Until: 06:00,24.0, !- Field 29
Until: 17:00,24.0, !- Field 31
Until: 24:00,26.7, !- Field 33
For WinterDesignDay, !- Field 35
Until: 24:00,26.7, !- Field 36
For: Sunday Holidays AllOtherDays, !- Field 38
Until: 24:00,26.7; !- Field 39
Schedule:Compact,
MinOA_MotorizedDamper_Sched, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays SummerDesignDay, !- Field 2
Until: 07:00,0.0, !- Field 3
Until: 22:00,1.0, !- Field 5
Until: 24:00,0.0, !- Field 7
For: Saturday WinterDesignDay, !- Field 9
Until: 07:00,0.0, !- Field 10
Until: 18:00,1.0, !- Field 12
Until: 24:00,0.0, !- Field 14
For: Sunday Holidays AllOtherDays, !- Field 16
Until: 24:00,0.0; !- Field 17
Schedule:Compact,
MinOA_Sched, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
Dual Zone Control Type Sched, !- Name
Control Type, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,4; !- Field 3
Schedule:Compact,
Cool-Supply-Air-Temp-Sch,!- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,12.8; !- Field 3
Schedule:Compact,
Heat-Supply-Air-Temp-Sch,!- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,12.8; !- Field 3
Schedule:Compact,
CW-Loop-Temp-Schedule, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,6.7; !- Field 3
Schedule:Compact,
HW-Loop-Temp-Schedule, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,82; !- Field 3
!- Per 90.1-2010 G3.1.3.11, the tower shall be controlled to maintain a 70F leaving water temperature
!- where weather permits, floating up to leaving water temperature at design conditions.
Schedule:Compact,
Tower-Loop-Temp-Schedule,!- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,21.1; !- Field 3
Schedule:Compact,
Core_bottom sub cat Latent fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.05; !- Field 3
Schedule:Compact,
Core_bottom sub cat Sensible fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.2; !- Field 3
Schedule:Compact,
Core_bottom sub cat Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,60.0; !- Field 3
Schedule:Compact,
Core_bottom sub catHot Supply Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,55; !- Field 3
Schedule:Compact,
Core_mid sub cat Latent fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.05; !- Field 3
Schedule:Compact,
Core_mid sub cat Sensible fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.2; !- Field 3
Schedule:Compact,
Core_mid sub cat Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,60.0; !- Field 3
Schedule:Compact,
Core_mid sub catHot Supply Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,55; !- Field 3
Schedule:Compact,
Core_top sub cat Latent fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.05; !- Field 3
Schedule:Compact,
Core_top sub cat Sensible fract sched, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.2; !- Field 3
Schedule:Compact,
Core_top sub cat Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,60.0; !- Field 3
Schedule:Compact,
Core_top sub catHot Supply Temp Sched, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,55; !- Field 3
Schedule:Compact,
SHWSys1-Loop-Temp-Schedule, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,60; !- Field 3
Schedule:Compact,
SHWSys1 Water Heater Setpoint Temperature Schedule, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,60.0; !- Field 3
Schedule:Compact,
SHWSys1 Water Heater Ambient Temperature Schedule, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,22.0; !- Field 3
Schedule:Compact,
CLGSETP_DC_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR SummerDesignDay, !- Field 2
UNTIL: 24:00,27, !- Field 3
FOR WinterDesignDay, !- Field 5
UNTIL: 24:00,27, !- Field 6
FOR:AllOtherDays, !- Field 8
UNTIL: 24:00,27; !- Field 9
Schedule:Compact,
HTGSETP_DC_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00,18; !- Field 3
Schedule:Compact,
PLANT LOOP HIGH TEMP SCHEDULE, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Alldays, !- Field 2
Until: 24:00,18.33; !- Field 3
Schedule:Compact,
PLANT LOOP LOW TEMP SCHEDULE, !- Name
Temperature, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Alldays, !- Field 2
Until: 24:00,5; !- Field 3
Schedule:Compact,
SupplyFanSch, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
DC_MinRelHumSetSch, !- Name
Humidity, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,30; !- Field 3
Schedule:Compact,
PERIMETER_MID_ZN_2_MDP_Sch, !-Name
Fraction, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 0.097,
Until: 02:00, 0.097,
Until: 03:00, 0.097,
Until: 04:00, 0.097,
Until: 05:00, 0.097,
Until: 06:00, 0.097,
Until: 07:00, 0.097,
Until: 08:00, 0.097,
Until: 09:00, 0.097,
Until: 10:00, 0.097,
Until: 11:00, 0,
Until: 12:00, 0.097,
Until: 13:00, 0,
Until: 14:00, 0.097,
Until: 15:00, 0,
Until: 16:00, 0.097,
Until: 17:00, 0.097,
Until: 18:00, 0.097,
Until: 19:00, 0.097,
Until: 20:00, 0.097,
Until: 21:00, 0.097,
Until: 22:00, 0.097,
Until: 23:00, 0.097,
Until: 24:00, 0.097,
For: Saturday,
Until: 01:00, 0.097,
Until: 02:00, 0.097,
Until: 03:00, 0.097,
Until: 04:00, 0.097,
Until: 05:00, 0.097,
Until: 06:00, 0.097,
Until: 07:00, 0.097,
Until: 08:00, 0.097,
Until: 09:00, 0.097,
Until: 10:00, 0.097,
Until: 11:00, 0,
Until: 12:00, 0.097,
Until: 13:00, 0,
Until: 14:00, 0.097,
Until: 15:00, 0,
Until: 16:00, 0.097,
Until: 17:00, 0.097,
Until: 18:00, 0.097,
Until: 19:00, 0.097,
Until: 20:00, 0.097,
Until: 21:00, 0.097,
Until: 22:00, 0.097,
Until: 23:00, 0.097,
Until: 24:00, 0.097,
For: AllOtherDays,
Until: 24:00,
0.097;
Schedule:Constant,
VAV_BOT WITH REHEAT Max OA Fraction, !- Name
, !- Schedule Type Limits Name
1.0; !- Hourly Value
Schedule:Constant,
VAV_MID WITH REHEAT Max OA Fraction, !- Name
, !- Schedule Type Limits Name
1.0; !- Hourly Value
Schedule:Constant,
VAV_TOP WITH REHEAT Max OA Fraction, !- Name
, !- Schedule Type Limits Name
1.0; !- Hourly Value
!- =========== ALL OBJECTS IN CLASS: PEOPLE ===========
People,
Basement, !- Name
Basement, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Core_bottom, !- Name
Core_bottom, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Core_mid, !- Name
Core_mid, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Core_top, !- Name
Core_top, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_bot_ZN_3, !- Name
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_bot_ZN_2, !- Name
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_bot_ZN_1, !- Name
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_bot_ZN_4, !- Name
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_mid_ZN_3, !- Name
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_mid_ZN_2, !- Name
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
BLDG_OCC_SCH_w_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_mid_ZN_1, !- Name
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_mid_ZN_4, !- Name
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_top_ZN_3, !- Name
Perimeter_top_ZN_3, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_top_ZN_2, !- Name
Perimeter_top_ZN_2, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_top_ZN_1, !- Name
Perimeter_top_ZN_1, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
People,
Perimeter_top_ZN_4, !- Name
Perimeter_top_ZN_4, !- Zone or ZoneList Name
BLDG_OCC_SCH_wo_SB, !- Number of People Schedule Name
Area/Person, !- Number of People Calculation Method
, !- Number of People
, !- People per Zone Floor Area {person/m2}
18.5787942465724, !- Zone Floor Area per Person {m2/person}
0.3000, !- Fraction Radiant
AUTOCALCULATE, !- Sensible Heat Fraction
ACTIVITY_SCH, !- Activity Level Schedule Name
, !- Carbon Dioxide Generation Rate {m3/s-W}
No, !- Enable ASHRAE 55 Comfort Warnings
ZoneAveraged, !- Mean Radiant Temperature Calculation Type
, !- Surface Name/Angle Factor List Name
WORK_EFF_SCH, !- Work Efficiency Schedule Name
ClothingInsulationSchedule, !- Clothing Insulation Calculation Method
, !- Clothing Insulation Calculation Method Schedule Name
CLOTHING_SCH, !- Clothing Insulation Schedule Name
AIR_VELO_SCH, !- Air Velocity Schedule Name
FANGER; !- Thermal Comfort Model 1 Type
!- =========== ALL OBJECTS IN CLASS: LIGHTS ===========
Lights,
Basement_Lights, !- Name
Basement, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Core_bottom_Lights, !- Name
Core_bottom, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Core_mid_Lights, !- Name
Core_mid, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Core_top_Lights, !- Name
Core_top, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_bot_ZN_3_Lights, !- Name
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_bot_ZN_2_Lights, !- Name
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_bot_ZN_1_Lights, !- Name
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_bot_ZN_4_Lights, !- Name
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_mid_ZN_3_Lights, !- Name
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_mid_ZN_2_Lights, !- Name
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_mid_ZN_1_Lights, !- Name
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_mid_ZN_4_Lights, !- Name
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_top_ZN_3_Lights, !- Name
Perimeter_top_ZN_3, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_top_ZN_2_Lights, !- Name
Perimeter_top_ZN_2, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_top_ZN_1_Lights, !- Name
Perimeter_top_ZN_1, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Perimeter_top_ZN_4_Lights, !- Name
Perimeter_top_ZN_4, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
DataCenter_Basement_Lights, !- Name
DataCenter_basement_ZN_6,!- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
DataCenter_bot_Lights, !- Name
DataCenter_bot_ZN_6, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
DataCenter_mid_Lights, !- Name
DataCenter_mid_ZN_6, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
DataCenter_top_Lights, !- Name
DataCenter_top_ZN_6, !- Zone or ZoneList Name
BLDG_LIGHT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.888902667, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Return Air Fraction
0.7000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
!- =========== ALL OBJECTS IN CLASS: ELECTRIC EQUIPMENT ===========
ElectricEquipment,
Basement_MiscPlug_Equip, !- Name
Basement, !- Zone or ZoneList Name
Always_on, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
13457.544, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Core_bottom_MiscPlug_Equip, !- Name
Core_bottom, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
20142.877, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Core_mid_MiscPlug_Equip, !- Name
Core_mid, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
20142.8, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Core_top_MiscPlug_Equip, !- Name
Core_top, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
20142.8, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_bot_ZN_3_MiscPlug_Equip, !- Name
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2421, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_bot_ZN_2_MiscPlug_Equip, !- Name
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9400, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_bot_ZN_1_MiscPlug_Equip, !- Name
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2809, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_bot_ZN_4_MiscPlug_Equip, !- Name
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9293, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_mid_ZN_3_MiscPlug_Equip, !- Name
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2421, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_mid_ZN_2_MiscPlug_Equip, !- Name
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9400, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_mid_ZN_1_MiscPlug_Equip, !- Name
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2809, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_mid_ZN_4_MiscPlug_Equip, !- Name
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9293, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_top_ZN_3_MiscPlug_Equip, !- Name
Perimeter_top_ZN_3, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2421, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_top_ZN_2_MiscPlug_Equip, !- Name
Perimeter_top_ZN_2, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9400, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_top_ZN_1_MiscPlug_Equip, !- Name
Perimeter_top_ZN_1, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
2529.2809, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Perimeter_top_ZN_4_MiscPlug_Equip, !- Name
Perimeter_top_ZN_4, !- Zone or ZoneList Name
BLDG_EQUIP_SCH, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
1629.9293, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.5000, !- Fraction Radiant
0.0000, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
DataCenter_Basement_MiscPlug_Equip, !- Name
DataCenter_basement_ZN_6,!- Zone or ZoneList Name
DataCenter_EQUIP_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
0, !- Design Level {W}
484.423246742185, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.1000, !- Fraction Radiant
0.0000, !- Fraction Lost
DataCenterPlugLoads; !- End-Use Subcategory
ElectricEquipment,
DataCenter_bot_MiscPlug_Equip, !- Name
DataCenter_bot_ZN_6, !- Zone or ZoneList Name
DataCenter_EQUIP_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
0, !- Design Level {W}
215.299220774304, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.1000, !- Fraction Radiant
0.0000, !- Fraction Lost
DataCenterPlugLoads; !- End-Use Subcategory
ElectricEquipment,
DataCenter_mid_MiscPlug_Equip, !- Name
DataCenter_mid_ZN_6, !- Zone or ZoneList Name
DataCenter_EQUIP_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
0, !- Design Level {W}
215.299220774304, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.1000, !- Fraction Radiant
0.0000, !- Fraction Lost
DataCenterPlugLoads; !- End-Use Subcategory
ElectricEquipment,
DataCenter_top_MiscPlug_Equip, !- Name
DataCenter_top_ZN_6, !- Zone or ZoneList Name
DataCenter_EQUIP_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
0, !- Design Level {W}
215.299220774304, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.1000, !- Fraction Radiant
0.0000, !- Fraction Lost
DataCenterPlugLoads; !- End-Use Subcategory
Exterior:FuelEquipment,
Elevators, !- Name
Electricity, !- Fuel Use Type
BLDG_ELEVATORS, !- Schedule Name
244443.956043956, !- Design Level {W}
ElevatorLift; !- End-Use Subcategory
Exterior:FuelEquipment,
Elevators_Lights_Fan, !- Name
Electricity, !- Fuel Use Type
ELEV_LIGHT_FAN_SCH_ADD_DF, !- Schedule Name
752, !- Design Level {W}
ElevatorLightsFan; !- End-Use Subcategory
!- =========== ALL OBJECTS IN CLASS: EXTERIORLIGHTS ===========
Exterior:Lights,
Exterior_Lights_a, !- Name
Exterior_lighting_schedule_a, !- Schedule Name
12979.2, !- Design Level {W}
AstronomicalClock, !- Control Option
General; !- End-Use Subcategory
Exterior:Lights,
Exterior_Lights_b, !- Name
Exterior_lighting_schedule_b_2016, !- Schedule Name
968, !- Design Level {W}
AstronomicalClock, !- Control Option
General; !- End-Use Subcategory
Exterior:Lights,
Exterior_Lights_c, !- Name
Exterior_lighting_schedule_c_2016, !- Schedule Name
26027, !- Design Level {W}
AstronomicalClock, !- Control Option
General; !- End-Use Subcategory
!- =========== ALL OBJECTS IN CLASS: DAYLIGHTING:DETAILED ===========
Daylighting:Controls,
Perimeter_bot_ZN_1_DaylCtrl, !- Name
Perimeter_bot_ZN_1, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_bot_ZN_1_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
180.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_bot_ZN_1_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_bot_ZN_1_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_1_DaylRefPt1, !- Name
Perimeter_bot_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
1.676400, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_1_DaylRefPt2, !- Name
Perimeter_bot_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
3.352800, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_bot_ZN_2_DaylCtrl, !- Name
Perimeter_bot_ZN_2, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_bot_ZN_2_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
90.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_bot_ZN_2_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_bot_ZN_2_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_2_DaylRefPt1, !- Name
Perimeter_bot_ZN_2, !- Zone Name
71.430800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_2_DaylRefPt2, !- Name
Perimeter_bot_ZN_2, !- Zone Name
69.754400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_bot_ZN_3_DaylCtrl, !- Name
Perimeter_bot_ZN_3, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_bot_ZN_3_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
0.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_bot_ZN_3_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_bot_ZN_3_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_3_DaylRefPt1, !- Name
Perimeter_bot_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
47.061700, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_3_DaylRefPt2, !- Name
Perimeter_bot_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
45.384700, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_bot_ZN_4_DaylCtrl, !- Name
Perimeter_bot_ZN_4, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_bot_ZN_4_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
270.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_bot_ZN_4_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_bot_ZN_4_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_4_DaylRefPt1, !- Name
Perimeter_bot_ZN_4, !- Zone Name
1.676400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_bot_ZN_4_DaylRefPt2, !- Name
Perimeter_bot_ZN_4, !- Zone Name
3.352800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
0.762000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_mid_ZN_1_DaylCtrl, !- Name
Perimeter_mid_ZN_1, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_mid_ZN_1_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
180.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_mid_ZN_1_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_mid_ZN_1_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_1_DaylRefPt1, !- Name
Perimeter_mid_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
1.676400, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_1_DaylRefPt2, !- Name
Perimeter_mid_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
3.352800, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_mid_ZN_2_DaylCtrl, !- Name
Perimeter_mid_ZN_2, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_mid_ZN_2_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
90.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_mid_ZN_2_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_mid_ZN_2_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_2_DaylRefPt1, !- Name
Perimeter_mid_ZN_2, !- Zone Name
71.430800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_2_DaylRefPt2, !- Name
Perimeter_mid_ZN_2, !- Zone Name
69.754400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_mid_ZN_3_DaylCtrl, !- Name
Perimeter_mid_ZN_3, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_mid_ZN_3_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
0.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_mid_ZN_3_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_mid_ZN_3_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_3_DaylRefPt1, !- Name
Perimeter_mid_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
47.061700, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_3_DaylRefPt2, !- Name
Perimeter_mid_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
45.384700, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_mid_ZN_4_DaylCtrl, !- Name
Perimeter_mid_ZN_4, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_mid_ZN_4_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
270.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_mid_ZN_4_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_mid_ZN_4_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_4_DaylRefPt1, !- Name
Perimeter_mid_ZN_4, !- Zone Name
1.676400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_mid_ZN_4_DaylRefPt2, !- Name
Perimeter_mid_ZN_4, !- Zone Name
3.352800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
17.526000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_top_ZN_1_DaylCtrl, !- Name
Perimeter_top_ZN_1, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_top_ZN_1_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
180.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_top_ZN_1_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_top_ZN_1_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_top_ZN_1_DaylRefPt1, !- Name
Perimeter_top_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
1.676400, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_top_ZN_1_DaylRefPt2, !- Name
Perimeter_top_ZN_1, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
3.352800, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_top_ZN_2_DaylCtrl, !- Name
Perimeter_top_ZN_2, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_top_ZN_2_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
90.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_top_ZN_2_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_top_ZN_2_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_top_ZN_2_DaylRefPt1, !- Name
Perimeter_top_ZN_2, !- Zone Name
71.430800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_top_ZN_2_DaylRefPt2, !- Name
Perimeter_top_ZN_2, !- Zone Name
69.754400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_top_ZN_3_DaylCtrl, !- Name
Perimeter_top_ZN_3, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_top_ZN_3_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
0.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_top_ZN_3_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_top_ZN_3_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_top_ZN_3_DaylRefPt1, !- Name
Perimeter_top_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
47.061700, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_top_ZN_3_DaylRefPt2, !- Name
Perimeter_top_ZN_3, !- Zone Name
36.576000, !- X-Coordinate of Reference Point {m}
45.384700, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:Controls,
Perimeter_top_ZN_4_DaylCtrl, !- Name
Perimeter_top_ZN_4, !- Zone Name
SplitFlux, !- Daylighting Method
, !- Availability Schedule Name
Continuousoff, !- Lighting Control Type
0.2, !- Minimum Input Power Fraction for Continuous or ContinuousOff Dimming Control
0.2, !- Minimum Light Output Fraction for Continuous or ContinuousOff Dimming Control
3, !- Number of Stepped Control Steps
1.0, !- Probability Lighting will be Reset When Needed in Manual Stepped Control
Perimeter_top_ZN_4_DaylRefPt1, !- Glare Calculation Daylighting Reference Point Name
270.0, !- Glare Calculation Azimuth Angle of View Direction Clockwise from Zone y-Axis {deg}
22.0, !- Maximum Allowable Discomfort Glare Index
, !- DElight Gridding Resolution {m2}
Perimeter_top_ZN_4_DaylRefPt1, !- Daylighting Reference Point 1 Name
0.3857, !- Fraction of Zone Controlled by Reference Point 1
377.0, !- Illuminance Setpoint at Reference Point 1 {lux}
Perimeter_top_ZN_4_DaylRefPt2, !- Daylighting Reference Point 2 Name
0.1385, !- Fraction of Zone Controlled by Reference Point 2
377.0; !- Illuminance Setpoint at Reference Point 2 {lux}
Daylighting:ReferencePoint,
Perimeter_top_ZN_4_DaylRefPt1, !- Name
Perimeter_top_ZN_4, !- Zone Name
1.676400, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
Daylighting:ReferencePoint,
Perimeter_top_ZN_4_DaylRefPt2, !- Name
Perimeter_top_ZN_4, !- Zone Name
3.352800, !- X-Coordinate of Reference Point {m}
24.384000, !- Y-Coordinate of Reference Point {m}
34.290000; !- Z-Coordinate of Reference Point {m}
!- =========== ALL OBJECTS IN CLASS: INFILTRATION ===========
ZoneInfiltration:DesignFlowRate,
Perimeter_bot_ZN_3_Infiltration, !- Name
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_bot_ZN_2_Infiltration, !- Name
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_bot_ZN_1_Infiltration, !- Name
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_bot_ZN_4_Infiltration, !- Name
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_mid_ZN_3_Infiltration, !- Name
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_mid_ZN_2_Infiltration, !- Name
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_mid_ZN_1_Infiltration, !- Name
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_mid_ZN_4_Infiltration, !- Name
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_top_ZN_3_Infiltration, !- Name
Perimeter_top_ZN_3, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_top_ZN_2_Infiltration, !- Name
Perimeter_top_ZN_2, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_top_ZN_1_Infiltration, !- Name
Perimeter_top_ZN_1, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Perimeter_top_ZN_4_Infiltration, !- Name
Perimeter_top_ZN_4, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
GroundFloor_Plenum_Infiltration, !- Name
GroundFloor_Plenum, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
MidFloor_Plenum_Infiltration, !- Name
MidFloor_Plenum, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
TopFloor_Plenum_Infiltration, !- Name
TopFloor_Plenum, !- Zone or ZoneList Name
INFIL_SCH_PNNL, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
4.37644032e-05, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0.0000, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
!- =========== ALL OBJECTS IN CLASS: SIZING PARAMETERS ===========
Sizing:Parameters,
1, !- Heating Sizing Factor
1, !- Cooling Sizing Factor
6; !- Timesteps in Averaging Window
!- =========== ALL OBJECTS IN CLASS: ZONE SIZING ===========
Sizing:Zone,
Basement, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Basement, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA Basement, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Core_bottom, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Core_bottom, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Core_bottom, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Core_mid, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Core_mid, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Core_mid, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Core_top, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Core_top, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Core_top, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_bot_ZN_3, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_bot_ZN_3, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_bot_ZN_2, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_bot_ZN_2, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_bot_ZN_1, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_bot_ZN_1, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_bot_ZN_4, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_bot_ZN_4, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_mid_ZN_3, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_mid_ZN_3, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_mid_ZN_2, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_mid_ZN_2, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_mid_ZN_1, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_mid_ZN_1, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_mid_ZN_4, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_mid_ZN_4, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_top_ZN_3, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_top_ZN_3, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_top_ZN_3, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_top_ZN_2, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_top_ZN_2, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_top_ZN_2, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_top_ZN_1, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_top_ZN_1, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_top_ZN_1, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Perimeter_top_ZN_4, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40.0, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Perimeter_top_ZN_4, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0.0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0.0, !- Cooling Minimum Air Flow {m3/s}
0.0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0.0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
, !- Heating Maximum Air Flow Fraction
VAV_Zone_AirDistribution;!- Design Specification Zone Air Distribution Object Name
DesignSpecification:OutdoorAir,
SZ DSOA Perimeter_top_ZN_4, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
DataCenter_basement_ZN_6,!- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA DataCenter_basement_ZN_6, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
; !- Heating Maximum Air Flow {m3/s}
DesignSpecification:OutdoorAir,
SZ DSOA DataCenter_basement_ZN_6, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
DataCenter_bot_ZN_6, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA DataCenter_bot_ZN_6, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
; !- Heating Maximum Air Flow {m3/s}
DesignSpecification:OutdoorAir,
SZ DSOA DataCenter_bot_ZN_6, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
DataCenter_mid_ZN_6, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA DataCenter_mid_ZN_6, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
; !- Heating Maximum Air Flow {m3/s}
DesignSpecification:OutdoorAir,
SZ DSOA DataCenter_mid_ZN_6, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
DataCenter_top_ZN_6, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.0085, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA DataCenter_top_ZN_6, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
0, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
; !- Heating Maximum Air Flow {m3/s}
DesignSpecification:OutdoorAir,
SZ DSOA DataCenter_top_ZN_6, !- Name
Flow/Area, !- Outdoor Air Method
, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0; !- Outdoor Air Flow per Zone {m3/s}
DesignSpecification:ZoneAirDistribution,
VAV_Zone_AirDistribution, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
, !- Zone Air Distribution Effectiveness Schedule Name
, !- Zone Secondary Recirculation Fraction {dimensionless}
0.6; !- Minimum Zone Ventilation Efficiency {dimensionless}
!- =========== ALL OBJECTS IN CLASS: SYSTEM SIZING ===========
Sizing:System,
CAV_bas, !- AirLoop Name
Sensible, !- Type of Load to Size On
AUTOSIZE, !- Design Outdoor Air Flow Rate {m3/s}
1.00, !- Central Heating Maximum System Air Flow Ratio
7.0, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Central Cooling Design Supply Air Temperature {C}
40.0000, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0.0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0.0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
VAV_bot WITH REHEAT, !- AirLoop Name
Sensible, !- Type of Load to Size On
2.0304, !- Design Outdoor Air Flow Rate {m3/s}
0.3000, !- Central Heating Maximum System Air Flow Ratio
7.0, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Central Cooling Design Supply Air Temperature {C}
12.8000, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0.0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0.0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
VAV_mid WITH REHEAT, !- AirLoop Name
Sensible, !- Type of Load to Size On
20.304, !- Design Outdoor Air Flow Rate {m3/s}
0.3000, !- Central Heating Maximum System Air Flow Ratio
7.0, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Central Cooling Design Supply Air Temperature {C}
12.8000, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0.0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0.0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
VAV_top WITH REHEAT, !- AirLoop Name
Sensible, !- Type of Load to Size On
2.0304, !- Design Outdoor Air Flow Rate {m3/s}
0.3000, !- Central Heating Maximum System Air Flow Ratio
7.0, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8000, !- Central Cooling Design Supply Air Temperature {C}
12.8000, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0.0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0.0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
AirLoop DataCenter Basement, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
AirLoop DataCenter bot, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
AirLoop DataCenter mid, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
AirLoop DataCenter top, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
Coincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.0085, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
!- =========== ALL OBJECTS IN CLASS: PLANT SIZING ===========
Sizing:Plant,
SHWSys1, !- Plant or Condenser Loop Name
Heating, !- Loop Type
60, !- Design Loop Exit Temperature {C}
5.0; !- Loop Design Temperature Difference {deltaC}
Sizing:Plant,
HeatSys1, !- Plant or Condenser Loop Name
Heating, !- Loop Type
82.0, !- Design Loop Exit Temperature {C}
11.0; !- Loop Design Temperature Difference {deltaC}
Sizing:Plant,
CoolSys1_Supply, !- Plant or Condenser Loop Name
Cooling, !- Loop Type
6.67, !- Design Loop Exit Temperature {C}
8.33; !- Loop Design Temperature Difference {deltaC}
Sizing:Plant,
CoolSys1_Demand, !- Plant or Condenser Loop Name
Cooling, !- Loop Type
6.67, !- Design Loop Exit Temperature {C}
8.33; !- Loop Design Temperature Difference {deltaC}
!- Design Loop Exit Temperature: Per 90.1-2010 G3.1.3.13, condenser water design supply temperature shall be
!- 85F or 10F approaching design wet-bulb temperature, whichever is lower, with a design temperature rise of 10F (range temperature).
!- Loop Design Temperature Difference: Per 90.1-2010 G3.1.3.13, design temperature rise of 10F (range temperature).
!- Sizing Option: new inputs after V8.3. We choose coincident to be aligned with system sizing. Default (leaving blank) is noncoincident.
!- Zone Timesteps in Averaging Window: alignment with system inputs for Timesteps in Averaging Window.
!- Coincident Sizing Factor Mode: GlobalCoolingSizingFactor aligns with the system level sizing parameter inputs.
Sizing:Plant,
TowerWaterSys, !- Plant or Condenser Loop Name
Condenser, !- Loop Type
29.4444444444444, !- Design Loop Exit Temperature {C}
5.55555555555556, !- Loop Design Temperature Difference {deltaC}
Coincident, !- Sizing Option
6, !- Zone Timesteps in Averaging Window
GlobalCoolingSizingFactor; !- Coincident Sizing Factor Mode
!- Plant loop for dry cooler and boiler for Data Center
Sizing:Plant,
Single Water Plant Loop, !- Plant or Condenser Loop Name
Heating, !- Loop Type
39, !- Design Loop Exit Temperature {C}
11; !- Loop Design Temperature Difference {deltaC}
!- Set of chiller curves based on Dick Lord's study dated January 17, 2010...
!- Hospital and Large Office have water cooled chillers...Hence set of water cooled chillers to be used in these prototypes...
!- Large Office will follow 90.1-2010 Path B in the PI case whereas Hospital will follow Path A based on the discussion with the SWG
!- Changed the min. chiller condenser fluid entering temperature to 64 F (17.78 deg C) for water cooled chillers based on Dick's email dated June 4, 2010
!- and 55 F (12.7 deg C) for air cooled chillers
!- based on email string and energyplus support clarification dated June 1, 2010...also changed the upper limit for air cooled chillers to 125 F (51.67 deg C)
!- and the water cooled chillers to 115 F (46.11 deg C) later the same day...
! Temporary changes to address Dick's wrong PLR curves. On Oct. 27, 2010
! Water cooled chiller PLR curve comes from E+ data library "ReformEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR"
! Air-cooled chiller PLR comes from the original curve before addendum M.
!- Water cooled chillers: Positive Displacement chillers...
!- 90.1-2004 and 2007 Baseline curves...
Curve:Biquadratic,
WC_PD_2004_CAPFT, !- Name
0.9061150, !- Coefficient1 Constant
0.0292277, !- Coefficient2 x
-0.0003647, !- Coefficient3 x**2
-0.0009709, !- Coefficient4 y
-0.0000905, !- Coefficient5 y**2
0.0002527, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_PD_2004_EIRFT, !- Name
0.3617105, !- Coefficient1 Constant
-0.0229833, !- Coefficient2 x
0.0009519, !- Coefficient3 x**2
0.0131889, !- Coefficient4 y
0.0003752, !- Coefficient5 y**2
-0.0007059, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_PD_LT75_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_75TO150_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_150TO300_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_GT300_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- 90.1-2010 Path A curves...
Curve:Biquadratic,
WC_PD_LT150_2010_PA_CAPFT, !- Name
0.9061150, !- Coefficient1 Constant
0.0292277, !- Coefficient2 x
-0.0003647, !- Coefficient3 x**2
-0.0009709, !- Coefficient4 y
-0.0000905, !- Coefficient5 y**2
0.0002527, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_PD_LT150_2010_PA_EIRFT, !- Name
0.3617105, !- Coefficient1 Constant
-0.0229833, !- Coefficient2 x
0.0009519, !- Coefficient3 x**2
0.0131889, !- Coefficient4 y
0.0003752, !- Coefficient5 y**2
-0.0007059, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_PD_GT150_2010_PA_CAPFT, !- Name
0.9061150, !- Coefficient1 Constant
0.0292277, !- Coefficient2 x
-0.0003647, !- Coefficient3 x**2
-0.0009709, !- Coefficient4 y
-0.0000905, !- Coefficient5 y**2
0.0002527, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_PD_GT150_2010_PA_EIRFT, !- Name
0.3773115, !- Coefficient1 Constant
-0.0229032, !- Coefficient2 x
0.0016504, !- Coefficient3 x**2
0.0118156, !- Coefficient4 y
0.0004345, !- Coefficient5 y**2
-0.0010132, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_PD_LT75_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_75TO150_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_150TO300_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_GT300_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- 90.1-2010 Path B curves..
Curve:Biquadratic,
WC_PD_2010_PB_CAPFT, !- Name
0.9061171, !- Coefficient1 Constant
0.0292267, !- Coefficient2 x
-0.0003665, !- Coefficient3 x**2
-0.0009698, !- Coefficient4 y
-0.0000907, !- Coefficient5 y**2
0.0002535, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_PD_2010_PB_EIRFT, !- Name
0.3617782, !- Coefficient1 Constant
-0.0230016, !- Coefficient2 x
0.0009672, !- Coefficient3 x**2
0.0131801, !- Coefficient4 y
0.0003761, !- Coefficient5 y**2
-0.0007121, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_PD_LT75_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_75TO150_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_150TO300_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_PD_GT300_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- Water cooled chillers: Centrifugal Chillers...
!- 90.1-2004 Baseline curves...
Curve:Biquadratic,
WC_Cent_LT150_2004_CAPFT, !- Name
0.7446451, !- Coefficient1 Constant
0.0114858, !- Coefficient2 x
0.0000148, !- Coefficient3 x**2
0.0224010, !- Coefficient4 y
-0.0006880, !- Coefficient5 y**2
0.0009839, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_Cent_LT150_2004_EIRFT, !- Name
0.7728770, !- Coefficient1 Constant
0.0221010, !- Coefficient2 x
-0.0000799, !- Coefficient3 x**2
-0.0070045, !- Coefficient4 y
0.0004763, !- Coefficient5 y**2
-0.0010612, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_Cent_GT150_2004_CAPFT, !- Name
0.7600172, !- Coefficient1 Constant
0.0147432, !- Coefficient2 x
0.0002144, !- Coefficient3 x**2
0.0207218, !- Coefficient4 y
-0.0006425, !- Coefficient5 y**2
0.0008007, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_Cent_GT150_2004_EIRFT, !- Name
0.6772577, !- Coefficient1 Constant
0.0117857, !- Coefficient2 x
-0.0001967, !- Coefficient3 x**2
0.0014414, !- Coefficient4 y
0.0003005, !- Coefficient5 y**2
-0.0006807, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_LT150_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_150TO300_2004_EIRFPLR,!- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_GT300_2004_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- 90.1-2010 Path A curves...
Curve:Biquadratic,
WC_Cent_2010_PA_CAPFT, !- Name
0.7600172, !- Coefficient1 Constant
0.0147432, !- Coefficient2 x
0.0002144, !- Coefficient3 x**2
0.0207218, !- Coefficient4 y
-0.0006425, !- Coefficient5 y**2
0.0008007, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_Cent_2010_PA_EIRFT, !- Name
0.6772577, !- Coefficient1 Constant
0.0117857, !- Coefficient2 x
-0.0001967, !- Coefficient3 x**2
0.0014414, !- Coefficient4 y
0.0003005, !- Coefficient5 y**2
-0.0006807, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_LT150_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_150TO300_2010_PA_EIRFPLR,!- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_300TO600_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_GT600_2010_PA_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- 90.1-2010 Path B curves...
Curve:Biquadratic,
WC_Cent_2010_PB_CAPFT, !- Name
0.5362340, !- Coefficient1 Constant
0.005581, !- Coefficient2 x
-0.0013654, !- Coefficient3 x**2
0.0488966, !- Coefficient4 y
-0.0012018, !- Coefficient5 y**2
0.0010523, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Biquadratic,
WC_Cent_2010_PB_EIRFT, !- Name
1.0821822, !- Coefficient1 Constant
0.0042977, !- Coefficient2 x
-0.0013182, !- Coefficient3 x**2
-0.0260781, !- Coefficient4 y
0.0008256, !- Coefficient5 y**2
-0.0006013, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
17.78, !- Minimum Value of y
46.11; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_LT150_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_150TO300_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_300TO600_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
Curve:Bicubic,
WC_Cent_GT600_2010_PB_EIRFPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- Air cooled chillers...
!- 90.1-2004 Baseline curves...
Curve:Biquadratic,
AC_2004_CAPFT, !- Name
1.0433811, !- Coefficient1 Constant
0.0407077, !- Coefficient2 x
0.0004506, !- Coefficient3 x**2
-0.0041514, !- Coefficient4 y
-0.0000886, !- Coefficient5 y**2
-0.0003467, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
12.7, !- Minimum Value of y
51.67; !- Maximum Value of y
Curve:Biquadratic,
AC_2004_EIRFT, !- Name
0.5961915, !- Coefficient1 Constant
-0.0099496, !- Coefficient2 x
0.0007888, !- Coefficient3 x**2
0.0004506, !- Coefficient4 y
0.0004875, !- Coefficient5 y**2
-0.0007623, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
12.7, !- Minimum Value of y
51.67; !- Maximum Value of y
Curve:Quadratic,
AC_LT150_2004_EIRFPLR, !- Name
0.1410, !- Coefficient1 Constant
0.6550, !- Coefficient2 x
0.2030, !- Coefficient3 x**2
0.0000, !- Minimum Value of x
1.0000; !- Maximum Value of x
Curve:Quadratic,
AC_GT150_2004_EIRFPLR, !- Name
0.1410, !- Coefficient1 Constant
0.6550, !- Coefficient2 x
0.2030, !- Coefficient3 x**2
0.0000, !- Minimum Value of x
1.0000; !- Maximum Value of x
!- 90.1-2010 Path A curves...
Curve:Biquadratic,
AC_2010_PA_CAPFT, !- Name
1.0433825, !- Coefficient1 Constant
0.0407073, !- Coefficient2 x
0.0004506, !- Coefficient3 x**2
-0.0041514, !- Coefficient4 y
-0.0000886, !- Coefficient5 y**2
-0.0003467, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
12.7, !- Minimum Value of y
51.67; !- Maximum Value of y
Curve:Biquadratic,
AC_2010_PA_EIRFT, !- Name
0.5961907, !- Coefficient1 Constant
-0.0099493, !- Coefficient2 x
0.0007888, !- Coefficient3 x**2
0.0004506, !- Coefficient4 y
0.0004875, !- Coefficient5 y**2
-0.0007623, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
12.7, !- Minimum Value of y
51.67; !- Maximum Value of y
Curve:Quadratic,
AC_LT150_2010_PA_EIRFPLR, !- Name
0.1410, !- Coefficient1 Constant
0.6550, !- Coefficient2 x
0.2030, !- Coefficient3 x**2
0.0000, !- Minimum Value of x
1.0000; !- Maximum Value of x
Curve:Quadratic,
AC_GT150_2010_PA_EIRFPLR, !- Name
0.1410, !- Coefficient1 Constant
0.6550, !- Coefficient2 x
0.2030, !- Coefficient3 x**2
0.0000, !- Minimum Value of x
1.0000; !- Maximum Value of x
!- =========== ALL OBJECTS IN CLASS: CURVE:BIQUADRATIC ===========
!***** Following curve is from Dick Lord's Chiller Model study for ASHRAE 2007 baseline *****
Curve:Biquadratic,
ChillerCentCapFT, !- Name
0.7446451, !- Coefficient1 Constant
0.0114858, !- Coefficient2 x
0.0000148, !- Coefficient3 x**2
0.0224010, !- Coefficient4 y
-0.0006880, !- Coefficient5 y**2
0.0009839, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
24.0000, !- Minimum Value of y
35.0000; !- Maximum Value of y
!***** Following curve is from Dick Lord's Chiller Model study for ASHRAE 2007 baseline *****
Curve:Biquadratic,
ChillerCentEIRFT, !- Name
0.7728770, !- Coefficient1 Constant
0.0221010, !- Coefficient2 x
-0.0000799, !- Coefficient3 x**2
-0.0070045, !- Coefficient4 y
0.0004763, !- Coefficient5 y**2
-0.0010612, !- Coefficient6 x*y
5.0000, !- Minimum Value of x
10.0000, !- Maximum Value of x
24.0000, !- Minimum Value of y
35.0000; !- Maximum Value of y
!- =========== ALL OBJECTS IN CLASS: CURVE:BICUBIC ===========
!***** Following curve is from Dick Lord's Chiller Model study for ASHRAE 2007 baseline *****
Curve:Bicubic,
ChillerCentEIRPLR, !- Name
-1.360532E-01, !- Coefficient1 Constant
8.642703E-03, !- Coefficient2 x
3.855583E-06, !- Coefficient3 x**2
1.024034E+00, !- Coefficient4 y
6.047444E-02, !- Coefficient5 y**2
-8.947860E-03, !- Coefficient6 x*y
0.000000E+00, !- Coefficient7 x**3
5.706602E-02, !- Coefficient8 y**3
0.000000E+00, !- Coefficient9 x**2*y
0.000000E+00, !- Coefficient10 x*y**2
31.13, !- Minimum Value of x
36.52, !- Maximum Value of x
0.19, !- Minimum Value of y
1.03; !- Maximum Value of y
!- =========== ALL OBJECTS IN CLASS: NODE LIST ===========
NodeList,
Basement Inlet Nodes, !- Name
Basement Direct Air Inlet Node Name; !- Node 1 Name
NodeList,
Core_bottom Inlet Nodes, !- Name
Core_bottom VAV Box Outlet Node; !- Node 1 Name
NodeList,
Core_mid Inlet Nodes, !- Name
Core_mid VAV Box Outlet Node; !- Node 1 Name
NodeList,
Core_top Inlet Nodes, !- Name
Core_top VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_bot_ZN_3 Inlet Nodes, !- Name
Perimeter_bot_ZN_3 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_bot_ZN_2 Inlet Nodes, !- Name
Perimeter_bot_ZN_2 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_bot_ZN_1 Inlet Nodes, !- Name
Perimeter_bot_ZN_1 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_bot_ZN_4 Inlet Nodes, !- Name
Perimeter_bot_ZN_4 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_mid_ZN_3 Inlet Nodes, !- Name
Perimeter_mid_ZN_3 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_mid_ZN_2 Inlet Nodes, !- Name
Perimeter_mid_ZN_2 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_mid_ZN_1 Inlet Nodes, !- Name
Perimeter_mid_ZN_1 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_mid_ZN_4 Inlet Nodes, !- Name
Perimeter_mid_ZN_4 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_top_ZN_3 Inlet Nodes, !- Name
Perimeter_top_ZN_3 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_top_ZN_2 Inlet Nodes, !- Name
Perimeter_top_ZN_2 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_top_ZN_1 Inlet Nodes, !- Name
Perimeter_top_ZN_1 VAV Box Outlet Node; !- Node 1 Name
NodeList,
Perimeter_top_ZN_4 Inlet Nodes, !- Name
Perimeter_top_ZN_4 VAV Box Outlet Node; !- Node 1 Name
NodeList,
CAV_bas_OANode List, !- Name
CAV_bas_OAInlet Node; !- Node 1 Name
NodeList,
VAV_bot WITH REHEAT_OANode List, !- Name
VAV_bot WITH REHEAT_OAInlet Node; !- Node 1 Name
NodeList,
VAV_mid WITH REHEAT_OANode List, !- Name
VAV_mid WITH REHEAT_OAInlet Node; !- Node 1 Name
NodeList,
VAV_top WITH REHEAT_OANode List, !- Name
VAV_top WITH REHEAT_OAInlet Node; !- Node 1 Name
NodeList,
DataCenter Basement Inlets, !- Name
DataCenter Basement Supply Inlet; !- Node 1 Name
NodeList,
DataCenter bot Inlets, !- Name
DataCenter bot Supply Inlet; !- Node 1 Name
NodeList,
DataCenter mid Inlets, !- Name
DataCenter mid Supply Inlet; !- Node 1 Name
NodeList,
DataCenter top Inlets, !- Name
DataCenter top Supply Inlet; !- Node 1 Name
!- =========== ALL OBJECTS IN CLASS: BRANCH LIST ===========
BranchList,
CAV_bas Air Loop Branches, !- Name
CAV_bas Air Loop Main Branch; !- Branch 1 Name
BranchList,
VAV_bot WITH REHEAT Air Loop Branches, !- Name
VAV_bot WITH REHEAT Air Loop Main Branch; !- Branch 1 Name
BranchList,
VAV_mid WITH REHEAT Air Loop Branches, !- Name
VAV_mid WITH REHEAT Air Loop Main Branch; !- Branch 1 Name
BranchList,
VAV_top WITH REHEAT Air Loop Branches, !- Name
VAV_top WITH REHEAT Air Loop Main Branch; !- Branch 1 Name
BranchList,
SHWSys1 Supply Branches, !- Name
SHWSys1 Supply Inlet Branch, !- Branch 1 Name
SHWSys1 Supply Equipment Branch, !- Branch 2 Name
SHWSys1 Supply Equipment Bypass Branch, !- Branch 3 Name
SHWSys1 Supply Outlet Branch; !- Branch 4 Name
BranchList,
SHWSys1 Demand Branches, !- Name
SHWSys1 Demand Inlet Branch, !- Branch 1 Name
SHWSys1 Demand Load Branch 1, !- Branch 2 Name
SHWSys1 Demand Load Branch 2, !- Branch 3 Name
SHWSys1 Demand Load Branch 3, !- Branch 4 Name
SHWSys1 Demand Bypass Branch, !- Branch 5 Name
SHWSys1 Demand Outlet Branch; !- Branch 6 Name
BranchList,
HeatSys1 Supply Branches,!- Name
HeatSys1 Supply Inlet Branch, !- Branch 1 Name
HeatSys1 Supply Equipment Branch, !- Branch 2 Name
HeatSys1 Supply Equipment Bypass Branch, !- Branch 3 Name
HeatSys1 Supply Outlet Branch; !- Branch 4 Name
BranchList,
HeatSys1 Demand Branches,!- Name
HeatSys1 Demand Inlet Branch, !- Branch 1 Name
HeatSys1 Demand Load Branch 1, !- Branch 2 Name
HeatSys1 Demand Load Branch 2, !- Branch 3 Name
HeatSys1 Demand Load Branch 3, !- Branch 4 Name
HeatSys1 Demand Load Branch 4, !- Branch 5 Name
HeatSys1 Demand Load Branch 5, !- Branch 6 Name
HeatSys1 Demand Load Branch 6, !- Branch 7 Name
HeatSys1 Demand Load Branch 7, !- Branch 8 Name
HeatSys1 Demand Load Branch 8, !- Branch 9 Name
HeatSys1 Demand Load Branch 9, !- Branch 10 Name
HeatSys1 Demand Load Branch 10, !- Branch 11 Name
HeatSys1 Demand Load Branch 11, !- Branch 12 Name
HeatSys1 Demand Load Branch 12, !- Branch 13 Name
HeatSys1 Demand Load Branch 13, !- Branch 14 Name
HeatSys1 Demand Load Branch 14, !- Branch 15 Name
HeatSys1 Demand Load Branch 15, !- Branch 16 Name
HeatSys1 Demand Load Branch 17, !- Branch 17 Name
HeatSys1 Demand Load Branch 18, !- Branch 18 Name
HeatSys1 Demand Load Branch 19, !- Branch 19 Name
HeatSys1 Demand Load Branch 20, !- Branch 20 Name
HeatSys1 Demand Load Branch 21, !- Branch 21 Name
HeatSys1 Demand Bypass Branch, !- Branch 22 Name
HeatSys1 Demand Outlet Branch; !- Branch 23 Name
BranchList,
CoolSys1 Supply Supply Side Branches,!- Name
CoolSys1 Supply Inlet Branch, !- Branch 1 Name
CoolSys1 Supply Equipment Branch 1, !- Branch 2 Name
CoolSys1 Supply Equipment Branch 2, !- Branch 3 Name
CoolSys1 Supply Equipment Bypass Branch, !- Branch 4 Name
CoolSys1 Supply Outlet Branch; !- Branch 5 Name
BranchList,
CoolSys1 Demand Demand Side Branches,!- Name
CoolSys1 Demand Inlet Branch, !- Branch 1 Name
CoolSys1 Demand Load Branch 1, !- Branch 2 Name
CoolSys1 Demand Load Branch 2, !- Branch 3 Name
CoolSys1 Demand Load Branch 3, !- Branch 4 Name
CoolSys1 Demand Load Branch 4, !- Branch 5 Name
CoolSys1 Demand Outlet Branch; !- Branch 6 Name
BranchList,
TowerWaterSys Supply Branches, !- Name
TowerWaterSys Supply Inlet Branch, !- Branch 1 Name
TowerWaterSys Supply Equipment Branch 1, !- Branch 2 Name
TowerWaterSys Supply Equipment Branch 2, !- Branch 3 Name
TowerWaterSys Supply Equipment Bypass Branch, !- Branch 4 Name
TowerWaterSys Supply Outlet Branch; !- Branch 5 Name
BranchList,
TowerWaterSys Demand Branches, !- Name
TowerWaterSys Demand Inlet Branch, !- Branch 1 Name
TowerWaterSys Demand Load Branch 1, !- Branch 2 Name
TowerWaterSys Demand Load Branch 2, !- Branch 3 Name
TowerWaterSys Demand Bypass Branch, !- Branch 4 Name
TowerWaterSys Demand Outlet Branch; !- Branch 5 Name
BranchList,
AirLoop DataCenter Basement Branches, !- Name
AirLoop DataCenter Basement Main Branch; !- Branch 1 Name
BranchList,
AirLoop DataCenter bot Branches, !- Name
AirLoop DataCenter bot Main Branch; !- Branch 1 Name
BranchList,
AirLoop DataCenter mid Branches, !- Name
AirLoop DataCenter mid Main Branch; !- Branch 1 Name
BranchList,
AirLoop DataCenter top Branches, !- Name
AirLoop DataCenter top Main Branch; !- Branch 1 Name
BranchList,
Plant Supply Side Branches, !- Name
Plant Supply Inlet Branch, !- Branch 1 Name
Plant Supply Tower Branch, !- Branch 2 Name
Dummy Boiler Branch, !- Branch 3 Name
Plant Supply Bypass Branch, !- Branch 4 Name
Plant Supply Outlet Branch; !- Branch 5 Name
BranchList,
Plant Demand Side Branches, !- Name
Plant Demand Inlet Branch, !- Branch 1 Name
WLHP Cooling Plant Branch AirLoop DataCenter Basement, !- Branch 2 Name
WLHP Heating Plant Branch AirLoop DataCenter Basement, !- Branch 3 Name
WLHP Cooling Plant Branch AirLoop DataCenter bot, !- Branch 4 Name
WLHP Heating Plant Branch AirLoop DataCenter bot, !- Branch 5 Name
WLHP Cooling Plant Branch AirLoop DataCenter mid, !- Branch 6 Name
WLHP Heating Plant Branch AirLoop DataCenter mid, !- Branch 7 Name
WLHP Cooling Plant Branch AirLoop DataCenter top, !- Branch 8 Name
WLHP Heating Plant Branch AirLoop DataCenter top, !- Branch 9 Name
Plant Demand Bypass Branch, !- Branch 10 Name
Plant Demand Outlet Branch; !- Branch 11 Name
BranchList,
CoolSys1 Supply Demand Side Branches, !- Name
CoolSys1 Supply Demand Side Inlet Branch, !- Branch 1 Name
CoolSys1 Heat Exchanger Supply Branch, !- Branch 2 Name
CoolSys1 Supply Side Bypass, !- Branch 3 Name
CoolSys1 Supply Demand Side Outlet Branch; !- Branch 4 Name
BranchList,
CoolSys1 Demand Supply Side Branches, !- Name
CoolSys1 Demand Supply Side Inlet Branch, !- Branch 1 Name
CoolSys1 Heat Exchanger Demand Branch, !- Branch 2 Name
CoolSys1 Demand Side Bypass, !- Branch 3 Name
CoolSys1 Demand Supply Side Outlet Branch; !- Branch 4 Name
!- =========== ALL OBJECTS IN CLASS: CONNECTOR LIST ===========
ConnectorList,
SHWSys1 Supply Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
SHWSys1 Supply Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
SHWSys1 Supply Mixer; !- Connector 2 Name
ConnectorList,
SHWSys1 Demand Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
SHWSys1 Demand Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
SHWSys1 Demand Mixer; !- Connector 2 Name
ConnectorList,
HeatSys1 Supply Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
HeatSys1 Supply Splitter,!- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
HeatSys1 Supply Mixer; !- Connector 2 Name
ConnectorList,
HeatSys1 Demand Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
HeatSys1 Demand Splitter,!- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
HeatSys1 Demand Mixer; !- Connector 2 Name
ConnectorList,
CoolSys1 Supply Supply Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
CoolSys1 Supply Supply Side Splitter,!- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
CoolSys1 Supply Supply Side Mixer; !- Connector 2 Name
ConnectorList,
CoolSys1 Demand Demand Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
CoolSys1 Demand Demand Side Splitter,!- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
CoolSys1 Demand Demand Side Mixer; !- Connector 2 Name
ConnectorList,
TowerWaterSys Supply Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
TowerWaterSys Supply Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
TowerWaterSys Supply Mixer; !- Connector 2 Name
ConnectorList,
TowerWaterSys Demand Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
TowerWaterSys Demand Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
TowerWaterSys Demand Mixer; !- Connector 2 Name
ConnectorList,
CoolSys1 Supply Demand Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
CoolSys1 Supply Demand Side Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
CoolSys1 Supply Demand Side Mixer; !- Connector 2 Name
ConnectorList,
CoolSys1 Demand Supply Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
CoolSys1 Demand Supply Side Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
CoolSys1 Demand Supply Side Mixer; !- Connector 2 Name
ConnectorList,
Plant Supply Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
Plant Supply Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
Plant Supply Mixer; !- Connector 2 Name
ConnectorList,
Plant Demand Side Connectors, !- Name
Connector:Splitter, !- Connector 1 Object Type
Plant Demand Splitter, !- Connector 1 Name
Connector:Mixer, !- Connector 2 Object Type
Plant Demand Mixer; !- Connector 2 Name
!- =========== ALL OBJECTS IN CLASS: BRANCH ===========
Branch,
CAV_bas Air Loop Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
CAV_bas_OA, !- Component 1 Name
CAV_bas Supply Equipment Inlet Node, !- Component 1 Inlet Node Name
CAV_bas_OA-CAV_CoolCNode,!- Component 1 Outlet Node Name
Coil:Cooling:Water, !- Component 2 Object Type
CAV_bas_CoolC, !- Component 2 Name
CAV_bas_OA-CAV_CoolCNode,!- Component 2 Inlet Node Name
CAV_bas_CoolC-CAV_HeatCNode, !- Component 2 Outlet Node Name
Coil:Heating:Water, !- Component 3 Object Type
CAV_bas_HeatC, !- Component 3 Name
CAV_bas_CoolC-CAV_HeatCNode, !- Component 3 Inlet Node Name
CAV_bas_HeatC-CAV_FanNode, !- Component 3 Outlet Node Name
Fan:ConstantVolume, !- Component 4 Object Type
CAV_bas Fan, !- Component 4 Name
CAV_bas_HeatC-CAV_FanNode, !- Component 4 Inlet Node Name
CAV_bas Supply Equipment Outlet Node; !- Component 4 Outlet Node Name
Branch,
VAV_bot WITH REHEAT Air Loop Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
VAV_bot WITH REHEAT_OA, !- Component 1 Name
VAV_bot WITH REHEAT Supply Equipment Inlet Node, !- Component 1 Inlet Node Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 1 Outlet Node Name
Coil:Cooling:Water, !- Component 2 Object Type
VAV_bot WITH REHEAT_CoolC, !- Component 2 Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 2 Inlet Node Name
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 2 Outlet Node Name
Coil:Heating:Water, !- Component 3 Object Type
VAV_bot WITH REHEAT_HeatC, !- Component 3 Name
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 3 Inlet Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 3 Outlet Node Name
Fan:VariableVolume, !- Component 4 Object Type
VAV_bot WITH REHEAT Fan, !- Component 4 Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 4 Inlet Node Name
VAV_bot WITH REHEAT Supply Equipment Outlet Node; !- Component 4 Outlet Node Name
Branch,
VAV_mid WITH REHEAT Air Loop Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
VAV_mid WITH REHEAT_OA, !- Component 1 Name
VAV_mid WITH REHEAT Supply Equipment Inlet Node, !- Component 1 Inlet Node Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 1 Outlet Node Name
Coil:Cooling:Water, !- Component 2 Object Type
VAV_mid WITH REHEAT_CoolC, !- Component 2 Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 2 Inlet Node Name
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 2 Outlet Node Name
Coil:Heating:Water, !- Component 3 Object Type
VAV_mid WITH REHEAT_HeatC, !- Component 3 Name
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 3 Inlet Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 3 Outlet Node Name
Fan:VariableVolume, !- Component 4 Object Type
VAV_mid WITH REHEAT Fan, !- Component 4 Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 4 Inlet Node Name
VAV_mid WITH REHEAT Supply Equipment Outlet Node; !- Component 4 Outlet Node Name
Branch,
VAV_top WITH REHEAT Air Loop Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
VAV_top WITH REHEAT_OA, !- Component 1 Name
VAV_top WITH REHEAT Supply Equipment Inlet Node, !- Component 1 Inlet Node Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 1 Outlet Node Name
Coil:Cooling:Water, !- Component 2 Object Type
VAV_top WITH REHEAT_CoolC, !- Component 2 Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Component 2 Inlet Node Name
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 2 Outlet Node Name
Coil:Heating:Water, !- Component 3 Object Type
VAV_top WITH REHEAT_HeatC, !- Component 3 Name
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Component 3 Inlet Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 3 Outlet Node Name
Fan:VariableVolume, !- Component 4 Object Type
VAV_top WITH REHEAT Fan, !- Component 4 Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Component 4 Inlet Node Name
VAV_top WITH REHEAT Supply Equipment Outlet Node; !- Component 4 Outlet Node Name
Branch,
SHWSys1 Supply Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pump:ConstantSpeed, !- Component 1 Object Type
SHWSys1 Pump, !- Component 1 Name
SHWSys1 Supply Inlet Node, !- Component 1 Inlet Node Name
SHWSys1 Pump-SHWSys1 Water HeaterNodeviaConnector; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Supply Equipment Branch, !- Name
, !- Pressure Drop Curve Name
WaterHeater:Mixed, !- Component 1 Object Type
SHWSys1 Water Heater, !- Component 1 Name
SHWSys1 Pump-SHWSys1 Water HeaterNode, !- Component 1 Inlet Node Name
SHWSys1 Supply Equipment Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Supply Equipment Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
SHWSys1 Supply Equipment Bypass Pipe, !- Component 1 Name
SHWSys1 Supply Equip Bypass Inlet Node, !- Component 1 Inlet Node Name
SHWSys1 Supply Equip Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Supply Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
SHWSys1 Supply Outlet Pipe, !- Component 1 Name
SHWSys1 Supply Mixer-SHWSys1 Supply Outlet Pipe, !- Component 1 Inlet Node Name
SHWSys1 Supply Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
SHWSys1 Demand Inlet Pipe, !- Component 1 Name
SHWSys1 Demand Inlet Node, !- Component 1 Inlet Node Name
SHWSys1 Demand Inlet Pipe-SHWSys1 Demand Mixer; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Load Branch 1, !- Name
, !- Pressure Drop Curve Name
WaterUse:Connections, !- Component 1 Object Type
Core_bottom sub cat, !- Component 1 Name
Core_bottom sub cat Water Inlet Node, !- Component 1 Inlet Node Name
Core_bottom sub cat Water Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Load Branch 2, !- Name
, !- Pressure Drop Curve Name
WaterUse:Connections, !- Component 1 Object Type
Core_mid sub cat, !- Component 1 Name
Core_mid sub cat Water Inlet Node, !- Component 1 Inlet Node Name
Core_mid sub cat Water Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Load Branch 3, !- Name
, !- Pressure Drop Curve Name
WaterUse:Connections, !- Component 1 Object Type
Core_top sub cat, !- Component 1 Name
Core_top sub cat Water Inlet Node, !- Component 1 Inlet Node Name
Core_top sub cat Water Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
SHWSys1 Demand Bypass Pipe, !- Component 1 Name
SHWSys1 Demand Bypass Pipe Inlet Node, !- Component 1 Inlet Node Name
SHWSys1 Demand Bypass Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
SHWSys1 Demand Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
SHWSys1 Demand Outlet Pipe, !- Component 1 Name
SHWSys1 Demand Mixer-SHWSys1 Demand Outlet Pipe, !- Component 1 Inlet Node Name
SHWSys1 Demand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Supply Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pump:VariableSpeed, !- Component 1 Object Type
HeatSys1 Pump, !- Component 1 Name
HeatSys1 Supply Inlet Node, !- Component 1 Inlet Node Name
HeatSys1 Pump-HeatSys1 BoilerNodeviaConnector; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Supply Equipment Branch, !- Name
, !- Pressure Drop Curve Name
Boiler:HotWater, !- Component 1 Object Type
HeatSys1 Boiler, !- Component 1 Name
HeatSys1 Pump-HeatSys1 BoilerNode, !- Component 1 Inlet Node Name
HeatSys1 Supply Equipment Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Supply Equipment Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
HeatSys1 Supply Equipment Bypass Pipe, !- Component 1 Name
HeatSys1 Supply Equip Bypass Inlet Node, !- Component 1 Inlet Node Name
HeatSys1 Supply Equip Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Supply Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
HeatSys1 Supply Outlet Pipe, !- Component 1 Name
HeatSys1 Supply Mixer-HeatSys1 Supply Outlet Pipe, !- Component 1 Inlet Node Name
HeatSys1 Supply Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
HeatSys1 Demand Inlet Pipe, !- Component 1 Name
HeatSys1 Demand Inlet Node, !- Component 1 Inlet Node Name
HeatSys1 Demand Inlet Pipe-HeatSys1 Demand Mixer; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 1, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Core_bottom VAV Box Reheat Coil, !- Component 1 Name
Core_bottom VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Core_bottom VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 2, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Core_mid VAV Box Reheat Coil, !- Component 1 Name
Core_mid VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Core_mid VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 3, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Core_top VAV Box Reheat Coil, !- Component 1 Name
Core_top VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Core_top VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 4, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_bot_ZN_3 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_bot_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_bot_ZN_3 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 5, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_bot_ZN_2 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_bot_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_bot_ZN_2 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 6, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_bot_ZN_1 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_bot_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_bot_ZN_1 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 7, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_bot_ZN_4 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_bot_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_bot_ZN_4 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 8, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_mid_ZN_3 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_mid_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_mid_ZN_3 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 9, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_mid_ZN_2 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_mid_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_mid_ZN_2 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 10, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_mid_ZN_1 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_mid_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_mid_ZN_1 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 11, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_mid_ZN_4 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_mid_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_mid_ZN_4 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 12, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_top_ZN_3 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_top_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_top_ZN_3 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 13, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_top_ZN_2 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_top_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_top_ZN_2 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 14, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_top_ZN_1 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_top_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_top_ZN_1 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 15, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
Perimeter_top_ZN_4 VAV Box Reheat Coil, !- Component 1 Name
Perimeter_top_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Component 1 Inlet Node Name
Perimeter_top_ZN_4 VAV Box Reheat CoilDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 17, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
VAV_bot WITH REHEAT_HeatC, !- Component 1 Name
VAV_bot WITH REHEAT_HeatCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_bot WITH REHEAT_HeatCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 18, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
VAV_mid WITH REHEAT_HeatC, !- Component 1 Name
VAV_mid WITH REHEAT_HeatCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_mid WITH REHEAT_HeatCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 19, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
VAV_top WITH REHEAT_HeatC, !- Component 1 Name
VAV_top WITH REHEAT_HeatCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_top WITH REHEAT_HeatCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 20, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
CAV_bas_HeatC, !- Component 1 Name
CAV_bas_HeatCDemand Inlet Node, !- Component 1 Inlet Node Name
CAV_bas_HeatCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Load Branch 21, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:Water, !- Component 1 Object Type
DataCenter_ExtraWaterHeatC, !- Component 1 Name
DataCenter_ExtraWaterHeatCDemand Inlet Node, !- Component 1 Inlet Node Name
DataCenter_ExtraWaterHeatCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
HeatSys1 Demand Bypass Pipe, !- Component 1 Name
HeatSys1 Demand Bypass Pipe Inlet Node, !- Component 1 Inlet Node Name
HeatSys1 Demand Bypass Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
HeatSys1 Demand Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
HeatSys1 Demand Outlet Pipe, !- Component 1 Name
HeatSys1 Demand Mixer-HeatSys1 Demand Outlet Pipe, !- Component 1 Inlet Node Name
HeatSys1 Demand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Inlet Pipe, !- Component 1 Name
CoolSys1 Supply Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Pump-CoolSys1 ChillerNodeviaConnector; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Equipment Branch 1, !- Name
, !- Pressure Drop Curve Name
Pump:ConstantSpeed, !- Component 1 Object Type
CoolSys1 Chiller1 Pump, !- Component 1 Name
CoolSys1 Chiller1 Pump Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Pump-CoolSys1 Chiller1Node, !- Component 1 Outlet Node Name
Chiller:Electric:ReformulatedEIR, !- Component 2 Object Type
CoolSys1 Chiller1, !- Component 2 Name
CoolSys1 Pump-CoolSys1 Chiller1Node, !- Component 2 Inlet Node Name
CoolSys1 Supply Equipment Outlet Node 1; !- Component 2 Outlet Node Name
Branch,
CoolSys1 Supply Equipment Branch 2, !- Name
, !- Pressure Drop Curve Name
Pump:ConstantSpeed, !- Component 1 Object Type
CoolSys1 Chiller2 Pump, !- Component 1 Name
CoolSys1 Chiller2 Pump Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Pump-CoolSys1 Chiller2Node, !- Component 1 Outlet Node Name
Chiller:Electric:ReformulatedEIR, !- Component 2 Object Type
CoolSys1 Chiller2, !- Component 2 Name
CoolSys1 Pump-CoolSys1 Chiller2Node, !- Component 2 Inlet Node Name
CoolSys1 Supply Equipment Outlet Node 2; !- Component 2 Outlet Node Name
Branch,
CoolSys1 Supply Equipment Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Equipment Bypass Pipe, !- Component 1 Name
CoolSys1 Supply Equip Bypass Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Supply Equip Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Outlet Pipe, !- Component 1 Name
CoolSys1 Supply Mixer-CoolSys1 Supply Outlet Pipe, !- Component 1 Inlet Node Name
CoolSys1 Supply Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pump:VariableSpeed, !- Component 1 Object Type
CoolSys1 Pump Secondary, !- Component 1 Name
CoolSys1 Demand Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Pump Secondary-CoolSys1 Demand Mixer; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Load Branch 1, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:Water, !- Component 1 Object Type
VAV_bot WITH REHEAT_CoolC, !- Component 1 Name
VAV_bot WITH REHEAT_CoolCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_bot WITH REHEAT_CoolCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Load Branch 2, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:Water, !- Component 1 Object Type
VAV_mid WITH REHEAT_CoolC, !- Component 1 Name
VAV_mid WITH REHEAT_CoolCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_mid WITH REHEAT_CoolCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Load Branch 3, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:Water, !- Component 1 Object Type
VAV_top WITH REHEAT_CoolC, !- Component 1 Name
VAV_top WITH REHEAT_CoolCDemand Inlet Node, !- Component 1 Inlet Node Name
VAV_top WITH REHEAT_CoolCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Load Branch 4, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:Water, !- Component 1 Object Type
CAV_bas_CoolC, !- Component 1 Name
CAV_bas_CoolCDemand Inlet Node, !- Component 1 Inlet Node Name
CAV_bas_CoolCDemand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Demand Outlet Pipe, !- Component 1 Name
CoolSys1 Demand Mixer-CoolSys1 Demand Outlet Pipe, !- Component 1 Inlet Node Name
CoolSys1 Demand Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Supply Inlet Branch, !- Name
, !- Pressure Drop Curve Name
HeaderedPumps:VariableSpeed, !- Component 1 Object Type
TowerWaterSys Pump, !- Component 1 Name
TowerWaterSys Supply Inlet Node, !- Component 1 Inlet Node Name
TowerWaterSys Pump-TowerWaterSys CoolTowerNodeviaConnector; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Supply Equipment Branch 1, !- Name
, !- Pressure Drop Curve Name
CoolingTower:VariableSpeed, !- Component 1 Object Type
TowerWaterSys CoolTower 1, !- Component 1 Name
TowerWaterSys Pump-TowerWaterSys CoolTower1Node, !- Component 1 Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node 1; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Supply Equipment Branch 2, !- Name
, !- Pressure Drop Curve Name
CoolingTower:VariableSpeed, !- Component 1 Object Type
TowerWaterSys CoolTower 2, !- Component 1 Name
TowerWaterSys Pump-TowerWaterSys CoolTower2Node, !- Component 1 Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node 2; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Supply Equipment Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
TowerWaterSys Supply Equipment Bypass Pipe, !- Component 1 Name
TowerWaterSys Supply Equip Bypass Inlet Node, !- Component 1 Inlet Node Name
TowerWaterSys Supply Equip Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Supply Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
TowerWaterSys Supply Outlet Pipe, !- Component 1 Name
TowerWaterSys Supply Mixer-TowerWaterSys Supply Outlet Pipe, !- Component 1 Inlet Node Name
TowerWaterSys Supply Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Demand Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
TowerWaterSys Demand Inlet Pipe, !- Component 1 Name
TowerWaterSys Demand Inlet Node, !- Component 1 Inlet Node Name
TowerWaterSys Demand Inlet Pipe-TowerWaterSys Demand Mixer; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Demand Load Branch 1, !- Name
, !- Pressure Drop Curve Name
Chiller:Electric:ReformulatedEIR, !- Component 1 Object Type
CoolSys1 Chiller1, !- Component 1 Name
CoolSys1 Chiller1 Water Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Chiller1 Water Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Demand Load Branch 2, !- Name
, !- Pressure Drop Curve Name
Chiller:Electric:ReformulatedEIR, !- Component 1 Object Type
CoolSys1 Chiller2, !- Component 1 Name
CoolSys1 Chiller2 Water Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Chiller2 Water Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Demand Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
TowerWaterSys Demand Bypass Pipe, !- Component 1 Name
TowerWaterSys Demand Bypass Pipe Inlet Node, !- Component 1 Inlet Node Name
TowerWaterSys Demand Bypass Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
TowerWaterSys Demand Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
TowerWaterSys Demand Outlet Pipe, !- Component 1 Name
TowerWaterSys Demand Mixer-TowerWaterSys Demand Outlet Pipe, !- Component 1 Inlet Node Name
TowerWaterSys Demand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Heat Exchanger Supply Branch, !- Name
, !- Pressure Drop Curve Name
HeatExchanger:FluidToFluid, !- Component 1 Object Type
Bypass Heat exchanger, !- Component 1 Name
CoolSys1 Exchancher Supply Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Exchancher Supply Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Heat Exchanger Demand Branch, !- Name
, !- Pressure Drop Curve Name
HeatExchanger:FluidToFluid, !- Component 1 Object Type
Bypass Heat exchanger, !- Component 1 Name
CoolSys1 Exchancher Demand Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Exchancher Demand Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Side Bypass, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Bypass, !- Component 1 Name
CoolSys1 Supply Bypass Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Supply Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Side Bypass, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Demand Bypass, !- Component 1 Name
CoolSys1 Demand Bypass Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Demand Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Demand Side Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Demand Side Inlet Pipe, !- Component 1 Name
CoolSys1 Supply Demand Side Inlet Pipe Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Supply Demand Side Inlet Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Supply Demand Side Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Supply Demand Side Outlet Pipe , !- Component 1 Name
CoolSys1 Supply Demand Side Outlet Pipe Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Supply Demand Side Outlet Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Supply Side Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Demand Supply Side Inlet Pipe , !- Component 1 Name
CoolSys1 Demand Supply Side Inlet Pipe Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Demand Supply Side Inlet Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
CoolSys1 Demand Supply Side Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
CoolSys1 Demand Supply Side Outlet Pipe , !- Component 1 Name
CoolSys1 Demand Supply Side Outlet Pipe Inlet Node, !- Component 1 Inlet Node Name
CoolSys1 Demand Supply Side Outlet Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
AirLoop DataCenter Basement Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
AirLoop DataCenter Basement OA System, !- Component 1 Name
AirLoop DataCenter Basement Return Air Inlet, !- Component 1 Inlet Node Name
DataCenter Basement Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir, !- Component 2 Object Type
AirLoop DataCenter Basement DXAC Heat Pump, !- Component 2 Name
DataCenter Basement Mixed Air Outlet, !- Component 2 Inlet Node Name
AirLoop DataCenter Basement Humidifier Inlet, !- Component 2 Outlet Node Name
Humidifier:Steam:Electric, !- Component 3 Object Type
DataCenter Basement Humidifier, !- Component 3 Name
AirLoop DataCenter Basement Humidifier Inlet, !- Component 3 Inlet Node Name
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode, !- Component 3 Outlet Node Name
Coil:Heating:Electric, !- Component 4 Object Type
DataCenter_ExtraElecHeatC, !- Component 4 Name
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode, !- Component 4 Inlet Node Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode, !- Component 4 Outlet Node Name
Coil:Heating:Water, !- Component 5 Object Type
DataCenter_ExtraWaterHeatC, !- Component 5 Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode, !- Component 5 Inlet Node Name
AirLoop DataCenter Basement Supply Air Outlet; !- Component 5 Outlet Node Name
Branch,
AirLoop DataCenter bot Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
AirLoop DataCenter bot OA System, !- Component 1 Name
AirLoop DataCenter bot Return Air Inlet, !- Component 1 Inlet Node Name
DataCenter bot Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir, !- Component 2 Object Type
AirLoop DataCenter bot DXAC Heat Pump, !- Component 2 Name
DataCenter bot Mixed Air Outlet, !- Component 2 Inlet Node Name
AirLoop DataCenter bot Supply Air Outlet; !- Component 2 Outlet Node Name
Branch,
AirLoop DataCenter mid Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
AirLoop DataCenter mid OA System, !- Component 1 Name
AirLoop DataCenter mid Return Air Inlet, !- Component 1 Inlet Node Name
DataCenter mid Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir, !- Component 2 Object Type
AirLoop DataCenter mid DXAC Heat Pump, !- Component 2 Name
DataCenter mid Mixed Air Outlet, !- Component 2 Inlet Node Name
AirLoop DataCenter mid Supply Air Outlet; !- Component 2 Outlet Node Name
Branch,
AirLoop DataCenter top Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
AirLoop DataCenter top OA System, !- Component 1 Name
AirLoop DataCenter top Return Air Inlet, !- Component 1 Inlet Node Name
DataCenter top Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir, !- Component 2 Object Type
AirLoop DataCenter top DXAC Heat Pump, !- Component 2 Name
DataCenter top Mixed Air Outlet, !- Component 2 Inlet Node Name
AirLoop DataCenter top Supply Air Outlet; !- Component 2 Outlet Node Name
Branch,
Plant Supply Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pump:ConstantSpeed, !- Component 1 Object Type
Plant Circ Pump, !- Component 1 Name
Plant Supply Inlet Node, !- Component 1 Inlet Node Name
Plant Pump Outlet Node; !- Component 1 Outlet Node Name
Branch,
Plant Supply Tower Branch, !- Name
, !- Pressure Drop Curve Name
FluidCooler:TwoSpeed, !- Component 1 Object Type
Central Tower, !- Component 1 Name
Central Tower Inlet Node,!- Component 1 Inlet Node Name
Central Tower Outlet Node; !- Component 1 Outlet Node Name
Branch,
Dummy Boiler Branch, !- Name
, !- Pressure Drop Curve Name
Boiler:HotWater, !- Component 1 Object Type
Dummy Boiler, !- Component 1 Name
Dummy Boiler Inlet Node, !- Component 1 Inlet Node Name
Dummy Boiler Outlet Node;!- Component 1 Outlet Node Name
Branch,
Plant Supply Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
Plant Supply Side Bypass,!- Component 1 Name
Plant Supply Bypass Inlet Node, !- Component 1 Inlet Node Name
Plant Supply Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
Plant Supply Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
Plant Supply Outlet, !- Component 1 Name
Plant Supply Exit Pipe Inlet Node, !- Component 1 Inlet Node Name
Plant Supply Outlet Node;!- Component 1 Outlet Node Name
Branch,
Plant Demand Inlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
Plant Demand Inlet Pipe, !- Component 1 Name
Plant Demand Inlet Node, !- Component 1 Inlet Node Name
Plant Demand Entrance Pipe Outlet Node; !- Component 1 Outlet Node Name
Branch,
Plant Demand Bypass Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
Plant Demand Side Bypass,!- Component 1 Name
Cond Demand Bypass Inlet Node, !- Component 1 Inlet Node Name
Cond Demand Bypass Outlet Node; !- Component 1 Outlet Node Name
Branch,
Plant Demand Outlet Branch, !- Name
, !- Pressure Drop Curve Name
Pipe:Adiabatic, !- Component 1 Object Type
Plant Demand Outlet Pipe,!- Component 1 Name
Plant Demand Exit Pipe Inlet Node, !- Component 1 Inlet Node Name
Plant Demand Outlet Node;!- Component 1 Outlet Node Name
Branch,
WLHP Cooling Plant Branch AirLoop DataCenter Basement, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Cooling Mode AirLoop DataCenter Basement, !- Component 1 Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side1 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side1 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Heating Plant Branch AirLoop DataCenter Basement, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Heating Mode AirLoop DataCenter Basement, !- Component 1 Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side2 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side2 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Cooling Plant Branch AirLoop DataCenter bot, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Cooling Mode AirLoop DataCenter bot, !- Component 1 Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side1 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side1 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Cooling Plant Branch AirLoop DataCenter mid, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Cooling Mode AirLoop DataCenter mid, !- Component 1 Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side1 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side1 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Cooling Plant Branch AirLoop DataCenter top, !- Name
, !- Pressure Drop Curve Name
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Cooling Mode AirLoop DataCenter top, !- Component 1 Name
AirLoop DataCenter top Water to Air Heat Pump Source Side1 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter top Water to Air Heat Pump Source Side1 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Heating Plant Branch AirLoop DataCenter bot, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Heating Mode AirLoop DataCenter bot, !- Component 1 Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side2 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side2 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Heating Plant Branch AirLoop DataCenter mid, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Heating Mode AirLoop DataCenter mid, !- Component 1 Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side2 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side2 Outlet Node; !- Component 1 Outlet Node Name
Branch,
WLHP Heating Plant Branch AirLoop DataCenter top, !- Name
, !- Pressure Drop Curve Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Component 1 Object Type
Heat Pump Heating Mode AirLoop DataCenter top, !- Component 1 Name
AirLoop DataCenter top Water to Air Heat Pump Source Side2 Inlet Node, !- Component 1 Inlet Node Name
AirLoop DataCenter top Water to Air Heat Pump Source Side2 Outlet Node; !- Component 1 Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: PIPE ===========
Pipe:Adiabatic,
SHWSys1 Supply Equipment Bypass Pipe, !- Name
SHWSys1 Supply Equip Bypass Inlet Node, !- Inlet Node Name
SHWSys1 Supply Equip Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
SHWSys1 Supply Outlet Pipe, !- Name
SHWSys1 Supply Mixer-SHWSys1 Supply Outlet Pipe, !- Inlet Node Name
SHWSys1 Supply Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
SHWSys1 Demand Inlet Pipe, !- Name
SHWSys1 Demand Inlet Node, !- Inlet Node Name
SHWSys1 Demand Inlet Pipe-SHWSys1 Demand Mixer; !- Outlet Node Name
Pipe:Adiabatic,
SHWSys1 Demand Bypass Pipe, !- Name
SHWSys1 Demand Bypass Pipe Inlet Node, !- Inlet Node Name
SHWSys1 Demand Bypass Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
SHWSys1 Demand Outlet Pipe, !- Name
SHWSys1 Demand Mixer-SHWSys1 Demand Outlet Pipe, !- Inlet Node Name
SHWSys1 Demand Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
HeatSys1 Supply Equipment Bypass Pipe, !- Name
HeatSys1 Supply Equip Bypass Inlet Node, !- Inlet Node Name
HeatSys1 Supply Equip Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
HeatSys1 Supply Outlet Pipe, !- Name
HeatSys1 Supply Mixer-HeatSys1 Supply Outlet Pipe, !- Inlet Node Name
HeatSys1 Supply Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
HeatSys1 Demand Inlet Pipe, !- Name
HeatSys1 Demand Inlet Node, !- Inlet Node Name
HeatSys1 Demand Inlet Pipe-HeatSys1 Demand Mixer; !- Outlet Node Name
Pipe:Adiabatic,
HeatSys1 Demand Bypass Pipe, !- Name
HeatSys1 Demand Bypass Pipe Inlet Node, !- Inlet Node Name
HeatSys1 Demand Bypass Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
HeatSys1 Demand Outlet Pipe, !- Name
HeatSys1 Demand Mixer-HeatSys1 Demand Outlet Pipe, !- Inlet Node Name
HeatSys1 Demand Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Inlet Pipe, !- Name
CoolSys1 Supply Inlet Node, !- Inlet Node Name
CoolSys1 Pump-CoolSys1 ChillerNodeviaConnector; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Equipment Bypass Pipe, !- Name
CoolSys1 Supply Equip Bypass Inlet Node, !- Inlet Node Name
CoolSys1 Supply Equip Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Outlet Pipe, !- Name
CoolSys1 Supply Mixer-CoolSys1 Supply Outlet Pipe, !- Inlet Node Name
CoolSys1 Supply Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Demand Outlet Pipe, !- Name
CoolSys1 Demand Mixer-CoolSys1 Demand Outlet Pipe, !- Inlet Node Name
CoolSys1 Demand Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
TowerWaterSys Supply Equipment Bypass Pipe, !- Name
TowerWaterSys Supply Equip Bypass Inlet Node, !- Inlet Node Name
TowerWaterSys Supply Equip Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
TowerWaterSys Supply Outlet Pipe, !- Name
TowerWaterSys Supply Mixer-TowerWaterSys Supply Outlet Pipe, !- Inlet Node Name
TowerWaterSys Supply Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
TowerWaterSys Demand Inlet Pipe, !- Name
TowerWaterSys Demand Inlet Node, !- Inlet Node Name
TowerWaterSys Demand Inlet Pipe-TowerWaterSys Demand Mixer; !- Outlet Node Name
Pipe:Adiabatic,
TowerWaterSys Demand Bypass Pipe, !- Name
TowerWaterSys Demand Bypass Pipe Inlet Node, !- Inlet Node Name
TowerWaterSys Demand Bypass Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
TowerWaterSys Demand Outlet Pipe, !- Name
TowerWaterSys Demand Mixer-TowerWaterSys Demand Outlet Pipe, !- Inlet Node Name
TowerWaterSys Demand Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
Plant Demand Inlet Pipe, !- Name
Plant Demand Inlet Node, !- Inlet Node Name
Plant Demand Entrance Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
Plant Demand Side Bypass,!- Name
Cond Demand Bypass Inlet Node, !- Inlet Node Name
Cond Demand Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
Plant Demand Outlet Pipe,!- Name
Plant Demand Exit Pipe Inlet Node, !- Inlet Node Name
Plant Demand Outlet Node;!- Outlet Node Name
Pipe:Adiabatic,
Plant Supply Side Bypass,!- Name
Plant Supply Bypass Inlet Node, !- Inlet Node Name
Plant Supply Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
Plant Supply Outlet, !- Name
Plant Supply Exit Pipe Inlet Node, !- Inlet Node Name
Plant Supply Outlet Node;!- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Bypass, !- Name
CoolSys1 Supply Bypass Inlet Node, !- Inlet Node Name
CoolSys1 Supply Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Demand Bypass, !- Name
CoolSys1 Demand Bypass Inlet Node, !- Inlet Node Name
CoolSys1 Demand Bypass Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Demand Side Inlet Pipe, !- Name
CoolSys1 Supply Demand Side Inlet Pipe Inlet Node, !- Inlet Node Name
CoolSys1 Supply Demand Side Inlet Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Supply Demand Side Outlet Pipe , !- Name
CoolSys1 Supply Demand Side Outlet Pipe Inlet Node, !- Inlet Node Name
CoolSys1 Supply Demand Side Outlet Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Demand Supply Side Outlet Pipe , !- Name
CoolSys1 Demand Supply Side Outlet Pipe Inlet Node, !- Inlet Node Name
CoolSys1 Demand Supply Side Outlet Pipe Outlet Node; !- Outlet Node Name
Pipe:Adiabatic,
CoolSys1 Demand Supply Side Inlet Pipe , !- Name
CoolSys1 Demand Supply Side Inlet Pipe Inlet Node, !- Inlet Node Name
CoolSys1 Demand Supply Side Inlet Pipe Outlet Node; !- Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: PLANT LOOP ===========
PlantLoop,
SHWSys1, !- Name
WATER, !- Fluid Type
, !- User Defined Fluid Type
SHWSys1 Loop Operation Scheme List, !- Plant Equipment Operation Scheme Name
SHWSys1 Supply Outlet Node, !- Loop Temperature Setpoint Node Name
60.0, !- Maximum Loop Temperature {C}
10.0, !- Minimum Loop Temperature {C}
AUTOSIZE, !- Maximum Loop Flow Rate {m3/s}
0.0, !- Minimum Loop Flow Rate {m3/s}
AUTOSIZE, !- Plant Loop Volume {m3}
SHWSys1 Supply Inlet Node, !- Plant Side Inlet Node Name
SHWSys1 Supply Outlet Node, !- Plant Side Outlet Node Name
SHWSys1 Supply Branches, !- Plant Side Branch List Name
SHWSys1 Supply Connectors, !- Plant Side Connector List Name
SHWSys1 Demand Inlet Node, !- Demand Side Inlet Node Name
SHWSys1 Demand Outlet Node, !- Demand Side Outlet Node Name
SHWSys1 Demand Branches, !- Demand Side Branch List Name
SHWSys1 Demand Connectors, !- Demand Side Connector List Name
Optimal; !- Load Distribution Scheme
PlantLoop,
HeatSys1, !- Name
WATER, !- Fluid Type
, !- User Defined Fluid Type
HeatSys1 Loop Operation Scheme List, !- Plant Equipment Operation Scheme Name
HeatSys1 Supply Outlet Node, !- Loop Temperature Setpoint Node Name
100.0, !- Maximum Loop Temperature {C}
10.0, !- Minimum Loop Temperature {C}
AUTOSIZE, !- Maximum Loop Flow Rate {m3/s}
0.0, !- Minimum Loop Flow Rate {m3/s}
AUTOSIZE, !- Plant Loop Volume {m3}
HeatSys1 Supply Inlet Node, !- Plant Side Inlet Node Name
HeatSys1 Supply Outlet Node, !- Plant Side Outlet Node Name
HeatSys1 Supply Branches,!- Plant Side Branch List Name
HeatSys1 Supply Connectors, !- Plant Side Connector List Name
HeatSys1 Demand Inlet Node, !- Demand Side Inlet Node Name
HeatSys1 Demand Outlet Node, !- Demand Side Outlet Node Name
HeatSys1 Demand Branches,!- Demand Side Branch List Name
HeatSys1 Demand Connectors, !- Demand Side Connector List Name
Optimal; !- Load Distribution Scheme
PlantLoop,
CoolSys1_Supply, !- Name
WATER, !- Fluid Type
, !- User Defined Fluid Type
CoolSys1 Loop Operation Scheme List, !- Plant Equipment Operation Scheme Name
CoolSys1 Supply Outlet Node, !- Loop Temperature Setpoint Node Name
98.0, !- Maximum Loop Temperature {C}
1.0, !- Minimum Loop Temperature {C}
AUTOSIZE, !- Maximum Loop Flow Rate {m3/s}
0.0, !- Minimum Loop Flow Rate {m3/s}
autocalculate, !- Plant Loop Volume {m3}
CoolSys1 Supply Inlet Node, !- Plant Side Inlet Node Name
CoolSys1 Supply Outlet Node, !- Plant Side Outlet Node Name
CoolSys1 Supply Supply Side Branches, !- Plant Side Branch List Name
CoolSys1 Supply Supply Side Connectors, !- Plant Side Connector List Name
CoolSys1 Supply Demand Side Inlet Pipe Inlet Node, !- Demand Side Inlet Node Name
CoolSys1 Supply Demand Side Outlet Pipe Outlet Node, !- Demand Side Outlet Node Name
CoolSys1 Supply Demand Side Branches, !- Demand Side Branch List Name
CoolSys1 Supply Demand Side Connectors, !- Demand Side Connector List Name
UniformLoad; !- Load Distribution Scheme
PlantLoop,
CoolSys1_Demand, !- Name
Water, !- Fluid Type
, !- User Defined Fluid Type
CoolSys1 Sec Loop Operation, !- Plant Equipment Operation Scheme Name
CoolSys1 Demand Inlet Node, !- Loop Temperature Setpoint Node Name
98, !- Maximum Loop Temperature {C}
1, !- Minimum Loop Temperature {C}
autosize, !- Maximum Loop Flow Rate {m3/s}
0, !- Minimum Loop Flow Rate {m3/s}
autocalculate, !- Plant Loop Volume {m3}
CoolSys1 Demand Supply Side Inlet Pipe Inlet Node, !- Plant Side Inlet Node Name
CoolSys1 Demand Supply Side Outlet Pipe Outlet Node, !- Plant Side Outlet Node Name
CoolSys1 Demand Supply Side Branches, !- Plant Side Branch List Name
CoolSys1 Demand Supply Side Connectors, !- Plant Side Connector List Name
CoolSys1 Demand Inlet Node, !- Demand Side Inlet Node Name
CoolSys1 Demand Outlet Node, !- Demand Side Outlet Node Name
CoolSys1 Demand Demand Side Branches, !- Demand Side Branch List Name
CoolSys1 Demand Demand Side Connectors, !- Demand Side Connector List Name
UniformLoad; !- Load Distribution Scheme
PlantLoop,
Single Water Plant Loop, !- Name
UserDefinedFluidType, !- Fluid Type
EthyleneGlycol40Percent, !- User Defined Fluid Type
Plant Loop Operation, !- Plant Equipment Operation Scheme Name
Plant Supply Outlet Node,!- Loop Temperature Setpoint Node Name
35, !- Maximum Loop Temperature {C}
10, !- Minimum Loop Temperature {C}
autosize, !- Maximum Loop Flow Rate {m3/s}
0, !- Minimum Loop Flow Rate {m3/s}
autocalculate, !- Plant Loop Volume {m3}
Plant Supply Inlet Node, !- Plant Side Inlet Node Name
Plant Supply Outlet Node,!- Plant Side Outlet Node Name
Plant Supply Side Branches, !- Plant Side Branch List Name
Plant Supply Side Connectors, !- Plant Side Connector List Name
Plant Demand Inlet Node, !- Demand Side Inlet Node Name
Plant Demand Outlet Node,!- Demand Side Outlet Node Name
Plant Demand Side Branches, !- Demand Side Branch List Name
Plant Demand Side Connectors, !- Demand Side Connector List Name
SequentialLoad, !- Load Distribution Scheme
, !- Availability Manager List Name
DualSetpointDeadband; !- Plant Loop Demand Calculation Scheme
!- =========== ALL OBJECTS IN CLASS: CONDENSER LOOP ===========
!- Minimum and maximum Loop Temperatures are relaxed and not used to set the control or sizing limits.
CondenserLoop,
TowerWaterSys, !- Name
Water, !- Fluid Type
, !- User Defined Fluid Type
TowerWaterSys Loop Operation Scheme List, !- Condenser Equipment Operation Scheme Name
TowerWaterSys Supply Outlet Node, !- Condenser Loop Temperature Setpoint Node Name
80.0, !- Maximum Loop Temperature {C}
5.0, !- Minimum Loop Temperature {C}
AUTOSIZE, !- Maximum Loop Flow Rate {m3/s}
0.0, !- Minimum Loop Flow Rate {m3/s}
AUTOSIZE, !- Condenser Loop Volume {m3}
TowerWaterSys Supply Inlet Node, !- Condenser Side Inlet Node Name
TowerWaterSys Supply Outlet Node, !- Condenser Side Outlet Node Name
TowerWaterSys Supply Branches, !- Condenser Side Branch List Name
TowerWaterSys Supply Connectors, !- Condenser Side Connector List Name
TowerWaterSys Demand Inlet Node, !- Demand Side Inlet Node Name
TowerWaterSys Demand Outlet Node, !- Demand Side Outlet Node Name
TowerWaterSys Demand Branches, !- Condenser Demand Side Branch List Name
TowerWaterSys Demand Connectors, !- Condenser Demand Side Connector List Name
SequentialLoad; !- Load Distribution Scheme
!- =========== ALL OBJECTS IN CLASS: PLANT OPERATION SCHEMES ===========
PlantEquipmentOperationSchemes,
SHWSys1 Loop Operation Scheme List, !- Name
PlantEquipmentOperation:HeatingLoad, !- Control Scheme 1 Object Type
SHWSys1 Operation Scheme,!- Control Scheme 1 Name
PlantOnSched; !- Control Scheme 1 Schedule Name
PlantEquipmentOperationSchemes,
HeatSys1 Loop Operation Scheme List, !- Name
PlantEquipmentOperation:HeatingLoad, !- Control Scheme 1 Object Type
HeatSys1 Operation Scheme, !- Control Scheme 1 Name
PlantOnSched; !- Control Scheme 1 Schedule Name
PlantEquipmentOperationSchemes,
CoolSys1 Loop Operation Scheme List, !- Name
PlantEquipmentOperation:CoolingLoad, !- Control Scheme 1 Object Type
CoolSys1 Operation Scheme, !- Control Scheme 1 Name
PlantOnSched; !- Control Scheme 1 Schedule Name
PlantEquipmentOperationSchemes,
CoolSys1 Sec Loop Operation, !- Name
PlantEquipmentOperation:CoolingLoad, !- Control Scheme 1 Object Type
CoolSys1 Sec Operation Scheme, !- Control Scheme 1 Name
PlantOnSched; !- Control Scheme 1 Schedule Name
PlantEquipmentOperationSchemes,
Plant Loop Operation, !- Name
PlantEquipmentOperation:ComponentSetpoint, !- Control Scheme 1 Object Type
WSHPPlant Operation Scheme, !- Control Scheme 1 Name
Always_On; !- Control Scheme 1 Schedule Name
!- =========== ALL OBJECTS IN CLASS: CONDENSER OPERATION SCHEMES ===========
CondenserEquipmentOperationSchemes,
TowerWaterSys Loop Operation Scheme List, !- Name
PlantEquipmentOperation:CoolingLoad, !- Control Scheme 1 Object Type
TowerWaterSys Operation Scheme, !- Control Scheme 1 Name
PlantOnSched; !- Control Scheme 1 Schedule Name
!- =========== ALL OBJECTS IN CLASS: COOLING LOAD RANGE BASED OPERATION ===========
PlantEquipmentOperation:CoolingLoad,
CoolSys1 Operation Scheme, !- Name
0.0, !- Load Range 1 Lower Limit {W}
1302254.38, !- Load Range 1 Upper Limit {W}
CoolSys1 Equipment List 1, !- Range 1 Equipment List Name
1302254.38, !- Load Range 2 Lower Limit {W}
100000000000000, !- Load Range 2 Upper Limit {W}
CoolSys1 Equipment List 2; !- Range 2 Equipment List Name
PlantEquipmentOperation:CoolingLoad,
CoolSys1 Sec Operation Scheme, !- Name
0, !- Load Range 1 Lower Limit {W}
1302254.38, !- Load Range 1 Upper Limit {W}
CoolSys1 HeatExchanger; !- Range 1 Equipment List Name
PlantEquipmentOperation:CoolingLoad,
TowerWaterSys Operation Scheme, !- Name
0.0, !- Load Range 1 Lower Limit {W}
1302254.38, !- Load Range 1 Upper Limit {W}
TowerWaterSys Equipment List 1, !- Range 1 Equipment List Name
1302254.38, !- Load Range 2 Lower Limit {W}
100000000000000, !- Load Range 2 Upper Limit {W}
TowerWaterSys Equipment List 2; !- Range 2 Equipment List Name
!- =========== ALL OBJECTS IN CLASS: HEATING LOAD RANGE BASED OPERATION ===========
PlantEquipmentOperation:HeatingLoad,
SHWSys1 Operation Scheme,!- Name
0.0, !- Load Range 1 Lower Limit {W}
1000000000000000, !- Load Range 1 Upper Limit {W}
SHWSys1 Equipment List; !- Range 1 Equipment List Name
PlantEquipmentOperation:HeatingLoad,
HeatSys1 Operation Scheme, !- Name
0.0, !- Load Range 1 Lower Limit {W}
1000000000000000, !- Load Range 1 Upper Limit {W}
HeatSys1 Equipment List; !- Range 1 Equipment List Name
!- =========== ALL OBJECTS IN CLASS: PLANTEQUIPMENTOPERATION:COMPONENTSETPOINT ===========
PlantEquipmentOperation:ComponentSetpoint,
WSHPPlant Operation Scheme, !- Name
FluidCooler:TwoSpeed, !- Equipment 1 Object Type
Central Tower, !- Equipment 1 Name
Central Tower Inlet Node,!- Demand Calculation 1 Node Name
Plant Supply Outlet Node,!- Setpoint 1 Node Name
autosize, !- Component 1 Flow Rate {m3/s}
Cooling, !- Operation 1 Type
Boiler:HotWater, !- Equipment 2 Object Type
Dummy Boiler, !- Equipment 2 Name
Dummy Boiler Inlet Node, !- Demand Calculation 2 Node Name
Plant Supply Outlet Node,!- Setpoint 2 Node Name
autosize, !- Component 2 Flow Rate {m3/s}
Heating; !- Operation 2 Type
!- =========== ALL OBJECTS IN CLASS: PLANT EQUIPMENT LIST ===========
PlantEquipmentList,
SHWSys1 Equipment List, !- Name
WaterHeater:Mixed, !- Equipment 1 Object Type
SHWSys1 Water Heater; !- Equipment 1 Name
PlantEquipmentList,
HeatSys1 Equipment List, !- Name
Boiler:HotWater, !- Equipment 1 Object Type
HeatSys1 Boiler; !- Equipment 1 Name
PlantEquipmentList,
CoolSys1 Equipment List 1, !- Name
Chiller:Electric:ReformulatedEIR, !- Equipment 1 Object Type
CoolSys1 Chiller1; !- Equipment 1 Name
PlantEquipmentList,
CoolSys1 Equipment List 2, !- Name
Chiller:Electric:ReformulatedEIR, !- Equipment 1 Object Type
CoolSys1 Chiller1, !- Equipment 1 Name
Chiller:Electric:ReformulatedEIR, !- Equipment 2 Object Type
CoolSys1 Chiller2; !- Equipment 2 Name
PlantEquipmentList,
CoolSys1 HeatExchanger, !- Name
HeatExchanger:FluidToFluid, !- Equipment 1 Object Type
Bypass Heat exchanger; !- Equipment 1 Name
!- =========== ALL OBJECTS IN CLASS: CONDENSER EQUIPMENT LIST ===========
CondenserEquipmentList,
TowerWaterSys Equipment List 1, !- Name
CoolingTower:VariableSpeed, !- Equipment 1 Object Type
TowerWaterSys CoolTower 1; !- Equipment 1 Name
CondenserEquipmentList,
TowerWaterSys Equipment List 2, !- Name
CoolingTower:VariableSpeed, !- Equipment 1 Object Type
TowerWaterSys CoolTower 1, !- Equipment 1 Name
CoolingTower:VariableSpeed, !- Equipment 2 Object Type
TowerWaterSys CoolTower 2; !- Equipment 2 Name
!- =========== ALL OBJECTS IN CLASS: SPLITTER ===========
Connector:Splitter,
SHWSys1 Supply Splitter, !- Name
SHWSys1 Supply Inlet Branch, !- Inlet Branch Name
SHWSys1 Supply Equipment Branch, !- Outlet Branch 1 Name
SHWSys1 Supply Equipment Bypass Branch; !- Outlet Branch 2 Name
Connector:Splitter,
SHWSys1 Demand Splitter, !- Name
SHWSys1 Demand Inlet Branch, !- Inlet Branch Name
SHWSys1 Demand Load Branch 1, !- Outlet Branch 1 Name
SHWSys1 Demand Load Branch 2, !- Outlet Branch 2 Name
SHWSys1 Demand Load Branch 3, !- Outlet Branch 3 Name
SHWSys1 Demand Bypass Branch; !- Outlet Branch 4 Name
Connector:Splitter,
HeatSys1 Supply Splitter,!- Name
HeatSys1 Supply Inlet Branch, !- Inlet Branch Name
HeatSys1 Supply Equipment Branch, !- Outlet Branch 1 Name
HeatSys1 Supply Equipment Bypass Branch; !- Outlet Branch 2 Name
Connector:Splitter,
HeatSys1 Demand Splitter,!- Name
HeatSys1 Demand Inlet Branch, !- Inlet Branch Name
HeatSys1 Demand Load Branch 1, !- Outlet Branch 1 Name
HeatSys1 Demand Load Branch 2, !- Outlet Branch 2 Name
HeatSys1 Demand Load Branch 3, !- Outlet Branch 3 Name
HeatSys1 Demand Load Branch 4, !- Outlet Branch 4 Name
HeatSys1 Demand Load Branch 5, !- Outlet Branch 5 Name
HeatSys1 Demand Load Branch 6, !- Outlet Branch 6 Name
HeatSys1 Demand Load Branch 7, !- Outlet Branch 7 Name
HeatSys1 Demand Load Branch 8, !- Outlet Branch 8 Name
HeatSys1 Demand Load Branch 9, !- Outlet Branch 9 Name
HeatSys1 Demand Load Branch 10, !- Outlet Branch 10 Name
HeatSys1 Demand Load Branch 11, !- Outlet Branch 11 Name
HeatSys1 Demand Load Branch 12, !- Outlet Branch 12 Name
HeatSys1 Demand Load Branch 13, !- Outlet Branch 13 Name
HeatSys1 Demand Load Branch 14, !- Outlet Branch 14 Name
HeatSys1 Demand Load Branch 15, !- Outlet Branch 15 Name
HeatSys1 Demand Load Branch 17, !- Outlet Branch 16 Name
HeatSys1 Demand Load Branch 18, !- Outlet Branch 17 Name
HeatSys1 Demand Load Branch 19, !- Outlet Branch 18 Name
HeatSys1 Demand Load Branch 20, !- Outlet Branch 19 Name
HeatSys1 Demand Load Branch 21, !- Outlet Branch 20 Name
HeatSys1 Demand Bypass Branch; !- Outlet Branch 21 Name
Connector:Splitter,
CoolSys1 Supply Supply Side Splitter,!- Name
CoolSys1 Supply Inlet Branch, !- Inlet Branch Name
CoolSys1 Supply Equipment Branch 1, !- Outlet Branch 1 Name
CoolSys1 Supply Equipment Branch 2, !- Outlet Branch 2 Name
CoolSys1 Supply Equipment Bypass Branch; !- Outlet Branch 3 Name
Connector:Splitter,
CoolSys1 Demand Demand Side Splitter,!- Name
CoolSys1 Demand Inlet Branch, !- Inlet Branch Name
CoolSys1 Demand Load Branch 1, !- Outlet Branch 1 Name
CoolSys1 Demand Load Branch 2, !- Outlet Branch 2 Name
CoolSys1 Demand Load Branch 3, !- Outlet Branch 3 Name
CoolSys1 Demand Load Branch 4; !- Outlet Branch 4 Name
Connector:Splitter,
TowerWaterSys Supply Splitter, !- Name
TowerWaterSys Supply Inlet Branch, !- Inlet Branch Name
TowerWaterSys Supply Equipment Branch 1, !- Outlet Branch 1 Name
TowerWaterSys Supply Equipment Branch 2, !- Outlet Branch 2 Name
TowerWaterSys Supply Equipment Bypass Branch; !- Outlet Branch 3 Name
Connector:Splitter,
TowerWaterSys Demand Splitter, !- Name
TowerWaterSys Demand Inlet Branch, !- Inlet Branch Name
TowerWaterSys Demand Load Branch 1, !- Outlet Branch 1 Name
TowerWaterSys Demand Load Branch 2, !- Outlet Branch 2 Name
TowerWaterSys Demand Bypass Branch; !- Outlet Branch 3 Name
Connector:Splitter,
CoolSys1 Supply Demand Side Splitter, !- Name
CoolSys1 Supply Demand Side Inlet Branch, !- Inlet Branch Name
CoolSys1 Heat Exchanger Supply Branch, !- Outlet Branch 1 Name
CoolSys1 Supply Side Bypass; !- Outlet Branch 2 Name
Connector:Splitter,
CoolSys1 Demand Supply Side Splitter, !- Name
CoolSys1 Demand Supply Side Inlet Branch, !- Inlet Branch Name
CoolSys1 Heat Exchanger Demand Branch, !- Outlet Branch 1 Name
CoolSys1 Demand Side Bypass; !- Outlet Branch 2 Name
Connector:Splitter,
Plant Supply Splitter, !- Name
Plant Supply Inlet Branch, !- Inlet Branch Name
Plant Supply Tower Branch, !- Outlet Branch 1 Name
Dummy Boiler Branch, !- Outlet Branch 2 Name
Plant Supply Bypass Branch; !- Outlet Branch 3 Name
Connector:Splitter,
Plant Demand Splitter, !- Name
Plant Demand Inlet Branch, !- Inlet Branch Name
WLHP Cooling Plant Branch AirLoop DataCenter Basement, !- Outlet Branch 1 Name
WLHP Heating Plant Branch AirLoop DataCenter Basement, !- Outlet Branch 2 Name
WLHP Cooling Plant Branch AirLoop DataCenter bot, !- Outlet Branch 3 Name
WLHP Heating Plant Branch AirLoop DataCenter bot, !- Outlet Branch 4 Name
WLHP Cooling Plant Branch AirLoop DataCenter mid, !- Outlet Branch 5 Name
WLHP Heating Plant Branch AirLoop DataCenter mid, !- Outlet Branch 6 Name
WLHP Cooling Plant Branch AirLoop DataCenter top, !- Outlet Branch 7 Name
WLHP Heating Plant Branch AirLoop DataCenter top, !- Outlet Branch 8 Name
Plant Demand Bypass Branch; !- Outlet Branch 9 Name
!- =========== ALL OBJECTS IN CLASS: MIXER ===========
Connector:Mixer,
SHWSys1 Supply Mixer, !- Name
SHWSys1 Supply Outlet Branch, !- Outlet Branch Name
SHWSys1 Supply Equipment Branch, !- Inlet Branch 1 Name
SHWSys1 Supply Equipment Bypass Branch; !- Inlet Branch 2 Name
Connector:Mixer,
SHWSys1 Demand Mixer, !- Name
SHWSys1 Demand Outlet Branch, !- Outlet Branch Name
SHWSys1 Demand Load Branch 1, !- Inlet Branch 1 Name
SHWSys1 Demand Load Branch 2, !- Inlet Branch 2 Name
SHWSys1 Demand Load Branch 3, !- Inlet Branch 3 Name
SHWSys1 Demand Bypass Branch; !- Inlet Branch 4 Name
Connector:Mixer,
HeatSys1 Supply Mixer, !- Name
HeatSys1 Supply Outlet Branch, !- Outlet Branch Name
HeatSys1 Supply Equipment Branch, !- Inlet Branch 1 Name
HeatSys1 Supply Equipment Bypass Branch; !- Inlet Branch 2 Name
Connector:Mixer,
HeatSys1 Demand Mixer, !- Name
HeatSys1 Demand Outlet Branch, !- Outlet Branch Name
HeatSys1 Demand Load Branch 1, !- Inlet Branch 1 Name
HeatSys1 Demand Load Branch 2, !- Inlet Branch 2 Name
HeatSys1 Demand Load Branch 3, !- Inlet Branch 3 Name
HeatSys1 Demand Load Branch 4, !- Inlet Branch 4 Name
HeatSys1 Demand Load Branch 5, !- Inlet Branch 5 Name
HeatSys1 Demand Load Branch 6, !- Inlet Branch 6 Name
HeatSys1 Demand Load Branch 7, !- Inlet Branch 7 Name
HeatSys1 Demand Load Branch 8, !- Inlet Branch 8 Name
HeatSys1 Demand Load Branch 9, !- Inlet Branch 9 Name
HeatSys1 Demand Load Branch 10, !- Inlet Branch 10 Name
HeatSys1 Demand Load Branch 11, !- Inlet Branch 11 Name
HeatSys1 Demand Load Branch 12, !- Inlet Branch 12 Name
HeatSys1 Demand Load Branch 13, !- Inlet Branch 13 Name
HeatSys1 Demand Load Branch 14, !- Inlet Branch 14 Name
HeatSys1 Demand Load Branch 15, !- Inlet Branch 15 Name
HeatSys1 Demand Load Branch 17, !- Inlet Branch 16 Name
HeatSys1 Demand Load Branch 18, !- Inlet Branch 17 Name
HeatSys1 Demand Load Branch 19, !- Inlet Branch 18 Name
HeatSys1 Demand Load Branch 20, !- Inlet Branch 19 Name
HeatSys1 Demand Load Branch 21, !- Inlet Branch 20 Name
HeatSys1 Demand Bypass Branch; !- Inlet Branch 21 Name
Connector:Mixer,
CoolSys1 Supply Supply Side Mixer, !- Name
CoolSys1 Supply Outlet Branch, !- Outlet Branch Name
CoolSys1 Supply Equipment Branch 1, !- Inlet Branch 1 Name
CoolSys1 Supply Equipment Branch 2, !- Inlet Branch 2 Name
CoolSys1 Supply Equipment Bypass Branch; !- Inlet Branch 3 Name
Connector:Mixer,
CoolSys1 Demand Demand Side Mixer, !- Name
CoolSys1 Demand Outlet Branch, !- Outlet Branch Name
CoolSys1 Demand Load Branch 1, !- Inlet Branch 1 Name
CoolSys1 Demand Load Branch 2, !- Inlet Branch 2 Name
CoolSys1 Demand Load Branch 3, !- Inlet Branch 3 Name
CoolSys1 Demand Load Branch 4; !- Inlet Branch 4 Name
Connector:Mixer,
TowerWaterSys Supply Mixer, !- Name
TowerWaterSys Supply Outlet Branch, !- Outlet Branch Name
TowerWaterSys Supply Equipment Branch 1, !- Inlet Branch 1 Name
TowerWaterSys Supply Equipment Branch 2, !- Inlet Branch 2 Name
TowerWaterSys Supply Equipment Bypass Branch; !- Inlet Branch 3 Name
Connector:Mixer,
TowerWaterSys Demand Mixer, !- Name
TowerWaterSys Demand Outlet Branch, !- Outlet Branch Name
TowerWaterSys Demand Load Branch 1, !- Inlet Branch 1 Name
TowerWaterSys Demand Load Branch 2, !- Inlet Branch 2 Name
TowerWaterSys Demand Bypass Branch; !- Inlet Branch 3 Name
Connector:Mixer,
CoolSys1 Supply Demand Side Mixer, !- Name
CoolSys1 Supply Demand Side Outlet Branch, !- Outlet Branch Name
CoolSys1 Heat Exchanger Supply Branch, !- Inlet Branch 1 Name
CoolSys1 Supply Side Bypass; !- Inlet Branch 2 Name
Connector:Mixer,
CoolSys1 Demand Supply Side Mixer, !- Name
CoolSys1 Demand Supply Side Outlet Branch, !- Outlet Branch Name
CoolSys1 Heat Exchanger Demand Branch, !- Inlet Branch 1 Name
CoolSys1 Demand Side Bypass; !- Inlet Branch 2 Name
Connector:Mixer,
Plant Supply Mixer, !- Name
Plant Supply Outlet Branch, !- Outlet Branch Name
Plant Supply Tower Branch, !- Inlet Branch 1 Name
Dummy Boiler Branch, !- Inlet Branch 2 Name
Plant Supply Bypass Branch; !- Inlet Branch 3 Name
Connector:Mixer,
Plant Demand Mixer, !- Name
Plant Demand Outlet Branch, !- Outlet Branch Name
WLHP Cooling Plant Branch AirLoop DataCenter Basement, !- Inlet Branch 1 Name
WLHP Heating Plant Branch AirLoop DataCenter Basement, !- Inlet Branch 2 Name
WLHP Cooling Plant Branch AirLoop DataCenter bot, !- Inlet Branch 3 Name
WLHP Heating Plant Branch AirLoop DataCenter bot, !- Inlet Branch 4 Name
WLHP Cooling Plant Branch AirLoop DataCenter mid, !- Inlet Branch 5 Name
WLHP Heating Plant Branch AirLoop DataCenter mid, !- Inlet Branch 6 Name
WLHP Cooling Plant Branch AirLoop DataCenter top, !- Inlet Branch 7 Name
WLHP Heating Plant Branch AirLoop DataCenter top, !- Inlet Branch 8 Name
Plant Demand Bypass Branch; !- Inlet Branch 9 Name
!- =========== ALL OBJECTS IN CLASS: AIR PRIMARY LOOP ===========
AirLoopHVAC,
CAV_bas, !- Name
CAV_bas_Controllers, !- Controller List Name
CAV_bas Availability Manager List, !- Availability Manager List Name
AUTOSIZE, !- Design Supply Air Flow Rate {m3/s}
CAV_bas Air Loop Branches, !- Branch List Name
, !- Connector List Name
CAV_bas Supply Equipment Inlet Node, !- Supply Side Inlet Node Name
CAV_bas Zone Equipment Outlet Node, !- Demand Side Outlet Node Name
CAV_bas Zone Equipment Inlet Node, !- Demand Side Inlet Node Names
CAV_bas Supply Equipment Outlet Node; !- Supply Side Outlet Node Names
AirLoopHVAC,
VAV_bot WITH REHEAT, !- Name
VAV_bot WITH REHEAT_Controllers, !- Controller List Name
VAV_bot WITH REHEAT Availability Manager List, !- Availability Manager List Name
AUTOSIZE, !- Design Supply Air Flow Rate {m3/s}
VAV_bot WITH REHEAT Air Loop Branches, !- Branch List Name
, !- Connector List Name
VAV_bot WITH REHEAT Supply Equipment Inlet Node, !- Supply Side Inlet Node Name
VAV_bot WITH REHEAT Zone Equipment Outlet Node, !- Demand Side Outlet Node Name
VAV_bot WITH REHEAT Zone Equipment Inlet Node, !- Demand Side Inlet Node Names
VAV_bot WITH REHEAT Supply Equipment Outlet Node; !- Supply Side Outlet Node Names
AirLoopHVAC,
VAV_mid WITH REHEAT, !- Name
VAV_mid WITH REHEAT_Controllers, !- Controller List Name
VAV_mid WITH REHEAT Availability Manager List, !- Availability Manager List Name
AUTOSIZE, !- Design Supply Air Flow Rate {m3/s}
VAV_mid WITH REHEAT Air Loop Branches, !- Branch List Name
, !- Connector List Name
VAV_mid WITH REHEAT Supply Equipment Inlet Node, !- Supply Side Inlet Node Name
VAV_mid WITH REHEAT Zone Equipment Outlet Node, !- Demand Side Outlet Node Name
VAV_mid WITH REHEAT Zone Equipment Inlet Node, !- Demand Side Inlet Node Names
VAV_mid WITH REHEAT Supply Equipment Outlet Node; !- Supply Side Outlet Node Names
AirLoopHVAC,
VAV_top WITH REHEAT, !- Name
VAV_top WITH REHEAT_Controllers, !- Controller List Name
VAV_top WITH REHEAT Availability Manager List, !- Availability Manager List Name
AUTOSIZE, !- Design Supply Air Flow Rate {m3/s}
VAV_top WITH REHEAT Air Loop Branches, !- Branch List Name
, !- Connector List Name
VAV_top WITH REHEAT Supply Equipment Inlet Node, !- Supply Side Inlet Node Name
VAV_top WITH REHEAT Zone Equipment Outlet Node, !- Demand Side Outlet Node Name
VAV_top WITH REHEAT Zone Equipment Inlet Node, !- Demand Side Inlet Node Names
VAV_top WITH REHEAT Supply Equipment Outlet Node; !- Supply Side Outlet Node Names
AirLoopHVAC,
AirLoop DataCenter Basement, !- Name
DataCenter_bas_HeatC_Controllers, !- Controller List Name
AirLoop DataCenter Basement Availability Manager, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
AirLoop DataCenter Basement Branches, !- Branch List Name
, !- Connector List Name
AirLoop DataCenter Basement Return Air Inlet, !- Supply Side Inlet Node Name
ZoneMixer DataCenter Basement Return Air Outlet, !- Demand Side Outlet Node Name
ZoneSplitter DataCenter Basement Supply Air Inlet, !- Demand Side Inlet Node Names
AirLoop DataCenter Basement Supply Air Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
AirLoop DataCenter bot, !- Name
, !- Controller List Name
AirLoop DataCenter bot Availability Manager, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
AirLoop DataCenter bot Branches, !- Branch List Name
, !- Connector List Name
AirLoop DataCenter bot Return Air Inlet, !- Supply Side Inlet Node Name
ZoneMixer DataCenter bot Return Air Outlet, !- Demand Side Outlet Node Name
ZoneSplitter DataCenter bot Supply Air Inlet, !- Demand Side Inlet Node Names
AirLoop DataCenter bot Supply Air Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
AirLoop DataCenter mid, !- Name
, !- Controller List Name
AirLoop DataCenter mid Availability Manager, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
AirLoop DataCenter mid Branches, !- Branch List Name
, !- Connector List Name
AirLoop DataCenter mid Return Air Inlet, !- Supply Side Inlet Node Name
ZoneMixer DataCenter mid Return Air Outlet, !- Demand Side Outlet Node Name
ZoneSplitter DataCenter mid Supply Air Inlet, !- Demand Side Inlet Node Names
AirLoop DataCenter mid Supply Air Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
AirLoop DataCenter top, !- Name
, !- Controller List Name
AirLoop DataCenter top Availability Manager, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
AirLoop DataCenter top Branches, !- Branch List Name
, !- Connector List Name
AirLoop DataCenter top Return Air Inlet, !- Supply Side Inlet Node Name
ZoneMixer DataCenter top Return Air Outlet, !- Demand Side Outlet Node Name
ZoneSplitter DataCenter top Supply Air Inlet, !- Demand Side Inlet Node Names
AirLoop DataCenter top Supply Air Outlet; !- Supply Side Outlet Node Names
!- =========== ALL OBJECTS IN CLASS: CONTROLLER LIST ===========
AirLoopHVAC:ControllerList,
DataCenter_bas_HeatC_Controllers, !- Name
Controller:WaterCoil, !- Controller 1 Object Type
DataCenter_bas_HeatC_Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
CAV_bas_Controllers, !- Name
Controller:WaterCoil, !- Controller 1 Object Type
CAV_bas_CoolC_Controller,!- Controller 1 Name
Controller:WaterCoil, !- Controller 2 Object Type
CAV_bas_HeatC_Controller;!- Controller 2 Name
AirLoopHVAC:ControllerList,
VAV_bot WITH REHEAT_Controllers, !- Name
Controller:WaterCoil, !- Controller 1 Object Type
VAV_bot WITH REHEAT_CoolC_Controller, !- Controller 1 Name
Controller:WaterCoil, !- Controller 2 Object Type
VAV_bot WITH REHEAT_HeatC_Controller; !- Controller 2 Name
AirLoopHVAC:ControllerList,
VAV_mid WITH REHEAT_Controllers, !- Name
Controller:WaterCoil, !- Controller 1 Object Type
VAV_mid WITH REHEAT_CoolC_Controller, !- Controller 1 Name
Controller:WaterCoil, !- Controller 2 Object Type
VAV_mid WITH REHEAT_HeatC_Controller; !- Controller 2 Name
AirLoopHVAC:ControllerList,
VAV_top WITH REHEAT_Controllers, !- Name
Controller:WaterCoil, !- Controller 1 Object Type
VAV_top WITH REHEAT_CoolC_Controller, !- Controller 1 Name
Controller:WaterCoil, !- Controller 2 Object Type
VAV_top WITH REHEAT_HeatC_Controller; !- Controller 2 Name
AirLoopHVAC:ControllerList,
CAV_bas_OA_Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
CAV_bas_OA_Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
VAV_bot WITH REHEAT_OA_Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
VAV_bot WITH REHEAT_OA_Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
VAV_mid WITH REHEAT_OA_Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
VAV_mid WITH REHEAT_OA_Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
VAV_top WITH REHEAT_OA_Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
VAV_top WITH REHEAT_OA_Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
AirLoop DataCenter Basement OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
AirLoop DataCenter Basement OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
AirLoop DataCenter bot OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
AirLoop DataCenter bot OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
AirLoop DataCenter mid OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
AirLoop DataCenter mid OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
AirLoop DataCenter top OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
AirLoop DataCenter top OA Controller; !- Controller 1 Name
!- =========== ALL OBJECTS IN CLASS: AIR LOOP EQUIPMENT LIST ===========
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
CAV_bas_OA_Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
CAV_bas_OAMixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
VAV_bot WITH REHEAT_OA_Equipment, !- Name
HeatExchanger:AirToAir:SensibleAndLatent, !- Component 1 Object Type
VAV_bot WITH REHEAT OA Heat Recovery, !- Component 1 Name
OutdoorAir:Mixer, !- Component 2 Object Type
VAV_bot WITH REHEAT_OAMixing Box; !- Component 2 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
VAV_mid WITH REHEAT_OA_Equipment, !- Name
HeatExchanger:AirToAir:SensibleAndLatent, !- Component 1 Object Type
VAV_mid WITH REHEAT OA Heat Recovery, !- Component 1 Name
OutdoorAir:Mixer, !- Component 2 Object Type
VAV_mid WITH REHEAT_OAMixing Box; !- Component 2 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
VAV_top WITH REHEAT_OA_Equipment, !- Name
HeatExchanger:AirToAir:SensibleAndLatent, !- Component 1 Object Type
VAV_top WITH REHEAT OA Heat Recovery, !- Component 1 Name
OutdoorAir:Mixer, !- Component 2 Object Type
VAV_top WITH REHEAT_OAMixing Box; !- Component 2 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
AirLoop DataCenter Basement OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
DataCenter Basement OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
AirLoop DataCenter bot OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
DataCenter bot OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
AirLoop DataCenter mid OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
DataCenter mid OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
AirLoop DataCenter top OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
DataCenter top OA Mixing Box; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR SYSTEM ===========
AirLoopHVAC:OutdoorAirSystem,
CAV_bas_OA, !- Name
CAV_bas_OA_Controllers, !- Controller List Name
CAV_bas_OA_Equipment, !- Outdoor Air Equipment List Name
CAV_bas Availability Manager List; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
VAV_bot WITH REHEAT_OA, !- Name
VAV_bot WITH REHEAT_OA_Controllers, !- Controller List Name
VAV_bot WITH REHEAT_OA_Equipment, !- Outdoor Air Equipment List Name
VAV_bot WITH REHEAT Availability Manager List; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
VAV_mid WITH REHEAT_OA, !- Name
VAV_mid WITH REHEAT_OA_Controllers, !- Controller List Name
VAV_mid WITH REHEAT_OA_Equipment, !- Outdoor Air Equipment List Name
VAV_mid WITH REHEAT Availability Manager List; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
VAV_top WITH REHEAT_OA, !- Name
VAV_top WITH REHEAT_OA_Controllers, !- Controller List Name
VAV_top WITH REHEAT_OA_Equipment, !- Outdoor Air Equipment List Name
VAV_top WITH REHEAT Availability Manager List; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
AirLoop DataCenter Basement OA System, !- Name
AirLoop DataCenter Basement OA System Controllers, !- Controller List Name
AirLoop DataCenter Basement OA System Equipment, !- Outdoor Air Equipment List Name
AirLoop DataCenter Basement Availability Manager; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
AirLoop DataCenter bot OA System, !- Name
AirLoop DataCenter bot OA System Controllers, !- Controller List Name
AirLoop DataCenter bot OA System Equipment, !- Outdoor Air Equipment List Name
AirLoop DataCenter bot Availability Manager; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
AirLoop DataCenter mid OA System, !- Name
AirLoop DataCenter mid OA System Controllers, !- Controller List Name
AirLoop DataCenter mid OA System Equipment, !- Outdoor Air Equipment List Name
AirLoop DataCenter mid Availability Manager; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
AirLoop DataCenter top OA System, !- Name
AirLoop DataCenter top OA System Controllers, !- Controller List Name
AirLoop DataCenter top OA System Equipment, !- Outdoor Air Equipment List Name
AirLoop DataCenter top Availability Manager; !- Availability Manager List Name
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR INLET NODE LIST ===========
OutdoorAir:NodeList,
CAV_bas_OANode List; !- Node or NodeList Name 1
OutdoorAir:NodeList,
VAV_bot WITH REHEAT_OANode List; !- Node or NodeList Name 1
OutdoorAir:NodeList,
VAV_mid WITH REHEAT_OANode List; !- Node or NodeList Name 1
OutdoorAir:NodeList,
VAV_top WITH REHEAT_OANode List; !- Node or NodeList Name 1
OutdoorAir:Node,
DataCenter Basement Outside Air Inlet; !- Name
OutdoorAir:Node,
DataCenter bot Outside Air Inlet; !- Name
OutdoorAir:Node,
DataCenter mid Outside Air Inlet; !- Name
OutdoorAir:Node,
DataCenter top Outside Air Inlet; !- Name
OutdoorAir:Node,
Common OSA Inlet Node, !- Name
-1; !- Height Above Ground {m}
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR MIXER ===========
OutdoorAir:Mixer,
CAV_bas_OAMixing Box, !- Name
CAV_bas_OA-CAV_CoolCNode, !- Mixed Air Node Name
CAV_bas_OAInlet Node, !- Outdoor Air Stream Node Name !- Outdoor Air Stream Node Name
CAV_bas_OARelief Node, !- Relief Air Stream Node Name
CAV_bas Supply Equipment Inlet Node; !- Return Air Stream Node Name
OutdoorAir:Mixer,
VAV_bot WITH REHEAT_OAMixing Box, !- Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_bot WITH REHEAT Heat Recovery Outlet Node, !- Outdoor Air Stream Node Name !- Outdoor Air Stream Node Name
VAV_bot WITH REHEAT_OARelief Node, !- Relief Air Stream Node Name
VAV_bot WITH REHEAT Supply Equipment Inlet Node; !- Return Air Stream Node Name
OutdoorAir:Mixer,
VAV_mid WITH REHEAT_OAMixing Box, !- Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_mid WITH REHEAT Heat Recovery Outlet Node, !- Outdoor Air Stream Node Name !- Outdoor Air Stream Node Name
VAV_mid WITH REHEAT_OARelief Node, !- Relief Air Stream Node Name
VAV_mid WITH REHEAT Supply Equipment Inlet Node; !- Return Air Stream Node Name
OutdoorAir:Mixer,
VAV_top WITH REHEAT_OAMixing Box, !- Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_top WITH REHEAT Heat Recovery Outlet Node, !- Outdoor Air Stream Node Name !- Outdoor Air Stream Node Name
VAV_top WITH REHEAT_OARelief Node, !- Relief Air Stream Node Name
VAV_top WITH REHEAT Supply Equipment Inlet Node; !- Return Air Stream Node Name
OutdoorAir:Mixer,
DataCenter Basement OA Mixing Box, !- Name
DataCenter Basement Mixed Air Outlet, !- Mixed Air Node Name
DataCenter Basement Outside Air Inlet, !- Outdoor Air Stream Node Name
DataCenter Basement Relief Air Outlet, !- Relief Air Stream Node Name
AirLoop DataCenter Basement Return Air Inlet; !- Return Air Stream Node Name
OutdoorAir:Mixer,
DataCenter bot OA Mixing Box, !- Name
DataCenter bot Mixed Air Outlet, !- Mixed Air Node Name
DataCenter bot Outside Air Inlet, !- Outdoor Air Stream Node Name
DataCenter bot Relief Air Outlet, !- Relief Air Stream Node Name
AirLoop DataCenter bot Return Air Inlet; !- Return Air Stream Node Name
OutdoorAir:Mixer,
DataCenter mid OA Mixing Box, !- Name
DataCenter mid Mixed Air Outlet, !- Mixed Air Node Name
DataCenter mid Outside Air Inlet, !- Outdoor Air Stream Node Name
DataCenter mid Relief Air Outlet, !- Relief Air Stream Node Name
AirLoop DataCenter mid Return Air Inlet; !- Return Air Stream Node Name
OutdoorAir:Mixer,
DataCenter top OA Mixing Box, !- Name
DataCenter top Mixed Air Outlet, !- Mixed Air Node Name
DataCenter top Outside Air Inlet, !- Outdoor Air Stream Node Name
DataCenter top Relief Air Outlet, !- Relief Air Stream Node Name
AirLoop DataCenter top Return Air Inlet; !- Return Air Stream Node Name
!- =========== ALL OBJECTS IN CLASS: AVAILABILITYMANAGER:SCHEDULED ===========
AvailabilityManager:Scheduled,
AirLoop DataCenter Basement Availability, !- Name
Always_On; !- Schedule Name
AvailabilityManager:Scheduled,
AirLoop DataCenter bot Availability, !- Name
Always_On; !- Schedule Name
AvailabilityManager:Scheduled,
AirLoop DataCenter mid Availability, !- Name
Always_On; !- Schedule Name
AvailabilityManager:Scheduled,
AirLoop DataCenter top Availability, !- Name
Always_On; !- Schedule Name
!- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER LIST ===========
AvailabilityManagerAssignmentList,
CAV_bas Availability Manager List, !- Name
AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type
CAV_bas Availability Manager; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
VAV_bot WITH REHEAT Availability Manager List, !- Name
AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type
VAV_bot WITH REHEAT Availability Manager; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
VAV_mid WITH REHEAT Availability Manager List, !- Name
AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type
VAV_mid WITH REHEAT Availability Manager; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
VAV_top WITH REHEAT Availability Manager List, !- Name
AvailabilityManager:NightCycle, !- Availability Manager 1 Object Type
VAV_top WITH REHEAT Availability Manager; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
AirLoop DataCenter Basement Availability Manager, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
AirLoop DataCenter Basement Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
AirLoop DataCenter bot Availability Manager, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
AirLoop DataCenter bot Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
AirLoop DataCenter mid Availability Manager, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
AirLoop DataCenter mid Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
AirLoop DataCenter top Availability Manager, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
AirLoop DataCenter top Availability; !- Availability Manager 1 Name
!- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER:NIGHT CYCLE ===========
AvailabilityManager:NightCycle,
CAV_bas Availability Manager, !- Name
Always_On, !- Applicability Schedule Name
HVACOperationSchd, !- Fan Schedule Name
CycleOnAny, !- Control Type
1.0, !- Thermostat Tolerance {deltaC}
FixedRunTime, !- Cycling Run Time Control Type
1800; !- Cycling Run Time {s}
AvailabilityManager:NightCycle,
VAV_bot WITH REHEAT Availability Manager, !- Name
Always_On, !- Applicability Schedule Name
HVACOperationSchd, !- Fan Schedule Name
CycleOnAny, !- Control Type
1.0, !- Thermostat Tolerance {deltaC}
FixedRunTime, !- Cycling Run Time Control Type
1800; !- Cycling Run Time {s}
AvailabilityManager:NightCycle,
VAV_mid WITH REHEAT Availability Manager, !- Name
Always_On, !- Applicability Schedule Name
HVACOperationSchd, !- Fan Schedule Name
CycleOnAny, !- Control Type
1.0, !- Thermostat Tolerance {deltaC}
FixedRunTime, !- Cycling Run Time Control Type
1800; !- Cycling Run Time {s}
AvailabilityManager:NightCycle,
VAV_top WITH REHEAT Availability Manager, !- Name
Always_On, !- Applicability Schedule Name
HVACOperationSchd, !- Fan Schedule Name
CycleOnAny, !- Control Type
1.0, !- Thermostat Tolerance {deltaC}
FixedRunTime, !- Cycling Run Time Control Type
1800; !- Cycling Run Time {s}
!- =========== ALL OBJECTS IN CLASS: SETPOINTMANAGER:SINGLEZONE:HEATING & COOLING ===========
SetpointManager:SingleZone:Heating,
CAV_bas SupAirTemp Manager - Htg, !- Name
Temperature, !- Control Variable
10, !- Minimum Supply Air Temperature {C}
50, !- Maximum Supply Air Temperature {C}
Basement, !- Control Zone Name
Basement Air Node, !- Zone Node Name
Basement Direct Air Inlet Node Name, !- Zone Inlet Node Name
CAV_bas Supply Equipment Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
DataCenter Basement SupAirTemp Manager - Htg, !- Name
Temperature, !- Control Variable
10, !- Minimum Supply Air Temperature {C}
50, !- Maximum Supply Air Temperature {C}
DataCenter_basement_ZN_6,!- Control Zone Name
DataCenter Basement Zone Air Node, !- Zone Node Name
DataCenter Basement Supply Inlet, !- Zone Inlet Node Name
AirLoop DataCenter Basement Supply Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
DataCenter_bot_ZN_6 SupAirTemp Manager - Htg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_bot_ZN_6, !- Control Zone Name
DataCenter bot Zone Air Node, !- Zone Node Name
DataCenter bot Supply Inlet, !- Zone Inlet Node Name
AirLoop DataCenter bot Supply Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
DataCenter_mid_ZN_6 SupAirTemp Manager - Htg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_mid_ZN_6, !- Control Zone Name
DataCenter mid Zone Air Node, !- Zone Node Name
DataCenter mid Supply Inlet, !- Zone Inlet Node Name
AirLoop DataCenter mid Supply Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
DataCenter_top_ZN_6 SupAirTemp Manager - Htg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_top_ZN_6, !- Control Zone Name
DataCenter top Zone Air Node, !- Zone Node Name
DataCenter top Supply Inlet, !- Zone Inlet Node Name
AirLoop DataCenter top Supply Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
CAV_bas SupAirTemp Manager - Clg, !- Name
Temperature, !- Control Variable
10, !- Minimum Supply Air Temperature {C}
50, !- Maximum Supply Air Temperature {C}
Basement, !- Control Zone Name
Basement Air Node, !- Zone Node Name
Basement Direct Air Inlet Node Name, !- Zone Inlet Node Name
Basement Inlet Nodes; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
DataCenter Basement SupAirTemp Manager - Clg, !- Name
Temperature, !- Control Variable
10, !- Minimum Supply Air Temperature {C}
50, !- Maximum Supply Air Temperature {C}
DataCenter_basement_ZN_6,!- Control Zone Name
DataCenter Basement Zone Air Node, !- Zone Node Name
DataCenter Basement Supply Inlet, !- Zone Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter Basement; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
DataCenter_bot_ZN_6 SupAirTemp Manager - Clg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_bot_ZN_6, !- Control Zone Name
DataCenter bot Zone Air Node, !- Zone Node Name
DataCenter bot Supply Inlet, !- Zone Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter bot; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
DataCenter_mid_ZN_6 SupAirTemp Manager - Clg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_mid_ZN_6, !- Control Zone Name
DataCenter mid Zone Air Node, !- Zone Node Name
DataCenter mid Supply Inlet, !- Zone Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter mid; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
DataCenter_top_ZN_6 SupAirTemp Manager - Clg, !- Name
Temperature, !- Control Variable
10.0, !- Minimum Supply Air Temperature {C}
50.0, !- Maximum Supply Air Temperature {C}
DataCenter_top_ZN_6, !- Control Zone Name
DataCenter top Zone Air Node, !- Zone Node Name
DataCenter top Supply Inlet, !- Zone Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter top; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:WARMEST ===========
SetpointManager:OutdoorAirReset,
VAV_bot Supply Air Temperature Manager, !- Name
Temperature, !- Control Variable
15.6, !- Setpoint at Outdoor Low Temperature {C}
10, !- Outdoor Low Temperature {C}
12.8, !- Setpoint at Outdoor High Temperature {C}
21.1, !- Outdoor High Temperature {C}
VAV_bot WITH REHEAT Supply Equipment Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:OutdoorAirReset,
VAV_mid Supply Air Temperature Manager, !- Name
Temperature, !- Control Variable
15.6, !- Setpoint at Outdoor Low Temperature {C}
10, !- Outdoor Low Temperature {C}
12.8, !- Setpoint at Outdoor High Temperature {C}
21.1, !- Outdoor High Temperature {C}
VAV_mid WITH REHEAT Supply Equipment Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:OutdoorAirReset,
VAV_top Supply Air Temperature Manager, !- Name
Temperature, !- Control Variable
15.6, !- Setpoint at Outdoor Low Temperature {C}
10, !- Outdoor Low Temperature {C}
12.8, !- Setpoint at Outdoor High Temperature {C}
21.1, !- Outdoor High Temperature {C}
VAV_top WITH REHEAT Supply Equipment Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:Scheduled,
SHWSys1 Loop Setpoint Manager, !- Name
Temperature, !- Control Variable
SHWSys1-Loop-Temp-Schedule, !- Schedule Name
SHWSys1 Supply Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:Scheduled,
HeatSys1 Loop Setpoint Manager, !- Name
Temperature, !- Control Variable
HW-Loop-Temp-Schedule, !- Schedule Name
HeatSys1 Supply Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:Scheduled,
CoolSys1 Loop Setpoint Manager, !- Name
Temperature, !- Control Variable
CW-Loop-Temp-Schedule, !- Schedule Name
CoolSys1 Supply Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:Scheduled,
TowerWaterSystem Loop Setpoint Manager, !- Name
Temperature, !- Control Variable
Tower-Loop-Temp-Schedule,!- Schedule Name
TowerWaterSys Supply Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:Scheduled,
CoolSys1 Loop Plant Demand Inlet Setpoint Manager, !- Name
Temperature, !- Control Variable
CW-Loop-Temp-Schedule, !- Schedule Name
CoolSys1 Demand Inlet Node; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: SETPOINTMANAGER:SCHEDULED:DUALSETPOINT ===========
SetpointManager:Scheduled:DualSetpoint,
Water Loop Setpoint Manager, !- Name
Temperature, !- Control Variable
PLANT LOOP HIGH TEMP SCHEDULE, !- High Setpoint Schedule Name
PLANT LOOP LOW TEMP SCHEDULE, !- Low Setpoint Schedule Name
Plant Supply Outlet Node;!- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: SETPOINTMANAGER:SINGLEZONE:HUMIDITY:MINIMUM ===========
SetpointManager:SingleZone:Humidity:Minimum,
DataCenter_Basement Humidifier HUMRAT setpoint, !- Name
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode, !- Setpoint Node or NodeList Name
DataCenter Basement Zone Air Node; !- Control Zone Air Node Name
!- =========== ALL OBJECTS IN CLASS: SETPOINTMANAGER:MIXEDAIR ===========
SetpointManager:MixedAir,
DataCenter_ExtraElecHeatC Air Temp Manager, !- Name
Temperature, !- Control Variable
AirLoop DataCenter Basement Supply Air Outlet, !- Reference Setpoint Node Name
DataCenter Basement Mixed Air Outlet, !- Fan Inlet Node Name
AirLoop DataCenter Basement Supply Fan Outlet, !- Fan Outlet Node Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:MIXED AIR ===========
SetpointManager:MixedAir,
CAV_bas_CoolC SAT Manager, !- Name
Temperature, !- Control Variable
Basement Inlet Nodes, !- Reference Setpoint Node Name
CAV_bas_HeatC-CAV_FanNode, !- Fan Inlet Node Name
CAV_bas Supply Equipment Outlet Node, !- Fan Outlet Node Name
CAV_bas_CoolC-CAV_HeatCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
CAV_bas_HeatC SAT Manager, !- Name
Temperature, !- Control Variable
CAV_bas Supply Equipment Outlet Node, !- Reference Setpoint Node Name
CAV_bas_HeatC-CAV_FanNode, !- Fan Inlet Node Name
CAV_bas Supply Equipment Outlet Node, !- Fan Outlet Node Name
CAV_bas_HeatC-CAV_FanNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
CAV_bas_OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
Basement Inlet Nodes, !- Reference Setpoint Node Name
CAV_bas_HeatC-CAV_FanNode, !- Fan Inlet Node Name
CAV_bas Supply Equipment Outlet Node, !- Fan Outlet Node Name
CAV_bas_OA-CAV_CoolCNode;!- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_bot WITH REHEAT_CoolC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_bot WITH REHEAT_HeatC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_bot WITH REHEAT_OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_bot WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_mid WITH REHEAT_CoolC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_mid WITH REHEAT_HeatC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_mid WITH REHEAT_OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_mid WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_top WITH REHEAT_CoolC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_top WITH REHEAT_HeatC SAT Manager, !- Name
Temperature, !- Control Variable
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
VAV_top WITH REHEAT_OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Reference Setpoint Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Fan Inlet Node Name
VAV_top WITH REHEAT Supply Equipment Outlet Node, !- Fan Outlet Node Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
DataCenter Basement OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
Cooling Coil Air Outlet Node AirLoop DataCenter Basement, !- Reference Setpoint Node Name
DataCenter Basement Mixed Air Outlet, !- Fan Inlet Node Name
AirLoop DataCenter Basement Supply Fan Outlet, !- Fan Outlet Node Name
DataCenter Basement Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
DataCenter bot OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
Cooling Coil Air Outlet Node AirLoop DataCenter bot, !- Reference Setpoint Node Name
DataCenter bot Mixed Air Outlet, !- Fan Inlet Node Name
AirLoop DataCenter bot Supply Fan Outlet, !- Fan Outlet Node Name
DataCenter bot Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
DataCenter mid OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
Cooling Coil Air Outlet Node AirLoop DataCenter mid, !- Reference Setpoint Node Name
DataCenter mid Mixed Air Outlet, !- Fan Inlet Node Name
AirLoop DataCenter mid Supply Fan Outlet, !- Fan Outlet Node Name
DataCenter mid Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
DataCenter top OAMixed Air Temp Manager, !- Name
Temperature, !- Control Variable
Cooling Coil Air Outlet Node AirLoop DataCenter top, !- Reference Setpoint Node Name
DataCenter top Mixed Air Outlet, !- Fan Inlet Node Name
AirLoop DataCenter top Supply Fan Outlet, !- Fan Outlet Node Name
DataCenter top Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:OutdoorAirPretreat,
VAV_bot WITH REHEAT Heat Exhchanger Supply Air Temp Manager, !- Name
Temperature, !- Control Variable
-99, !- Minimum Setpoint Temperature {C}
99, !- Maximum Setpoint Temperature {C}
0.00001, !- Minimum Setpoint Humidity Ratio {kgWater/kgDryAir}
1.0, !- Maximum Setpoint Humidity Ratio {kgWater/kgDryAir}
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Reference Setpoint Node Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Stream Node Name
VAV_bot WITH REHEAT_OAInlet Node, !- Outdoor Air Stream Node Name
VAV_bot WITH REHEAT Supply Equipment Inlet Node, !- Return Air Stream Node Name
VAV_bot WITH REHEAT Heat Recovery Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:OutdoorAirPretreat,
VAV_mid WITH REHEAT Heat Exhchanger Supply Air Temp Manager, !- Name
Temperature, !- Control Variable
-99, !- Minimum Setpoint Temperature {C}
99, !- Maximum Setpoint Temperature {C}
0.00001, !- Minimum Setpoint Humidity Ratio {kgWater/kgDryAir}
1.0, !- Maximum Setpoint Humidity Ratio {kgWater/kgDryAir}
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Reference Setpoint Node Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Stream Node Name
VAV_mid WITH REHEAT_OAInlet Node, !- Outdoor Air Stream Node Name
VAV_mid WITH REHEAT Supply Equipment Inlet Node, !- Return Air Stream Node Name
VAV_mid WITH REHEAT Heat Recovery Outlet Node; !- Setpoint Node or NodeList Name
SetpointManager:OutdoorAirPretreat,
VAV_top WITH REHEAT Heat Exhchanger Supply Air Temp Manager, !- Name
Temperature, !- Control Variable
-99, !- Minimum Setpoint Temperature {C}
99, !- Maximum Setpoint Temperature {C}
0.00001, !- Minimum Setpoint Humidity Ratio {kgWater/kgDryAir}
1.0, !- Maximum Setpoint Humidity Ratio {kgWater/kgDryAir}
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Reference Setpoint Node Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Stream Node Name
VAV_top WITH REHEAT_OAInlet Node, !- Outdoor Air Stream Node Name
VAV_top WITH REHEAT Supply Equipment Inlet Node, !- Return Air Stream Node Name
VAV_top WITH REHEAT Heat Recovery Outlet Node; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: CONTROLLER:SIMPLE ===========
Controller:WaterCoil,
CAV_bas_CoolC_Controller,!- Name
Temperature, !- Control Variable
REVERSE, !- Action
FLOW, !- Actuator Variable
CAV_bas_CoolC-CAV_HeatCNode, !- Sensor Node Name
CAV_bas_CoolCDemand Inlet Node, !- Actuator Node Name
, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
CAV_bas_HeatC_Controller,!- Name
Temperature, !- Control Variable
NORMAL, !- Action
FLOW, !- Actuator Variable
CAV_bas_HeatC-CAV_FanNode, !- Sensor Node Name
CAV_bas_HeatCDemand Inlet Node, !- Actuator Node Name
0.0001, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_bot WITH REHEAT_CoolC_Controller, !- Name
Temperature, !- Control Variable
REVERSE, !- Action
FLOW, !- Actuator Variable
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Sensor Node Name
VAV_bot WITH REHEAT_CoolCDemand Inlet Node, !- Actuator Node Name
, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_bot WITH REHEAT_HeatC_Controller, !- Name
Temperature, !- Control Variable
NORMAL, !- Action
FLOW, !- Actuator Variable
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Sensor Node Name
VAV_bot WITH REHEAT_HeatCDemand Inlet Node, !- Actuator Node Name
0.0001, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_mid WITH REHEAT_CoolC_Controller, !- Name
Temperature, !- Control Variable
REVERSE, !- Action
FLOW, !- Actuator Variable
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Sensor Node Name
VAV_mid WITH REHEAT_CoolCDemand Inlet Node, !- Actuator Node Name
, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_mid WITH REHEAT_HeatC_Controller, !- Name
Temperature, !- Control Variable
NORMAL, !- Action
FLOW, !- Actuator Variable
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Sensor Node Name
VAV_mid WITH REHEAT_HeatCDemand Inlet Node, !- Actuator Node Name
0.0001, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_top WITH REHEAT_CoolC_Controller, !- Name
Temperature, !- Control Variable
REVERSE, !- Action
FLOW, !- Actuator Variable
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Sensor Node Name
VAV_top WITH REHEAT_CoolCDemand Inlet Node, !- Actuator Node Name
, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
VAV_top WITH REHEAT_HeatC_Controller, !- Name
Temperature, !- Control Variable
NORMAL, !- Action
FLOW, !- Actuator Variable
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Sensor Node Name
VAV_top WITH REHEAT_HeatCDemand Inlet Node, !- Actuator Node Name
0.0001, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
Controller:WaterCoil,
DataCenter_bas_HeatC_Controller, !- Name
Temperature, !- Control Variable
NORMAL, !- Action
FLOW, !- Actuator Variable
AirLoop DataCenter Basement Supply Air Outlet, !- Sensor Node Name
DataCenter_ExtraWaterHeatCDemand Inlet Node, !- Actuator Node Name
, !- Controller Convergence Tolerance {deltaC}
AUTOSIZE, !- Maximum Actuated Flow {m3/s}
0.0; !- Minimum Actuated Flow {m3/s}
!- =========== ALL OBJECTS IN CLASS: CONTROLLER:OUTSIDE AIR ===========
Controller:OutdoorAir,
CAV_bas_OA_Controller, !- Name
CAV_bas_OARelief Node, !- Relief Air Outlet Node Name
CAV_bas Supply Equipment Inlet Node, !- Return Air Node Name
CAV_bas_OA-CAV_CoolCNode, !- Mixed Air Node Name
CAV_bas_OAInlet Node, !- Actuator Node Name
AUTOSIZE, !- Minimum Outdoor Air Flow Rate {m3/s}
AUTOSIZE, !- Maximum Outdoor Air Flow Rate {m3/s}
DifferentialDryBulb, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
; !- Heat Recovery Bypass Control Type!- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
VAV_bot WITH REHEAT_OA_Controller, !- Name
VAV_bot WITH REHEAT_OARelief Node, !- Relief Air Outlet Node Name
VAV_bot WITH REHEAT Supply Equipment Inlet Node, !- Return Air Node Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_bot WITH REHEAT_OAInlet Node, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s} !- Minimum Outdoor Air Flow Rate {m3/s}
AUTOSIZE, !- Maximum Outdoor Air Flow Rate {m3/s}
DifferentialDryBulb, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
VAV_BOT WITH REHEAT Max OA Fraction, !- Maximum Fraction of Outdoor Air Schedule Name
VAV_bot WITH REHEAT_DCV, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenOAFlowGreaterThanMinimum; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
VAV_mid WITH REHEAT_OA_Controller, !- Name
VAV_mid WITH REHEAT_OARelief Node, !- Relief Air Outlet Node Name
VAV_mid WITH REHEAT Supply Equipment Inlet Node, !- Return Air Node Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_mid WITH REHEAT_OAInlet Node, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s} !- Minimum Outdoor Air Flow Rate {m3/s}
AUTOSIZE, !- Maximum Outdoor Air Flow Rate {m3/s}
DifferentialDryBulb, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
VAV_MID WITH REHEAT Max OA Fraction, !- Maximum Fraction of Outdoor Air Schedule Name
VAV_mid WITH REHEAT_DCV, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenOAFlowGreaterThanMinimum; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
VAV_top WITH REHEAT_OA_Controller, !- Name
VAV_top WITH REHEAT_OARelief Node, !- Relief Air Outlet Node Name
VAV_top WITH REHEAT Supply Equipment Inlet Node, !- Return Air Node Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Mixed Air Node Name
VAV_top WITH REHEAT_OAInlet Node, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s}
AUTOSIZE, !- Maximum Outdoor Air Flow Rate {m3/s}
DifferentialDryBulb, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
VAV_TOP WITH REHEAT Max OA Fraction, !- Maximum Fraction of Outdoor Air Schedule Name
VAV_top WITH REHEAT_DCV, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenOAFlowGreaterThanMinimum; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
AirLoop DataCenter Basement OA Controller, !- Name
DataCenter Basement Relief Air Outlet, !- Relief Air Outlet Node Name
AirLoop DataCenter Basement Return Air Inlet, !- Return Air Node Name
DataCenter Basement Mixed Air Outlet, !- Mixed Air Node Name
DataCenter Basement Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
DifferentialDryBulb, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched; !- Minimum Outdoor Air Schedule Name
Controller:OutdoorAir,
AirLoop DataCenter bot OA Controller, !- Name
DataCenter bot Relief Air Outlet, !- Relief Air Outlet Node Name
AirLoop DataCenter bot Return Air Inlet, !- Return Air Node Name
DataCenter bot Mixed Air Outlet, !- Mixed Air Node Name
DataCenter bot Outside Air Inlet, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched; !- Minimum Outdoor Air Schedule Name
Controller:OutdoorAir,
AirLoop DataCenter mid OA Controller, !- Name
DataCenter mid Relief Air Outlet, !- Relief Air Outlet Node Name
AirLoop DataCenter mid Return Air Inlet, !- Return Air Node Name
DataCenter mid Mixed Air Outlet, !- Mixed Air Node Name
DataCenter mid Outside Air Inlet, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched; !- Minimum Outdoor Air Schedule Name
Controller:OutdoorAir,
AirLoop DataCenter top OA Controller, !- Name
DataCenter top Relief Air Outlet, !- Relief Air Outlet Node Name
AirLoop DataCenter top Return Air Inlet, !- Return Air Node Name
DataCenter top Mixed Air Outlet, !- Mixed Air Node Name
DataCenter top Outside Air Inlet, !- Actuator Node Name
0, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C} !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
MinOA_MotorizedDamper_Sched; !- Minimum Outdoor Air Schedule Name
!- =========== ALL OBJECTS IN CLASS: CONTROLLER:MECHANICALVENTILATION ===========
Controller:MechanicalVentilation,
VAV_top WITH REHEAT_DCV, !- Name
MinOA_MotorizedDamper_Sched, !- Availability Schedule Name
Yes, !- Demand Controlled Ventilation
VentilationRateProcedure,!- System Outdoor Air Method
, !- Zone Maximum Outdoor Air Fraction {dimensionless}
Core_top, !- Zone 1 Name
CM DSOA Core_top, !- Design Specification Outdoor Air Object Name 1
CM DSZAD Core_top, !- Design Specification Zone Air Distribution Object Name 1
Perimeter_top_ZN_1, !- Zone 2 Name
CM DSOA Perimeter_top_ZN_1, !- Design Specification Outdoor Air Object Name 2
CM DSZAD Perimeter_top_ZN_1, !- Design Specification Zone Air Distribution Object Name 2
Perimeter_top_ZN_2, !- Zone 3 Name
CM DSOA Perimeter_top_ZN_2, !- Design Specification Outdoor Air Object Name 3
CM DSZAD Perimeter_top_ZN_2, !- Design Specification Zone Air Distribution Object Name 3
Perimeter_top_ZN_3, !- Zone 4 Name
CM DSOA Perimeter_top_ZN_3, !- Design Specification Outdoor Air Object Name 4
CM DSZAD Perimeter_top_ZN_3, !- Design Specification Zone Air Distribution Object Name 4
Perimeter_top_ZN_4, !- Zone 5 Name
CM DSOA Perimeter_top_ZN_4, !- Design Specification Outdoor Air Object Name 5
CM DSZAD Perimeter_top_ZN_4; !- Design Specification Zone Air Distribution Object Name 5
DesignSpecification:ZoneAirDistribution,
CM DSZAD Core_top, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_top_ZN_1, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_top_ZN_2, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_top_ZN_3, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_top_ZN_4, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:OutdoorAir,
CM DSOA Core_top, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_top_ZN_1, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_top_ZN_2, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_top_ZN_3, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_top_ZN_4, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
Controller:MechanicalVentilation,
VAV_bot WITH REHEAT_DCV, !- Name
MinOA_MotorizedDamper_Sched, !- Availability Schedule Name
Yes, !- Demand Controlled Ventilation
VentilationRateProcedure,!- System Outdoor Air Method
, !- Zone Maximum Outdoor Air Fraction {dimensionless}
Core_bottom, !- Zone 1 Name
CM DSOA Core_bottom, !- Design Specification Outdoor Air Object Name 1
CM DSZAD Core_bottom, !- Design Specification Zone Air Distribution Object Name 1
Perimeter_bot_ZN_1, !- Zone 2 Name
CM DSOA Perimeter_bot_ZN_1, !- Design Specification Outdoor Air Object Name 2
CM DSZAD Perimeter_bot_ZN_1, !- Design Specification Zone Air Distribution Object Name 2
Perimeter_bot_ZN_2, !- Zone 3 Name
CM DSOA Perimeter_bot_ZN_2, !- Design Specification Outdoor Air Object Name 3
CM DSZAD Perimeter_bot_ZN_2, !- Design Specification Zone Air Distribution Object Name 3
Perimeter_bot_ZN_3, !- Zone 4 Name
CM DSOA Perimeter_bot_ZN_3, !- Design Specification Outdoor Air Object Name 4
CM DSZAD Perimeter_bot_ZN_3, !- Design Specification Zone Air Distribution Object Name 4
Perimeter_bot_ZN_4, !- Zone 5 Name
CM DSOA Perimeter_bot_ZN_4, !- Design Specification Outdoor Air Object Name 5
CM DSZAD Perimeter_bot_ZN_4; !- Design Specification Zone Air Distribution Object Name 5
DesignSpecification:ZoneAirDistribution,
CM DSZAD Core_bottom, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_bot_ZN_1, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_bot_ZN_2, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_bot_ZN_3, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_bot_ZN_4, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:OutdoorAir,
CM DSOA Core_bottom, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_bot_ZN_1, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_bot_ZN_2, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_bot_ZN_3, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_bot_ZN_4, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
Controller:MechanicalVentilation,
VAV_mid WITH REHEAT_DCV, !- Name
MinOA_MotorizedDamper_Sched, !- Availability Schedule Name
Yes, !- Demand Controlled Ventilation
VentilationRateProcedure,!- System Outdoor Air Method
, !- Zone Maximum Outdoor Air Fraction {dimensionless}
Core_mid, !- Zone 1 Name
CM DSOA Core_mid, !- Design Specification Outdoor Air Object Name 1
CM DSZAD Core_mid, !- Design Specification Zone Air Distribution Object Name 1
Perimeter_mid_ZN_1, !- Zone 2 Name
CM DSOA Perimeter_mid_ZN_1, !- Design Specification Outdoor Air Object Name 2
CM DSZAD Perimeter_mid_ZN_1, !- Design Specification Zone Air Distribution Object Name 2
Perimeter_mid_ZN_2, !- Zone 3 Name
CM DSOA Perimeter_mid_ZN_2, !- Design Specification Outdoor Air Object Name 3
CM DSZAD Perimeter_mid_ZN_2, !- Design Specification Zone Air Distribution Object Name 3
Perimeter_mid_ZN_3, !- Zone 4 Name
CM DSOA Perimeter_mid_ZN_3, !- Design Specification Outdoor Air Object Name 4
CM DSZAD Perimeter_mid_ZN_3, !- Design Specification Zone Air Distribution Object Name 4
Perimeter_mid_ZN_4, !- Zone 5 Name
CM DSOA Perimeter_mid_ZN_4, !- Design Specification Outdoor Air Object Name 5
CM DSZAD Perimeter_mid_ZN_4; !- Design Specification Zone Air Distribution Object Name 5
DesignSpecification:ZoneAirDistribution,
CM DSZAD Core_mid, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_mid_ZN_1, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_mid_ZN_2, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_mid_ZN_3, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:ZoneAirDistribution,
CM DSZAD Perimeter_mid_ZN_4, !- Name
1, !- Zone Air Distribution Effectiveness in Cooling Mode {dimensionless}
1, !- Zone Air Distribution Effectiveness in Heating Mode {dimensionless}
; !- Zone Air Distribution Effectiveness Schedule Name
DesignSpecification:OutdoorAir,
CM DSOA Core_mid, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_mid_ZN_1, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_mid_ZN_2, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_mid_ZN_3, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
DesignSpecification:OutdoorAir,
CM DSOA Perimeter_mid_ZN_4, !- Name
Sum, !- Outdoor Air Method
0.00000001, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773; !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
!- =========== ALL OBJECTS IN CLASS: CONTROLLED ZONE EQUIP CONFIGURATION ===========
ZoneHVAC:EquipmentConnections,
Basement, !- Zone Name
Basement Equipment, !- Zone Conditioning Equipment List Name
Basement Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Basement Air Node, !- Zone Air Node Name
Basement Return Air Node;!- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Core_bottom, !- Zone Name
Core_bottom Equipment, !- Zone Conditioning Equipment List Name
Core_bottom Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Core_bottom Air Node, !- Zone Air Node Name
Core_bottom Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Core_mid, !- Zone Name
Core_mid Equipment, !- Zone Conditioning Equipment List Name
Core_mid Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Core_mid Air Node, !- Zone Air Node Name
Core_mid Return Air Node;!- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Core_top, !- Zone Name
Core_top Equipment, !- Zone Conditioning Equipment List Name
Core_top Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Core_top Air Node, !- Zone Air Node Name
Core_top Return Air Node;!- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_bot_ZN_3, !- Zone Name
Perimeter_bot_ZN_3 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_bot_ZN_3 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_bot_ZN_3 Air Node, !- Zone Air Node Name
Perimeter_bot_ZN_3 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_bot_ZN_2, !- Zone Name
Perimeter_bot_ZN_2 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_bot_ZN_2 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_bot_ZN_2 Air Node, !- Zone Air Node Name
Perimeter_bot_ZN_2 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_bot_ZN_1, !- Zone Name
Perimeter_bot_ZN_1 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_bot_ZN_1 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_bot_ZN_1 Air Node, !- Zone Air Node Name
Perimeter_bot_ZN_1 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_bot_ZN_4, !- Zone Name
Perimeter_bot_ZN_4 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_bot_ZN_4 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_bot_ZN_4 Air Node, !- Zone Air Node Name
Perimeter_bot_ZN_4 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_mid_ZN_3, !- Zone Name
Perimeter_mid_ZN_3 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_mid_ZN_3 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_mid_ZN_3 Air Node, !- Zone Air Node Name
Perimeter_mid_ZN_3 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_mid_ZN_2, !- Zone Name
Perimeter_mid_ZN_2 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_mid_ZN_2 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_mid_ZN_2 Air Node, !- Zone Air Node Name
Perimeter_mid_ZN_2 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_mid_ZN_1, !- Zone Name
Perimeter_mid_ZN_1 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_mid_ZN_1 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_mid_ZN_1 Air Node, !- Zone Air Node Name
Perimeter_mid_ZN_1 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_mid_ZN_4, !- Zone Name
Perimeter_mid_ZN_4 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_mid_ZN_4 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_mid_ZN_4 Air Node, !- Zone Air Node Name
Perimeter_mid_ZN_4 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_top_ZN_3, !- Zone Name
Perimeter_top_ZN_3 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_top_ZN_3 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_top_ZN_3 Air Node, !- Zone Air Node Name
Perimeter_top_ZN_3 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_top_ZN_2, !- Zone Name
Perimeter_top_ZN_2 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_top_ZN_2 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_top_ZN_2 Air Node, !- Zone Air Node Name
Perimeter_top_ZN_2 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_top_ZN_1, !- Zone Name
Perimeter_top_ZN_1 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_top_ZN_1 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_top_ZN_1 Air Node, !- Zone Air Node Name
Perimeter_top_ZN_1 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
Perimeter_top_ZN_4, !- Zone Name
Perimeter_top_ZN_4 Equipment, !- Zone Conditioning Equipment List Name
Perimeter_top_ZN_4 Inlet Nodes, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Perimeter_top_ZN_4 Air Node, !- Zone Air Node Name
Perimeter_top_ZN_4 Return Air Node; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
DataCenter_basement_ZN_6,!- Zone Name
DataCenter Basement Equipment, !- Zone Conditioning Equipment List Name
DataCenter Basement Inlets, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
DataCenter Basement Zone Air Node, !- Zone Air Node Name
DataCenter Basement Return Outlet; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
DataCenter_bot_ZN_6, !- Zone Name
DataCenter bot Equipment,!- Zone Conditioning Equipment List Name
DataCenter bot Inlets, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
DataCenter bot Zone Air Node, !- Zone Air Node Name
DataCenter bot Return Outlet; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
DataCenter_mid_ZN_6, !- Zone Name
DataCenter mid Equipment,!- Zone Conditioning Equipment List Name
DataCenter mid Inlets, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
DataCenter mid Zone Air Node, !- Zone Air Node Name
DataCenter mid Return Outlet; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
DataCenter_top_ZN_6, !- Zone Name
DataCenter top Equipment,!- Zone Conditioning Equipment List Name
DataCenter top Inlets, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
DataCenter top Zone Air Node, !- Zone Air Node Name
DataCenter top Return Outlet; !- Zone Return Air Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: ZONE EQUIPMENT LIST ===========
ZoneHVAC:EquipmentList,
Basement Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
Basement Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Core_bottom Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Core_bottom VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Core_mid Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Core_mid VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Core_top Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Core_top VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_bot_ZN_3 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_bot_ZN_3 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_bot_ZN_2 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_bot_ZN_2 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_bot_ZN_1 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_bot_ZN_1 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_bot_ZN_4 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_bot_ZN_4 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_mid_ZN_3 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_mid_ZN_3 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_mid_ZN_2 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_mid_ZN_2 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_mid_ZN_1 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_mid_ZN_1 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_mid_ZN_4 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_mid_ZN_4 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_top_ZN_3 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_top_ZN_3 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_top_ZN_2 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_top_ZN_2 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_top_ZN_1 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_top_ZN_1 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Perimeter_top_ZN_4 Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:AirDistributionUnit, !- Zone Equipment 1 Object Type
Perimeter_top_ZN_4 VAV Box, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
DataCenter Basement Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
DataCenter Basement Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
DataCenter bot Equipment,!- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
DataCenter bot Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
DataCenter mid Equipment,!- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
DataCenter mid Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
DataCenter top Equipment,!- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
DataCenter top Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
!- =========== ALL OBJECTS IN CLASS: AIR DISTRIBUTION UNIT ===========
ZoneHVAC:AirDistributionUnit,
Core_bottom VAV Box, !- Name
Core_bottom VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Core_bottom VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Core_mid VAV Box, !- Name
Core_mid VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Core_mid VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Core_top VAV Box, !- Name
Core_top VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Core_top VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_bot_ZN_3 VAV Box, !- Name
Perimeter_bot_ZN_3 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_bot_ZN_3 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_bot_ZN_2 VAV Box, !- Name
Perimeter_bot_ZN_2 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_bot_ZN_2 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_bot_ZN_1 VAV Box, !- Name
Perimeter_bot_ZN_1 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_bot_ZN_1 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_bot_ZN_4 VAV Box, !- Name
Perimeter_bot_ZN_4 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_bot_ZN_4 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_mid_ZN_3 VAV Box, !- Name
Perimeter_mid_ZN_3 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_mid_ZN_3 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_mid_ZN_2 VAV Box, !- Name
Perimeter_mid_ZN_2 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_mid_ZN_2 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_mid_ZN_1 VAV Box, !- Name
Perimeter_mid_ZN_1 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_mid_ZN_1 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_mid_ZN_4 VAV Box, !- Name
Perimeter_mid_ZN_4 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_mid_ZN_4 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_top_ZN_3 VAV Box, !- Name
Perimeter_top_ZN_3 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_top_ZN_3 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_top_ZN_2 VAV Box, !- Name
Perimeter_top_ZN_2 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_top_ZN_2 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_top_ZN_1 VAV Box, !- Name
Perimeter_top_ZN_1 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_top_ZN_1 VAV Box Component; !- Air Terminal Name
ZoneHVAC:AirDistributionUnit,
Perimeter_top_ZN_4 VAV Box, !- Name
Perimeter_top_ZN_4 VAV Box Outlet Node, !- Air Distribution Unit Outlet Node Name
AirTerminal:SingleDuct:VAV:Reheat, !- Air Terminal Object Type
Perimeter_top_ZN_4 VAV Box Component; !- Air Terminal Name
!- =========== ALL OBJECTS IN CLASS: AIRTERMINAL:SINGLEDUCT:UNCONTROLLED ===========
AirTerminal:SingleDuct:Uncontrolled,
Basement Direct Air, !- Name
ALWAYS_ON, !- Availability Schedule Name
Basement Direct Air Inlet Node Name, !- Zone Supply Air Node Name
AUTOSIZE; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
DataCenter Basement Direct Air, !- Name
Always_On, !- Availability Schedule Name
DataCenter Basement Supply Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
DataCenter bot Direct Air, !- Name
Always_On, !- Availability Schedule Name
DataCenter bot Supply Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
DataCenter mid Direct Air, !- Name
Always_On, !- Availability Schedule Name
DataCenter mid Supply Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
DataCenter top Direct Air, !- Name
Always_On, !- Availability Schedule Name
DataCenter top Supply Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
!- =========== ALL OBJECTS IN CLASS: AIRTERMINAL:SINGLEDUCT:VAV:REHEAT ===========
AirTerminal:SingleDuct:VAV:Reheat,
Core_bottom VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Core_bottom VAV Box Damper Node, !- Damper Air Outlet Node Name
Core_bottom VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.287, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Core_bottom VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Core_bottom VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Core_mid VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Core_mid VAV Box Damper Node, !- Damper Air Outlet Node Name
Core_mid VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.307, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Core_mid VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Core_mid VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Core_top VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Core_top VAV Box Damper Node, !- Damper Air Outlet Node Name
Core_top VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.307, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Core_top VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Core_top VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_bot_ZN_3 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_bot_ZN_3 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_bot_ZN_3 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.242, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_bot_ZN_3 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_bot_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_bot_ZN_2 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_bot_ZN_2 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_bot_ZN_2 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.103, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_bot_ZN_2 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_bot_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_bot_ZN_1 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_bot_ZN_1 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_bot_ZN_1 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.193, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_bot_ZN_1 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_bot_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_bot_ZN_4 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_bot_ZN_4 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_bot_ZN_4 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.085, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_bot_ZN_4 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_bot_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_mid_ZN_3 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_mid_ZN_3 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_mid_ZN_3 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.266, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_mid_ZN_3 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_mid_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_mid_ZN_2 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_mid_ZN_2 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_mid_ZN_2 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Scheduled, !- Zone Minimum Air Flow Input Method
, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
PERIMETER_MID_ZN_2_MDP_Sch, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_mid_ZN_2 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_mid_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_mid_ZN_1 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_mid_ZN_1 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_mid_ZN_1 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.198, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_mid_ZN_1 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_mid_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_mid_ZN_4 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_mid_ZN_4 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_mid_ZN_4 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.093, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_mid_ZN_4 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_mid_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_top_ZN_3 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_top_ZN_3 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_top_ZN_3 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.23, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_top_ZN_3 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_top_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_top_ZN_2 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_top_ZN_2 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_top_ZN_2 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.097, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_top_ZN_2 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_top_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_top_ZN_1 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_top_ZN_1 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_top_ZN_1 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.179, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_top_ZN_1 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_top_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
AirTerminal:SingleDuct:VAV:Reheat,
Perimeter_top_ZN_4 VAV Box Component, !- Name
ALWAYS_ON, !- Availability Schedule Name
Perimeter_top_ZN_4 VAV Box Damper Node, !- Damper Air Outlet Node Name
Perimeter_top_ZN_4 VAV Box Inlet Node, !- Air Inlet Node Name
AUTOSIZE, !- Maximum Air Flow Rate {m3/s}
Constant, !- Zone Minimum Air Flow Input Method
0.088, !- Constant Minimum Air Flow Fraction
, !- Fixed Minimum Air Flow Rate {m3/s}
, !- Minimum Air Flow Fraction Schedule Name
Coil:Heating:Water, !- Reheat Coil Object Type
Perimeter_top_ZN_4 VAV Box Reheat Coil, !- Reheat Coil Name
AUTOSIZE, !- Maximum Hot Water or Steam Flow Rate {m3/s}
0.0, !- Minimum Hot Water or Steam Flow Rate {m3/s}
Perimeter_top_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
0.001, !- Convergence Tolerance
ReverseWithLimits, !- Damper Heating Action
, !- Maximum Flow per Zone Floor Area During Reheat {m3/s-m2}
0.5, !- Maximum Flow Fraction During Reheat
40; !- Maximum Reheat Air Temperature {C}
!- =========== ALL OBJECTS IN CLASS: ZONECONTROL:HUMIDISTAT ===========
ZoneControl:Humidistat,
DataCenter Basement Humidistat, !- Name
DataCenter_basement_ZN_6,!- Zone Name
DC_MinRelHumSetSch; !- Humidifying Relative Humidity Setpoint Schedule Name
!- =========== ALL OBJECTS IN CLASS: ZONE CONTROL:THERMOSTATIC ===========
ZoneControl:Thermostat,
Basement Thermostat, !- Name
Basement, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Basement DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Core_bottom Thermostat, !- Name
Core_bottom, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Core_bottom DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Core_mid Thermostat, !- Name
Core_mid, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Core_mid DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Core_top Thermostat, !- Name
Core_top, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Core_top DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_bot_ZN_3 Thermostat, !- Name
Perimeter_bot_ZN_3, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_bot_ZN_3 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_bot_ZN_2 Thermostat, !- Name
Perimeter_bot_ZN_2, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_bot_ZN_2 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_bot_ZN_1 Thermostat, !- Name
Perimeter_bot_ZN_1, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_bot_ZN_1 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_bot_ZN_4 Thermostat, !- Name
Perimeter_bot_ZN_4, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_bot_ZN_4 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_mid_ZN_3 Thermostat, !- Name
Perimeter_mid_ZN_3, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_mid_ZN_3 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_mid_ZN_2 Thermostat, !- Name
Perimeter_mid_ZN_2, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_mid_ZN_2 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_mid_ZN_1 Thermostat, !- Name
Perimeter_mid_ZN_1, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_mid_ZN_1 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_mid_ZN_4 Thermostat, !- Name
Perimeter_mid_ZN_4, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_mid_ZN_4 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_top_ZN_3 Thermostat, !- Name
Perimeter_top_ZN_3, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_top_ZN_3 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_top_ZN_2 Thermostat, !- Name
Perimeter_top_ZN_2, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_top_ZN_2 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_top_ZN_1 Thermostat, !- Name
Perimeter_top_ZN_1, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_top_ZN_1 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
Perimeter_top_ZN_4 Thermostat, !- Name
Perimeter_top_ZN_4, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Perimeter_top_ZN_4 DualSPSched; !- Control 1 Name
ZoneControl:Thermostat,
DataCenter Basement Thermostat, !- Name
DataCenter_basement_ZN_6,!- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
DataCenter Cooling Setpoints Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
DataCenter bot Thermostat, !- Name
DataCenter_bot_ZN_6, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
DataCenter Cooling Setpoints Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
DataCenter mid Thermostat, !- Name
DataCenter_mid_ZN_6, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
DataCenter Cooling Setpoints Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
DataCenter top Thermostat, !- Name
DataCenter_top_ZN_6, !- Zone or ZoneList Name
Dual Zone Control Type Sched, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
DataCenter Cooling Setpoints Dual SP Control; !- Control 1 Name
!- =========== ALL OBJECTS IN CLASS: DUAL SETPOINT WITH DEADBAND ===========
ThermostatSetpoint:DualSetpoint,
Basement DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Core_bottom DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Core_mid DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Core_top DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_bot_ZN_3 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_bot_ZN_2 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_bot_ZN_1 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_bot_ZN_4 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_mid_ZN_3 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_mid_ZN_2 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM_w_SB, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM_w_SB; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_mid_ZN_1 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_mid_ZN_4 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_top_ZN_3 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_top_ZN_2 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_top_ZN_1 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Perimeter_top_ZN_4 DualSPSched, !- Name
HTGSETP_SCH_YES_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_SCH_YES_OPTIMUM; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
DataCenter Cooling Setpoints Dual SP Control, !- Name
HTGSETP_DC_SCH, !- Heating Setpoint Temperature Schedule Name
CLGSETP_DC_SCH; !- Cooling Setpoint Temperature Schedule Name
!- =========== ALL OBJECTS IN CLASS: ZONE SUPPLY AIR PATH ===========
AirLoopHVAC:SupplyPath,
CAV_bas, !- Name
CAV_bas Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
CAV_bas Supply Air Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
VAV_bot WITH REHEAT, !- Name
VAV_bot WITH REHEAT Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
VAV_bot WITH REHEAT Supply Air Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
VAV_mid WITH REHEAT, !- Name
VAV_mid WITH REHEAT Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
VAV_mid WITH REHEAT Supply Air Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
VAV_top WITH REHEAT, !- Name
VAV_top WITH REHEAT Zone Equipment Inlet Node, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
VAV_top WITH REHEAT Supply Air Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
AirLoop DataCenter Basement Supply Path, !- Name
ZoneSplitter DataCenter Basement Supply Air Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
AirLoop DataCenter Basement Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
AirLoop DataCenter bot Supply Path, !- Name
ZoneSplitter DataCenter bot Supply Air Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
AirLoop DataCenter bot Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
AirLoop DataCenter mid Supply Path, !- Name
ZoneSplitter DataCenter mid Supply Air Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
AirLoop DataCenter mid Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
AirLoop DataCenter top Supply Path, !- Name
ZoneSplitter DataCenter top Supply Air Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
AirLoop DataCenter top Zone Splitter; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: ZONE RETURN AIR PATH ===========
AirLoopHVAC:ReturnPath,
CAV_bas Return Air Path, !- Name
CAV_bas Zone Equipment Outlet Node, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
CAV_bas Return Air Mixer;!- Component 1 Name
AirLoopHVAC:ReturnPath,
VAV_bot WITH REHEAT Return Air Path, !- Name
VAV_bot WITH REHEAT Zone Equipment Outlet Node, !- Return Air Path Outlet Node Name
AirLoopHVAC:ReturnPlenum,!- Component 1 Object Type
GroundFloor_Return_Plenum, !- Component 1 Name
AirLoopHVAC:ZoneMixer, !- Component 2 Object Type
VAV_bot WITH REHEAT Return Air Mixer; !- Component 2 Name
AirLoopHVAC:ReturnPath,
VAV_mid WITH REHEAT Return Air Path, !- Name
VAV_mid WITH REHEAT Zone Equipment Outlet Node, !- Return Air Path Outlet Node Name
AirLoopHVAC:ReturnPlenum,!- Component 1 Object Type
MidFloor_Return_Plenum, !- Component 1 Name
AirLoopHVAC:ZoneMixer, !- Component 2 Object Type
VAV_mid WITH REHEAT Return Air Mixer; !- Component 2 Name
AirLoopHVAC:ReturnPath,
VAV_top WITH REHEAT Return Air Path, !- Name
VAV_top WITH REHEAT Zone Equipment Outlet Node, !- Return Air Path Outlet Node Name
AirLoopHVAC:ReturnPlenum,!- Component 1 Object Type
TopFloor_Return_Plenum, !- Component 1 Name
AirLoopHVAC:ZoneMixer, !- Component 2 Object Type
VAV_top WITH REHEAT Return Air Mixer; !- Component 2 Name
AirLoopHVAC:ReturnPath,
AirLoop DataCenter Basement Return Path, !- Name
ZoneMixer DataCenter Basement Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
AirLoop DataCenter Basement Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
AirLoop DataCenter bot Return Path, !- Name
ZoneMixer DataCenter bot Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
AirLoop DataCenter bot Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
AirLoop DataCenter mid Return Path, !- Name
ZoneMixer DataCenter mid Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
AirLoop DataCenter mid Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
AirLoop DataCenter top Return Path, !- Name
ZoneMixer DataCenter top Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
AirLoop DataCenter top Zone Mixer; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: ZONE RETURN PLENUM ===========
AirLoopHVAC:ReturnPlenum,
GroundFloor_Return_Plenum, !- Name
GroundFloor_Plenum, !- Zone Name
GroundFloor_Plenum Node, !- Zone Node Name
GroundFloor_Plenum Outlet Node, !- Outlet Node Name
, !- Induced Air Outlet Node or NodeList Name
Perimeter_bot_ZN_1 Return Air Node, !- Inlet 1 Node Name
Perimeter_bot_ZN_2 Return Air Node, !- Inlet 2 Node Name
Perimeter_bot_ZN_3 Return Air Node, !- Inlet 3 Node Name
Perimeter_bot_ZN_4 Return Air Node, !- Inlet 4 Node Name
Core_bottom Return Air Node; !- Inlet 5 Node Name
AirLoopHVAC:ReturnPlenum,
MidFloor_Return_Plenum, !- Name
MidFloor_Plenum, !- Zone Name
MidFloor_Plenum Node, !- Zone Node Name
MidFloor_Plenum Outlet Node, !- Outlet Node Name
, !- Induced Air Outlet Node or NodeList Name
Perimeter_mid_ZN_1 Return Air Node, !- Inlet 1 Node Name
Perimeter_mid_ZN_2 Return Air Node, !- Inlet 2 Node Name
Perimeter_mid_ZN_3 Return Air Node, !- Inlet 3 Node Name
Perimeter_mid_ZN_4 Return Air Node, !- Inlet 4 Node Name
Core_mid Return Air Node;!- Inlet 5 Node Name
AirLoopHVAC:ReturnPlenum,
TopFloor_Return_Plenum, !- Name
TopFloor_Plenum, !- Zone Name
TopFloor_Plenum Node, !- Zone Node Name
TopFloor_Plenum Outlet Node, !- Outlet Node Name
, !- Induced Air Outlet Node or NodeList Name
Perimeter_top_ZN_1 Return Air Node, !- Inlet 1 Node Name
Perimeter_top_ZN_2 Return Air Node, !- Inlet 2 Node Name
Perimeter_top_ZN_3 Return Air Node, !- Inlet 3 Node Name
Perimeter_top_ZN_4 Return Air Node, !- Inlet 4 Node Name
Core_top Return Air Node;!- Inlet 5 Node Name
!- =========== ALL OBJECTS IN CLASS: ZONE SPLITTER ===========
AirLoopHVAC:ZoneSplitter,
CAV_bas Supply Air Splitter, !- Name
CAV_bas Zone Equipment Inlet Node, !- Inlet Node Name
Basement Direct Air Inlet Node Name; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
VAV_bot WITH REHEAT Supply Air Splitter, !- Name
VAV_bot WITH REHEAT Zone Equipment Inlet Node, !- Inlet Node Name
Core_bottom VAV Box Inlet Node, !- Outlet 1 Node Name
Perimeter_bot_ZN_3 VAV Box Inlet Node, !- Outlet 2 Node Name
Perimeter_bot_ZN_2 VAV Box Inlet Node, !- Outlet 3 Node Name
Perimeter_bot_ZN_1 VAV Box Inlet Node, !- Outlet 4 Node Name
Perimeter_bot_ZN_4 VAV Box Inlet Node; !- Outlet 5 Node Name
AirLoopHVAC:ZoneSplitter,
VAV_mid WITH REHEAT Supply Air Splitter, !- Name
VAV_mid WITH REHEAT Zone Equipment Inlet Node, !- Inlet Node Name
Core_mid VAV Box Inlet Node, !- Outlet 1 Node Name
Perimeter_mid_ZN_3 VAV Box Inlet Node, !- Outlet 2 Node Name
Perimeter_mid_ZN_2 VAV Box Inlet Node, !- Outlet 3 Node Name
Perimeter_mid_ZN_1 VAV Box Inlet Node, !- Outlet 4 Node Name
Perimeter_mid_ZN_4 VAV Box Inlet Node; !- Outlet 5 Node Name
AirLoopHVAC:ZoneSplitter,
VAV_top WITH REHEAT Supply Air Splitter, !- Name
VAV_top WITH REHEAT Zone Equipment Inlet Node, !- Inlet Node Name
Core_top VAV Box Inlet Node, !- Outlet 1 Node Name
Perimeter_top_ZN_3 VAV Box Inlet Node, !- Outlet 2 Node Name
Perimeter_top_ZN_2 VAV Box Inlet Node, !- Outlet 3 Node Name
Perimeter_top_ZN_1 VAV Box Inlet Node, !- Outlet 4 Node Name
Perimeter_top_ZN_4 VAV Box Inlet Node; !- Outlet 5 Node Name
AirLoopHVAC:ZoneSplitter,
AirLoop DataCenter Basement Zone Splitter, !- Name
ZoneSplitter DataCenter Basement Supply Air Inlet, !- Inlet Node Name
DataCenter Basement Supply Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
AirLoop DataCenter bot Zone Splitter, !- Name
ZoneSplitter DataCenter bot Supply Air Inlet, !- Inlet Node Name
DataCenter bot Supply Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
AirLoop DataCenter mid Zone Splitter, !- Name
ZoneSplitter DataCenter mid Supply Air Inlet, !- Inlet Node Name
DataCenter mid Supply Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
AirLoop DataCenter top Zone Splitter, !- Name
ZoneSplitter DataCenter top Supply Air Inlet, !- Inlet Node Name
DataCenter top Supply Inlet; !- Outlet 1 Node Name
!- =========== ALL OBJECTS IN CLASS: ZONE MIXER ===========
AirLoopHVAC:ZoneMixer,
CAV_bas Return Air Mixer,!- Name
CAV_bas Zone Equipment Outlet Node, !- Outlet Node Name
Basement Return Air Node;!- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
VAV_bot WITH REHEAT Return Air Mixer, !- Name
VAV_bot WITH REHEAT Zone Equipment Outlet Node, !- Outlet Node Name
GroundFloor_Plenum Outlet Node; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
VAV_mid WITH REHEAT Return Air Mixer, !- Name
VAV_mid WITH REHEAT Zone Equipment Outlet Node, !- Outlet Node Name
MidFloor_Plenum Outlet Node; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
VAV_top WITH REHEAT Return Air Mixer, !- Name
VAV_top WITH REHEAT Zone Equipment Outlet Node, !- Outlet Node Name
TopFloor_Plenum Outlet Node; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
AirLoop DataCenter Basement Zone Mixer, !- Name
ZoneMixer DataCenter Basement Return Air Outlet, !- Outlet Node Name
DataCenter Basement Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
AirLoop DataCenter bot Zone Mixer, !- Name
ZoneMixer DataCenter bot Return Air Outlet, !- Outlet Node Name
DataCenter bot Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
AirLoop DataCenter mid Zone Mixer, !- Name
ZoneMixer DataCenter mid Return Air Outlet, !- Outlet Node Name
DataCenter mid Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
AirLoop DataCenter top Zone Mixer, !- Name
ZoneMixer DataCenter top Return Air Outlet, !- Outlet Node Name
DataCenter top Return Outlet; !- Inlet 1 Node Name
!- =========== ALL OBJECTS IN CLASS: BOILER:SIMPLE ===========
Boiler:HotWater,
HeatSys1 Boiler, !- Name
NATURALGAS, !- Fuel Type
1953430.325, !- Nominal Capacity {W}
0.8125, !- Nominal Thermal Efficiency
LeavingBoiler, !- Efficiency Curve Temperature Evaluation Variable
HeatSys1 Boiler Efficiency Curve, !- Normalized Boiler Efficiency Curve Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
0.0, !- Minimum Part Load Ratio
1.2, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
HeatSys1 Pump-HeatSys1 BoilerNode, !- Boiler Water Inlet Node Name
HeatSys1 Supply Equipment Outlet Node, !- Boiler Water Outlet Node Name
95.0, !- Water Outlet Upper Temperature Limit {C}
LeavingSetpointModulated;!- Boiler Flow Mode
SetpointManager:Scheduled,
HeatSys1 Boiler Setpoint Manager, !- Name
Temperature, !- Control Variable
HW-Loop-Temp-Schedule, !- Schedule Name
HeatSys1 Supply Equipment Outlet Node; !- Setpoint Node or NodeList Name
Boiler:HotWater,
Dummy Boiler, !- Name
NaturalGas, !- Fuel Type
93894.07, !- Nominal Capacity {W}
0.8, !- Nominal Thermal Efficiency
LeavingBoiler, !- Efficiency Curve Temperature Evaluation Variable
Dummy Boiler Efficiency Curve, !- Normalized Boiler Efficiency Curve Name
autosize, !- Design Water Flow Rate {m3/s}
0.0, !- Minimum Part Load Ratio
1.2, !- Maximum Part Load Ratio
1.0, !- Optimum Part Load Ratio
Dummy Boiler Inlet Node, !- Boiler Water Inlet Node Name
Dummy Boiler Outlet Node,!- Boiler Water Outlet Node Name
95, !- Water Outlet Upper Temperature Limit {C}
ConstantFlow; !- Boiler Flow Mode
Curve:Quadratic,
HeatSys1 Boiler Efficiency Curve, !- Name
1.0, !- Coefficient1 Constant
0.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0, !- Minimum Value of x
1; !- Maximum Value of x
Curve:Quadratic,
Dummy Boiler Efficiency Curve, !- Name
1.0, !- Coefficient1 Constant
0.0, !- Coefficient2 x
0.0, !- Coefficient3 x**2
0, !- Minimum Value of x
1; !- Maximum Value of x
!- =========== ALL OBJECTS IN CLASS: Chiller:Electric:ReformulatedEIR ===========
Chiller:Electric:ReformulatedEIR,
CoolSys1 Chiller1, !- Name
1302254.38, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
6.6700, !- Reference Leaving Chilled Water Temperature {C}
34.4444, !- Reference Leaving Condenser Water Temperature {C}
0.03697765, !- Reference Chilled Water Flow Rate {m3/s}
AutoSize, !- Reference Condenser Water Flow Rate {m3/s}
WC_CENT_2010_PB_CAPFT, !- Cooling Capacity Function of Temperature Curve Name
WC_CENT_2010_PB_EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
LeavingCondenserWaterTemperature, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Type
WC_CENT_300to600_2010_PB_EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.1000, !- Minimum Part Load Ratio
1.0000, !- Maximum Part Load Ratio
1.0000, !- Optimum Part Load Ratio
0.1000, !- Minimum Unloading Ratio
CoolSys1 Pump-CoolSys1 Chiller1Node, !- Chilled Water Inlet Node Name
CoolSys1 Supply Equipment Outlet Node 1, !- Chilled Water Outlet Node Name
CoolSys1 Chiller1 Water Inlet Node, !- Condenser Inlet Node Name
CoolSys1 Chiller1 Water Outlet Node, !- Condenser Outlet Node Name
, !- Fraction of Compressor Electric Consumption Rejected by Condenser
5.0000, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode Type
0.0000; !- Design Heat Recovery Water Flow Rate {m3/s}
Chiller:Electric:ReformulatedEIR,
CoolSys1 Chiller2, !- Name
1302254.38, !- Reference Capacity {W}
6.28, !- Reference COP {W/W}
6.6700, !- Reference Leaving Chilled Water Temperature {C}
34.4444, !- Reference Leaving Condenser Water Temperature {C}
0.03697765, !- Reference Chilled Water Flow Rate {m3/s}
AutoSize, !- Reference Condenser Water Flow Rate {m3/s}
WC_CENT_2010_PB_CAPFT, !- Cooling Capacity Function of Temperature Curve Name
WC_CENT_2010_PB_EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name
LeavingCondenserWaterTemperature, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Type
WC_CENT_300to600_2010_PB_EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name
0.1000, !- Minimum Part Load Ratio
1.0000, !- Maximum Part Load Ratio
1.0000, !- Optimum Part Load Ratio
0.1000, !- Minimum Unloading Ratio
CoolSys1 Pump-CoolSys1 Chiller2Node, !- Chilled Water Inlet Node Name
CoolSys1 Supply Equipment Outlet Node 2, !- Chilled Water Outlet Node Name
CoolSys1 Chiller2 Water Inlet Node, !- Condenser Inlet Node Name
CoolSys1 Chiller2 Water Outlet Node, !- Condenser Outlet Node Name
, !- Fraction of Compressor Electric Consumption Rejected by Condenser
5.0000, !- Leaving Chilled Water Lower Temperature Limit {C}
ConstantFlow, !- Chiller Flow Mode Type
0.0000; !- Design Heat Recovery Water Flow Rate {m3/s}
!- =========== ALL OBJECTS IN CLASS: WATER HEATER:MIXED ===========
WaterHeater:Mixed,
SHWSys1 Water Heater, !- Name
1.135624, !- Tank Volume {m3}
SHWSys1 Water Heater Setpoint Temperature Schedule, !- Setpoint Temperature Schedule Name
2.0, !- Deadband Temperature Difference {deltaC}
82.2222, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
87921.32, !- Heater Maximum Capacity {W}
, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
NATURALGAS, !- Heater Fuel Type
0.803988738, !- Heater Thermal Efficiency
, !- Part Load Factor Curve Name
7280.88, !- Off Cycle Parasitic Fuel Consumption Rate {W}
NATURALGAS, !- Off Cycle Parasitic Fuel Type
0.8, !- Off Cycle Parasitic Heat Fraction to Tank
7280.88, !- On Cycle Parasitic Fuel Consumption Rate {W}
NATURALGAS, !- On Cycle Parasitic Fuel Type
, !- On Cycle Parasitic Heat Fraction to Tank
zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
BASEMENT, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
11.25413987, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
11.25413987, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
, !- Peak Use Flow Rate {m3/s}
, !- Use Flow Rate Fraction Schedule Name
, !- Cold Water Supply Temperature Schedule Name
SHWSys1 Pump-SHWSys1 Water HeaterNode, !- Use Side Inlet Node Name
SHWSys1 Supply Equipment Outlet Node, !- Use Side Outlet Node Name
1.0, !- Use Side Effectiveness
, !- Source Side Inlet Node Name
, !- Source Side Outlet Node Name
1.0, !- Source Side Effectiveness
AUTOSIZE, !- Use Side Design Flow Rate {m3/s}
AUTOSIZE, !- Source Side Design Flow Rate {m3/s}
1.5; !- Indirect Water Heating Recovery Time {hr}
!- =========== ALL OBJECTS IN CLASS: COOLING TOWER:TWO SPEED ===========
!- Design Outdoor Air Wet-Bulb Temperature from the EPW file
!- Design Range Temperature is set to 10 deltaF per 90.1-2010 G3.1.3.13
!- Design Approach Temperature. Per 90.1-2010 G3.1.3.13, condenser water design supply temperature shall be
!- 85F or 10F approaching design wet-bulb temperature, whichever is lower, with a design temperature rise of 10F (range temperature).
!- Therefore, we use Design Approach Temperature to set condenser water design supply temperature, i.e. Design Approach Temperature = min(10F, (85 - Design OA WbT from EPW))
CoolingTower:VariableSpeed,
TowerWaterSys CoolTower 1, !- Name
TowerWaterSys Pump-TowerWaterSys CoolTower1Node, !- Water Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node 1, !- Water Outlet Node Name
CoolToolsCrossFlow, !- Model Type
, !- Model Coefficient Name
24.9, !- Design Inlet Air Wet-Bulb Temperature {C}
4.54444444444444, !- Design Approach Temperature {deltaC}
5.55555555555556, !- Design Range Temperature {deltaC}
0.05355, !- Design Water Flow Rate {m3/s}
autosize, !- Design Air Flow Rate {m3/s}
18925.9767634185, !- Design Fan Power {W}
Tower_Fan_Curve, !- Fan Power Ratio Function of Air Flow Rate Ratio Curve Name
0.2, !- Minimum Air Flow Rate Ratio
0.125, !- Fraction of Tower Capacity in Free Convection Regime
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
, !- Drift Loss Percent {percent}
, !- Blowdown Calculation Mode
, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
, !- Outdoor Air Inlet Node Name
2, !- Number of Cells
MaximalCell, !- Cell Control !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.000; !- Sizing Factor
CoolingTower:VariableSpeed,
TowerWaterSys CoolTower 2, !- Name
TowerWaterSys Pump-TowerWaterSys CoolTower2Node, !- Water Inlet Node Name
TowerWaterSys Supply Equipment Outlet Node 2, !- Water Outlet Node Name
CoolToolsCrossFlow, !- Model Type
, !- Model Coefficient Name
24.9, !- Design Inlet Air Wet-Bulb Temperature {C}
4.54444444444444, !- Design Approach Temperature {deltaC}
5.55555555555556, !- Design Range Temperature {deltaC}
0.05355, !- Design Water Flow Rate {m3/s}
autosize, !- Design Air Flow Rate {m3/s}
18925.9767634185, !- Design Fan Power {W}
Tower_Fan_Curve, !- Fan Power Ratio Function of Air Flow Rate Ratio Curve Name
0.2, !- Minimum Air Flow Rate Ratio
0.125, !- Fraction of Tower Capacity in Free Convection Regime
, !- Basin Heater Capacity {W/K}
, !- Basin Heater Setpoint Temperature {C}
, !- Basin Heater Operating Schedule Name
, !- Evaporation Loss Mode
, !- Evaporation Loss Factor {percent/K}
, !- Drift Loss Percent {percent}
, !- Blowdown Calculation Mode
, !- Blowdown Concentration Ratio
, !- Blowdown Makeup Water Usage Schedule Name
, !- Supply Water Storage Tank Name
, !- Outdoor Air Inlet Node Name
2, !- Number of Cells
MaximalCell, !- Cell Control !- Cell Control
, !- Cell Minimum Water Flow Rate Fraction
, !- Cell Maximum Water Flow Rate Fraction
1.000; !- Sizing Factor
!- =========== ALL OBJECTS IN CLASS: FLUIDCOOLER:SINGLESPEED ===========
!- Based on EnergyPlus 9.0 Reference, default
!- Low Fan Speed U-Factor Times Area Sizing Factor 0.6
!- Low Speed Nominal Capacity Sizing Factor 0.5
!- Low Fan Speed Air Flow Rate Sizing Factor 0.5
!- Low Fan Speed Fan Power Sizing Factor 0.16
FluidCooler:TwoSpeed,
Central Tower, !- Name
Central Tower Inlet Node,!- Water Inlet Node Name
Central Tower Outlet Node, !- Water Outlet Node Name
NominalCapacity, !- Performance Input Method
, !- High Fan Speed U-factor Times Area Value {W/K}
, !- Low Fan Speed U-factor Times Area Value {W/K}
0.6, !- Low Fan Speed U-Factor Times Area Sizing Factor
582060, !- High Speed Nominal Capacity {W}
291030, !- Low Speed Nominal Capacity {W}
0.5, !- Low Speed Nominal Capacity Sizing Factor
51.67, !- Design Entering Water Temperature {C}
35, !- Design Entering Air Temperature {C}
25.6, !- Design Entering Air Wet-bulb Temperature {C}
autosize, !- Design Water Flow Rate {m3/s}
autosize, !- High Fan Speed Air Flow Rate {m3/s}
43776.2410666667, !- High Fan Speed Fan Power {W}
autocalculate, !- Low Fan Speed Air Flow Rate {m3/s}
0.5, !- Low Fan Speed Air Flow Rate Sizing Factor
autocalculate, !- Low Fan Speed Fan Power {W}
0.16; !- Low Fan Speed Fan Power Sizing Factor
!- =========== ALL OBJECTS IN CLASS: PUMP:VARIABLE SPEED ===========
Pump:ConstantSpeed,
SHWSys1 Pump, !- Name
SHWSys1 Supply Inlet Node, !- Inlet Node Name
SHWSys1 Pump-SHWSys1 Water HeaterNodeviaConnector, !- Outlet Node Name
AUTOSIZE, !- Design Flow Rate {m3/s}
29891, !- Design Pump Head {Pa}
AUTOSIZE, !- Design Power Consumption {W}
0.30, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
Intermittent; !- Pump Control Type
Pump:VariableSpeed,
HeatSys1 Pump, !- Name
HeatSys1 Supply Inlet Node, !- Inlet Node Name
HeatSys1 Pump-HeatSys1 BoilerNodeviaConnector, !- Outlet Node Name
AUTOSIZE, !- Design Maximum Flow Rate {m3/s}
179352, !- Design Pump Head {Pa}
AUTOSIZE, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
0,0.0205, 0.4101,0.5753, !- VariableSpeed Pump Curve Coefficients
0, !- Minimum Flow Rate {m3/s}
Intermittent;
Pump:ConstantSpeed,
CoolSys1 Chiller1 Pump, !- Name
CoolSys1 Chiller1 Pump Inlet Node, !- Inlet Node Name
CoolSys1 Pump-CoolSys1 Chiller1Node, !- Outlet Node Name
AUTOSIZE, !- Design Flow Rate {m3/s}
44761.27683, !- Design Pump Head {Pa}
AUTOSIZE, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
Intermittent, !- Pump Control Type
; !- Pump Flow Rate Schedule Name
Pump:ConstantSpeed,
CoolSys1 Chiller2 Pump, !- Name
CoolSys1 Chiller2 Pump Inlet Node, !- Inlet Node Name
CoolSys1 Pump-CoolSys1 Chiller2Node, !- Outlet Node Name
AUTOSIZE, !- Design Flow Rate {m3/s}
44761.27683, !- Design Pump Head {Pa}
AUTOSIZE, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
Intermittent, !- Pump Control Type
; !- Pump Flow Rate Schedule Name
Pump:VariableSpeed,
CoolSys1 Pump Secondary, !- Name
CoolSys1 Demand Inlet Node, !- Inlet Node Name
CoolSys1 Pump Secondary-CoolSys1 Demand Mixer, !- Outlet Node Name
autosize, !- Design Maximum Flow Rate {m3/s}
134283.8305, !- Design Pump Head {Pa}
autosize, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0, !- Fraction of Motor Inefficiencies to Fluid Stream
0,0.0205, 0.4101,0.5753, !- VariableSpeed Pump Curve Coefficients
0, !- Minimum Flow Rate {m3/s}
Intermittent;
!- =========== ALL OBJECTS IN CLASS: PUMP:CONSTANT SPEED ===========
Pump:ConstantSpeed,
Plant Circ Pump, !- Name
Plant Supply Inlet Node, !- Inlet Node Name
Plant Pump Outlet Node, !- Outlet Node Name
autosize, !- Design Flow Rate {m3/s}
179045.1073, !- Design Pump Head {Pa}
autosize, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
Intermittent; !- Pump Control Type
HeaderedPumps:VariableSpeed,
TowerWaterSys Pump, !- Name
TowerWaterSys Supply Inlet Node, !- Inlet Node Name
TowerWaterSys Pump-TowerWaterSys CoolTowerNodeviaConnector, !- Outlet Node Name
AUTOSIZE, !- Total Design Flow Rate {m3/s}
2, !- Number of Pumps in Bank
SEQUENTIAL, !- Flow Sequencing Control Scheme
148556.6249, !- Design Pump Head {Pa}
autosize, !- Design Power Consumption {W}
0.909, !- Motor Efficiency
0.0, !- Fraction of Motor Inefficiencies to Fluid Stream
0, !- Coefficient 1 of the Part Load Performance Curve
0.0216, !- Coefficient 2 of the Part Load Performance Curve
-0.0325, !- Coefficient 3 of the Part Load Performance Curve
1.0095, !- Coefficient 4 of the Part Load Performance Curve
0, !- Minimum Flow Rate Fraction
Intermittent, !- Pump Control Type
; !- Pump Flow Rate Schedule Name
!- =========== ALL OBJECTS IN CLASS: COIL:WATER:COOLING ===========
Coil:Cooling:Water,
CAV_bas_CoolC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- Design Air Flow Rate {m3/s}
AUTOSIZE, !- Design Inlet Water Temperature {C}
AUTOSIZE, !- Design Inlet Air Temperature {C}
AUTOSIZE, !- Design Outlet Air Temperature {C}
AUTOSIZE, !- Design Inlet Air Humidity Ratio {kgWater/kgDryAir}
AUTOSIZE, !- Design Outlet Air Humidity Ratio {kgWater/kgDryAir}
CAV_bas_CoolCDemand Inlet Node, !- Water Inlet Node Name
CAV_bas_CoolCDemand Outlet Node, !- Water Outlet Node Name
CAV_bas_OA-CAV_CoolCNode,!- Air Inlet Node Name
CAV_bas_CoolC-CAV_HeatCNode, !- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger Configuration
Coil:Cooling:Water,
VAV_bot WITH REHEAT_CoolC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- Design Air Flow Rate {m3/s}
AUTOSIZE, !- Design Inlet Water Temperature {C}
AUTOSIZE, !- Design Inlet Air Temperature {C}
AUTOSIZE, !- Design Outlet Air Temperature {C}
AUTOSIZE, !- Design Inlet Air Humidity Ratio {kgWater/kgDryAir}
AUTOSIZE, !- Design Outlet Air Humidity Ratio {kgWater/kgDryAir}
VAV_bot WITH REHEAT_CoolCDemand Inlet Node, !- Water Inlet Node Name
VAV_bot WITH REHEAT_CoolCDemand Outlet Node, !- Water Outlet Node Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Air Inlet Node Name
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger Configuration
Coil:Cooling:Water,
VAV_mid WITH REHEAT_CoolC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- Design Air Flow Rate {m3/s}
AUTOSIZE, !- Design Inlet Water Temperature {C}
AUTOSIZE, !- Design Inlet Air Temperature {C}
AUTOSIZE, !- Design Outlet Air Temperature {C}
AUTOSIZE, !- Design Inlet Air Humidity Ratio {kgWater/kgDryAir}
AUTOSIZE, !- Design Outlet Air Humidity Ratio {kgWater/kgDryAir}
VAV_mid WITH REHEAT_CoolCDemand Inlet Node, !- Water Inlet Node Name
VAV_mid WITH REHEAT_CoolCDemand Outlet Node, !- Water Outlet Node Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Air Inlet Node Name
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger Configuration
Coil:Cooling:Water,
VAV_top WITH REHEAT_CoolC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- Design Water Flow Rate {m3/s}
AUTOSIZE, !- Design Air Flow Rate {m3/s}
AUTOSIZE, !- Design Inlet Water Temperature {C}
AUTOSIZE, !- Design Inlet Air Temperature {C}
AUTOSIZE, !- Design Outlet Air Temperature {C}
AUTOSIZE, !- Design Inlet Air Humidity Ratio {kgWater/kgDryAir}
AUTOSIZE, !- Design Outlet Air Humidity Ratio {kgWater/kgDryAir}
VAV_top WITH REHEAT_CoolCDemand Inlet Node, !- Water Inlet Node Name
VAV_top WITH REHEAT_CoolCDemand Outlet Node, !- Water Outlet Node Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Air Inlet Node Name
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Outlet Node Name
SimpleAnalysis, !- Type of Analysis
CrossFlow; !- Heat Exchanger Configuration
!- =========== ALL OBJECTS IN CLASS: COIL:WATER:SIMPLEHEATING ===========
Coil:Heating:Water,
DataCenter_ExtraWaterHeatC, !- Name
DataCenter_ExtraWaterHeatC_Sch, !- Availability Schedule Name
, !- U-Factor Times Area Value {W/K}
, !- Maximum Water Flow Rate {m3/s}
DataCenter_ExtraWaterHeatCDemand Inlet Node, !- Water Inlet Node Name
DataCenter_ExtraWaterHeatCDemand Outlet Node, !- Water Outlet Node Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode, !- Air Inlet Node Name
AirLoop DataCenter Basement Supply Air Outlet, !- Air Outlet Node Name
NominalCapacity, !- Performance Input Method
0, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
16.6, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
32.2, !- Rated Outlet Air Temperature {C}
0.5; !- Rated Ratio for Air and Water Convection
Coil:Heating:Electric,
DataCenter_ExtraElecHeatC, !- Name
DataCenter_ExtraElecHeatC_Sch, !- Availability Schedule Name
1.0000, !- Efficiency
10000000, !- Nominal Capacity {W}
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode, !- Air Inlet Node Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode, !- Air Outlet Node Name
DataCenter_ExtraElecHeatC-DataCenter_ExtraWaterHeatCNode; !- Temperature Setpoint Node Name
Coil:Heating:Water,
Core_bottom VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Core_bottom VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Core_bottom VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Core_bottom VAV Box Damper Node, !- Air Inlet Node Name
Core_bottom VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Core_mid VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Core_mid VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Core_mid VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Core_mid VAV Box Damper Node, !- Air Inlet Node Name
Core_mid VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Core_top VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Core_top VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Core_top VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Core_top VAV Box Damper Node, !- Air Inlet Node Name
Core_top VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_bot_ZN_3 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_bot_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_bot_ZN_3 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_bot_ZN_3 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_bot_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_bot_ZN_2 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_bot_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_bot_ZN_2 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_bot_ZN_2 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_bot_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_bot_ZN_1 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_bot_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_bot_ZN_1 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_bot_ZN_1 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_bot_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_bot_ZN_4 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_bot_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_bot_ZN_4 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_bot_ZN_4 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_bot_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_mid_ZN_3 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_mid_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_mid_ZN_3 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_mid_ZN_3 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_mid_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_mid_ZN_2 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_mid_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_mid_ZN_2 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_mid_ZN_2 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_mid_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_mid_ZN_1 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_mid_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_mid_ZN_1 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_mid_ZN_1 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_mid_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_mid_ZN_4 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_mid_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_mid_ZN_4 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_mid_ZN_4 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_mid_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_top_ZN_3 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_top_ZN_3 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_top_ZN_3 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_top_ZN_3 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_top_ZN_3 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_top_ZN_2 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_top_ZN_2 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_top_ZN_2 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_top_ZN_2 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_top_ZN_2 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_top_ZN_1 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_top_ZN_1 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_top_ZN_1 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_top_ZN_1 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_top_ZN_1 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
Perimeter_top_ZN_4 VAV Box Reheat Coil, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
Perimeter_top_ZN_4 VAV Box Reheat CoilDemand Inlet Node, !- Water Inlet Node Name
Perimeter_top_ZN_4 VAV Box Reheat CoilDemand Outlet Node, !- Water Outlet Node Name
Perimeter_top_ZN_4 VAV Box Damper Node, !- Air Inlet Node Name
Perimeter_top_ZN_4 VAV Box Outlet Node, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
CAV_bas_HeatC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
CAV_bas_HeatCDemand Inlet Node, !- Water Inlet Node Name
CAV_bas_HeatCDemand Outlet Node, !- Water Outlet Node Name
CAV_bas_CoolC-CAV_HeatCNode, !- Air Inlet Node Name
CAV_bas_HeatC-CAV_FanNode, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
VAV_bot WITH REHEAT_HeatC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
VAV_bot WITH REHEAT_HeatCDemand Inlet Node, !- Water Inlet Node Name
VAV_bot WITH REHEAT_HeatCDemand Outlet Node, !- Water Outlet Node Name
VAV_bot WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Inlet Node Name
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
VAV_mid WITH REHEAT_HeatC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
VAV_mid WITH REHEAT_HeatCDemand Inlet Node, !- Water Inlet Node Name
VAV_mid WITH REHEAT_HeatCDemand Outlet Node, !- Water Outlet Node Name
VAV_mid WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Inlet Node Name
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
Coil:Heating:Water,
VAV_top WITH REHEAT_HeatC, !- Name
ALWAYS_ON, !- Availability Schedule Name
AUTOSIZE, !- U-Factor Times Area Value {W/K}
AUTOSIZE, !- Maximum Water Flow Rate {m3/s}
VAV_top WITH REHEAT_HeatCDemand Inlet Node, !- Water Inlet Node Name
VAV_top WITH REHEAT_HeatCDemand Outlet Node, !- Water Outlet Node Name
VAV_top WITH REHEAT_CoolC-VAV WITH REHEAT_HeatCNode, !- Air Inlet Node Name
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Outlet Node Name
UFactorTimesAreaAndDesignWaterFlowRate, !- Performance Input Method
AUTOSIZE, !- Rated Capacity {W}
82.2, !- Rated Inlet Water Temperature {C}
12.8, !- Rated Inlet Air Temperature {C}
71.1, !- Rated Outlet Water Temperature {C}
40.0, !- Rated Outlet Air Temperature {C}
; !- Rated Ratio for Air and Water Convection
!- =========== ALL OBJECTS IN CLASS: COIL:HEATING:ELECTRIC ===========
Coil:Heating:Electric,
Heat Pump DX Supp Heating Coil AirLoop DataCenter Basement, !- Name
ALWAYS_OFF, !- Availability Schedule Name
1, !- Efficiency
autosize, !- Nominal Capacity {W}
Heating Coil Air Outlet Node AirLoop DataCenter Basement, !- Air Inlet Node Name
AirLoop DataCenter Basement Humidifier Inlet; !- Air Outlet Node Name
Coil:Heating:Electric,
Heat Pump DX Supp Heating Coil AirLoop DataCenter bot, !- Name
ALWAYS_OFF, !- Availability Schedule Name
1, !- Efficiency
autosize, !- Nominal Capacity {W}
Heating Coil Air Outlet Node AirLoop DataCenter bot, !- Air Inlet Node Name
AirLoop DataCenter bot Supply Air Outlet; !- Air Outlet Node Name
Coil:Heating:Electric,
Heat Pump DX Supp Heating Coil AirLoop DataCenter mid, !- Name
ALWAYS_OFF, !- Availability Schedule Name
1, !- Efficiency
autosize, !- Nominal Capacity {W}
Heating Coil Air Outlet Node AirLoop DataCenter mid, !- Air Inlet Node Name
AirLoop DataCenter mid Supply Air Outlet; !- Air Outlet Node Name
Coil:Heating:Electric,
Heat Pump DX Supp Heating Coil AirLoop DataCenter top, !- Name
ALWAYS_OFF, !- Availability Schedule Name
1, !- Efficiency
autosize, !- Nominal Capacity {W}
Heating Coil Air Outlet Node AirLoop DataCenter top, !- Air Inlet Node Name
AirLoop DataCenter top Supply Air Outlet; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT ===========
Coil:Cooling:WaterToAirHeatPump:EquationFit,
Heat Pump Cooling Mode AirLoop DataCenter Basement, !- Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side1 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side1 Outlet Node, !- Water Outlet Node Name
AirLoop DataCenter Basement Supply Fan Outlet, !- Air Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter Basement, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Cooling Capacity {W}
3.878739046, !- Gross Rated Cooling COP
-4.30266987344639, !- Total Cooling Capacity Coefficient 1
7.18536990534372, !- Total Cooling Capacity Coefficient 2
-2.23946714486189, !- Total Cooling Capacity Coefficient 3
0.139995928440879, !- Total Cooling Capacity Coefficient 4
0.102660179888915, !- Total Cooling Capacity Coefficient 5
6.0019444814887, !- Sensible Cooling Capacity Coefficient 1
22.6300677244073, !- Sensible Cooling Capacity Coefficient 2
-26.7960783730934, !- Sensible Cooling Capacity Coefficient 3
-1.72374720346819, !- Sensible Cooling Capacity Coefficient 4
0.490644802367817, !- Sensible Cooling Capacity Coefficient 5
0.0693119353468141, !- Sensible Cooling Capacity Coefficient 6
-5.67775976415698, !- Cooling Power Consumption Coefficient 1
0.438988156976704, !- Cooling Power Consumption Coefficient 2
5.845277342193, !- Cooling Power Consumption Coefficient 3
0.141605667000125, !- Cooling Power Consumption Coefficient 4
-0.168727936032429, !- Cooling Power Consumption Coefficient 5
0, !- Nominal Time for Condensate Removal to Begin {s}
0; !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
Coil:Cooling:WaterToAirHeatPump:EquationFit,
Heat Pump Cooling Mode AirLoop DataCenter bot, !- Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side1 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side1 Outlet Node, !- Water Outlet Node Name
AirLoop DataCenter bot Supply Fan Outlet, !- Air Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter bot, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Cooling Capacity {W}
4.005260634, !- Gross Rated Cooling COP
-4.30266987344639, !- Total Cooling Capacity Coefficient 1
7.18536990534372, !- Total Cooling Capacity Coefficient 2
-2.23946714486189, !- Total Cooling Capacity Coefficient 3
0.139995928440879, !- Total Cooling Capacity Coefficient 4
0.102660179888915, !- Total Cooling Capacity Coefficient 5
6.0019444814887, !- Sensible Cooling Capacity Coefficient 1
22.6300677244073, !- Sensible Cooling Capacity Coefficient 2
-26.7960783730934, !- Sensible Cooling Capacity Coefficient 3
-1.72374720346819, !- Sensible Cooling Capacity Coefficient 4
0.490644802367817, !- Sensible Cooling Capacity Coefficient 5
0.0693119353468141, !- Sensible Cooling Capacity Coefficient 6
-5.67775976415698, !- Cooling Power Consumption Coefficient 1
0.438988156976704, !- Cooling Power Consumption Coefficient 2
5.845277342193, !- Cooling Power Consumption Coefficient 3
0.141605667000125, !- Cooling Power Consumption Coefficient 4
-0.168727936032429, !- Cooling Power Consumption Coefficient 5
0, !- Nominal Time for Condensate Removal to Begin {s}
0; !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
Coil:Cooling:WaterToAirHeatPump:EquationFit,
Heat Pump Cooling Mode AirLoop DataCenter mid, !- Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side1 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side1 Outlet Node, !- Water Outlet Node Name
AirLoop DataCenter mid Supply Fan Outlet, !- Air Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter mid, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Cooling Capacity {W}
4.005260634, !- Gross Rated Cooling COP
-4.30266987344639, !- Total Cooling Capacity Coefficient 1
7.18536990534372, !- Total Cooling Capacity Coefficient 2
-2.23946714486189, !- Total Cooling Capacity Coefficient 3
0.139995928440879, !- Total Cooling Capacity Coefficient 4
0.102660179888915, !- Total Cooling Capacity Coefficient 5
6.0019444814887, !- Sensible Cooling Capacity Coefficient 1
22.6300677244073, !- Sensible Cooling Capacity Coefficient 2
-26.7960783730934, !- Sensible Cooling Capacity Coefficient 3
-1.72374720346819, !- Sensible Cooling Capacity Coefficient 4
0.490644802367817, !- Sensible Cooling Capacity Coefficient 5
0.0693119353468141, !- Sensible Cooling Capacity Coefficient 6
-5.67775976415698, !- Cooling Power Consumption Coefficient 1
0.438988156976704, !- Cooling Power Consumption Coefficient 2
5.845277342193, !- Cooling Power Consumption Coefficient 3
0.141605667000125, !- Cooling Power Consumption Coefficient 4
-0.168727936032429, !- Cooling Power Consumption Coefficient 5
0, !- Nominal Time for Condensate Removal to Begin {s}
0; !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
Coil:Cooling:WaterToAirHeatPump:EquationFit,
Heat Pump Cooling Mode AirLoop DataCenter top, !- Name
AirLoop DataCenter top Water to Air Heat Pump Source Side1 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter top Water to Air Heat Pump Source Side1 Outlet Node, !- Water Outlet Node Name
AirLoop DataCenter top Supply Fan Outlet, !- Air Inlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter top, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Cooling Capacity {W}
4.005260634, !- Gross Rated Cooling COP
-4.30266987344639, !- Total Cooling Capacity Coefficient 1
7.18536990534372, !- Total Cooling Capacity Coefficient 2
-2.23946714486189, !- Total Cooling Capacity Coefficient 3
0.139995928440879, !- Total Cooling Capacity Coefficient 4
0.102660179888915, !- Total Cooling Capacity Coefficient 5
6.0019444814887, !- Sensible Cooling Capacity Coefficient 1
22.6300677244073, !- Sensible Cooling Capacity Coefficient 2
-26.7960783730934, !- Sensible Cooling Capacity Coefficient 3
-1.72374720346819, !- Sensible Cooling Capacity Coefficient 4
0.490644802367817, !- Sensible Cooling Capacity Coefficient 5
0.0693119353468141, !- Sensible Cooling Capacity Coefficient 6
-5.67775976415698, !- Cooling Power Consumption Coefficient 1
0.438988156976704, !- Cooling Power Consumption Coefficient 2
5.845277342193, !- Cooling Power Consumption Coefficient 3
0.141605667000125, !- Cooling Power Consumption Coefficient 4
-0.168727936032429, !- Cooling Power Consumption Coefficient 5
0, !- Nominal Time for Condensate Removal to Begin {s}
0; !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
!- =========== ALL OBJECTS IN CLASS: COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT ===========
Coil:Heating:WaterToAirHeatPump:EquationFit,
Heat Pump HEATING Mode AirLoop DataCenter Basement, !- Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side2 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter Basement Water to Air Heat Pump Source Side2 Outlet Node, !- Water Outlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter Basement, !- Air Inlet Node Name
Heating Coil Air Outlet Node AirLoop DataCenter Basement, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Heating Capacity {W}
4.2, !- Gross Rated Heating COP
0.237847462869254, !- Heating Capacity Coefficient 1
-3.35823796081626, !- Heating Capacity Coefficient 2
3.80640467406376, !- Heating Capacity Coefficient 3
0.179200417311554, !- Heating Capacity Coefficient 4
0.12860719846082, !- Heating Capacity Coefficient 5
-3.79175529243238, !- Heating Power Consumption Coefficient 1
3.38799239505527, !- Heating Power Consumption Coefficient 2
1.5022612076303, !- Heating Power Consumption Coefficient 3
-0.177653510577989, !- Heating Power Consumption Coefficient 4
-0.103079864171839; !- Heating Power Consumption Coefficient 5
Coil:Heating:WaterToAirHeatPump:EquationFit,
Heat Pump HEATING Mode AirLoop DataCenter bot, !- Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side2 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter bot Water to Air Heat Pump Source Side2 Outlet Node, !- Water Outlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter bot, !- Air Inlet Node Name
Heating Coil Air Outlet Node AirLoop DataCenter bot, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Heating Capacity {W}
4.2, !- Gross Rated Heating COP
0.237847462869254, !- Heating Capacity Coefficient 1
-3.35823796081626, !- Heating Capacity Coefficient 2
3.80640467406376, !- Heating Capacity Coefficient 3
0.179200417311554, !- Heating Capacity Coefficient 4
0.12860719846082, !- Heating Capacity Coefficient 5
-3.79175529243238, !- Heating Power Consumption Coefficient 1
3.38799239505527, !- Heating Power Consumption Coefficient 2
1.5022612076303, !- Heating Power Consumption Coefficient 3
-0.177653510577989, !- Heating Power Consumption Coefficient 4
-0.103079864171839; !- Heating Power Consumption Coefficient 5
Coil:Heating:WaterToAirHeatPump:EquationFit,
Heat Pump HEATING Mode AirLoop DataCenter mid, !- Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side2 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter mid Water to Air Heat Pump Source Side2 Outlet Node, !- Water Outlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter mid, !- Air Inlet Node Name
Heating Coil Air Outlet Node AirLoop DataCenter mid, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Heating Capacity {W}
4.2, !- Gross Rated Heating COP
0.237847462869254, !- Heating Capacity Coefficient 1
-3.35823796081626, !- Heating Capacity Coefficient 2
3.80640467406376, !- Heating Capacity Coefficient 3
0.179200417311554, !- Heating Capacity Coefficient 4
0.12860719846082, !- Heating Capacity Coefficient 5
-3.79175529243238, !- Heating Power Consumption Coefficient 1
3.38799239505527, !- Heating Power Consumption Coefficient 2
1.5022612076303, !- Heating Power Consumption Coefficient 3
-0.177653510577989, !- Heating Power Consumption Coefficient 4
-0.103079864171839; !- Heating Power Consumption Coefficient 5
Coil:Heating:WaterToAirHeatPump:EquationFit,
Heat Pump HEATING Mode AirLoop DataCenter top, !- Name
AirLoop DataCenter top Water to Air Heat Pump Source Side2 Inlet Node, !- Water Inlet Node Name
AirLoop DataCenter top Water to Air Heat Pump Source Side2 Outlet Node, !- Water Outlet Node Name
Cooling Coil Air Outlet Node AirLoop DataCenter top, !- Air Inlet Node Name
Heating Coil Air Outlet Node AirLoop DataCenter top, !- Air Outlet Node Name
autosize, !- Rated Air Flow Rate {m3/s}
autosize, !- Rated Water Flow Rate {m3/s}
autosize, !- Gross Rated Heating Capacity {W}
4.2, !- Gross Rated Heating COP
0.237847462869254, !- Heating Capacity Coefficient 1
-3.35823796081626, !- Heating Capacity Coefficient 2
3.80640467406376, !- Heating Capacity Coefficient 3
0.179200417311554, !- Heating Capacity Coefficient 4
0.12860719846082, !- Heating Capacity Coefficient 5
-3.79175529243238, !- Heating Power Consumption Coefficient 1
3.38799239505527, !- Heating Power Consumption Coefficient 2
1.5022612076303, !- Heating Power Consumption Coefficient 3
-0.177653510577989, !- Heating Power Consumption Coefficient 4
-0.103079864171839; !- Heating Power Consumption Coefficient 5
!- =========== ALL OBJECTS IN CLASS: HUMIDIFIER:STEAM:ELECTRIC ===========
Humidifier:Steam:Electric,
DataCenter Basement Humidifier, !- Name
ALWAYS_ON, !- Availability Schedule Name
3.72E-5, !- Rated Capacity {m3/s}
100000, !- Rated Power {W}
0, !- Rated Fan Power {W}
0, !- Standby Power {W}
AirLoop DataCenter Basement Humidifier Inlet, !- Air Inlet Node Name
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: AIRLOOPHVAC:UNITARYHEATPUMP:WATERTOAIR ===========
AirLoopHVAC:UnitaryHeatPump:WaterToAir,
AirLoop DataCenter Basement DXAC Heat Pump, !- Name
Always_On, !- Availability Schedule Name
DataCenter Basement Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter Basement Humidifier Inlet, !- Air Outlet Node Name
autosize, !- Supply Air Flow Rate {m3/s}
DataCenter_basement_ZN_6,!- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Air Fan Object Type
DataCenter Basement Supply Fan, !- Supply Air Fan Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Heating Coil Object Type
Heat Pump HEATING Mode AirLoop DataCenter Basement, !- Heating Coil Name
0.001, !- Heating Convergence
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Cooling Coil Object Type
Heat Pump Cooling Mode AirLoop DataCenter Basement, !- Cooling Coil Name
0.001, !- Cooling Convergence
2.5, !- Maximum Cycling Rate {cycles/hr}
60, !- Heat Pump Time Constant {s}
0.01, !- Fraction of On-Cycle Power Use
60, !- Heat Pump Fan Delay Time {s}
Coil:Heating:Electric, !- Supplemental Heating Coil Object Type
Heat Pump DX Supp Heating Coil AirLoop DataCenter Basement, !- Supplemental Heating Coil Name
50, !- Maximum Supply Air Temperature from Supplemental Heater {C}
, !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C}
Common OSA Inlet Node, !- Outdoor Dry-Bulb Temperature Sensor Node Name
BlowThrough, !- Fan Placement
SupplyFanSch; !- Supply Air Fan Operating Mode Schedule Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir,
AirLoop DataCenter bot DXAC Heat Pump, !- Name
Always_On, !- Availability Schedule Name
DataCenter bot Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter bot Supply Air Outlet, !- Air Outlet Node Name
autosize, !- Supply Air Flow Rate {m3/s}
DataCenter_bot_ZN_6, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Air Fan Object Type
DataCenter bot Supply Fan, !- Supply Air Fan Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Heating Coil Object Type
Heat Pump HEATING Mode AirLoop DataCenter bot, !- Heating Coil Name
0.001, !- Heating Convergence
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Cooling Coil Object Type
Heat Pump Cooling Mode AirLoop DataCenter bot, !- Cooling Coil Name
0.001, !- Cooling Convergence
2.5, !- Maximum Cycling Rate {cycles/hr}
60, !- Heat Pump Time Constant {s}
0.01, !- Fraction of On-Cycle Power Use
60, !- Heat Pump Fan Delay Time {s}
Coil:Heating:Electric, !- Supplemental Heating Coil Object Type
Heat Pump DX Supp Heating Coil AirLoop DataCenter bot, !- Supplemental Heating Coil Name
50, !- Maximum Supply Air Temperature from Supplemental Heater {C}
, !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C}
Common OSA Inlet Node, !- Outdoor Dry-Bulb Temperature Sensor Node Name
BlowThrough, !- Fan Placement
SupplyFanSch; !- Supply Air Fan Operating Mode Schedule Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir,
AirLoop DataCenter mid DXAC Heat Pump, !- Name
Always_On, !- Availability Schedule Name
DataCenter mid Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter mid Supply Air Outlet, !- Air Outlet Node Name
autosize, !- Supply Air Flow Rate {m3/s}
DataCenter_mid_ZN_6, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Air Fan Object Type
DataCenter mid Supply Fan, !- Supply Air Fan Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Heating Coil Object Type
Heat Pump HEATING Mode AirLoop DataCenter mid, !- Heating Coil Name
0.001, !- Heating Convergence
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Cooling Coil Object Type
Heat Pump Cooling Mode AirLoop DataCenter mid, !- Cooling Coil Name
0.001, !- Cooling Convergence
2.5, !- Maximum Cycling Rate {cycles/hr}
60, !- Heat Pump Time Constant {s}
0.01, !- Fraction of On-Cycle Power Use
60, !- Heat Pump Fan Delay Time {s}
Coil:Heating:Electric, !- Supplemental Heating Coil Object Type
Heat Pump DX Supp Heating Coil AirLoop DataCenter mid, !- Supplemental Heating Coil Name
50, !- Maximum Supply Air Temperature from Supplemental Heater {C}
, !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C}
Common OSA Inlet Node, !- Outdoor Dry-Bulb Temperature Sensor Node Name
BlowThrough, !- Fan Placement
SupplyFanSch; !- Supply Air Fan Operating Mode Schedule Name
AirLoopHVAC:UnitaryHeatPump:WaterToAir,
AirLoop DataCenter top DXAC Heat Pump, !- Name
Always_On, !- Availability Schedule Name
DataCenter top Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter top Supply Air Outlet, !- Air Outlet Node Name
autosize, !- Supply Air Flow Rate {m3/s}
DataCenter_top_ZN_6, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Air Fan Object Type
DataCenter top Supply Fan, !- Supply Air Fan Name
Coil:Heating:WaterToAirHeatPump:EquationFit, !- Heating Coil Object Type
Heat Pump HEATING Mode AirLoop DataCenter top, !- Heating Coil Name
0.001, !- Heating Convergence
Coil:Cooling:WaterToAirHeatPump:EquationFit, !- Cooling Coil Object Type
Heat Pump Cooling Mode AirLoop DataCenter top, !- Cooling Coil Name
0.001, !- Cooling Convergence
2.5, !- Maximum Cycling Rate {cycles/hr}
60, !- Heat Pump Time Constant {s}
0.01, !- Fraction of On-Cycle Power Use
60, !- Heat Pump Fan Delay Time {s}
Coil:Heating:Electric, !- Supplemental Heating Coil Object Type
Heat Pump DX Supp Heating Coil AirLoop DataCenter top, !- Supplemental Heating Coil Name
50, !- Maximum Supply Air Temperature from Supplemental Heater {C}
, !- Maximum Outdoor Dry-Bulb Temperature for Supplemental Heater Operation {C}
Common OSA Inlet Node, !- Outdoor Dry-Bulb Temperature Sensor Node Name
BlowThrough, !- Fan Placement
SupplyFanSch; !- Supply Air Fan Operating Mode Schedule Name
!- =========== ALL OBJECTS IN CLASS: FAN:CONSTANTVOLUME ===========
Fan:ConstantVolume,
CAV_bas Fan, !- Name
HVACOperationSchd, !- Availability Schedule Name
0.6006, !- Fan Total Efficiency
1018.41, !- Pressure Rise {Pa}
AUTOSIZE, !- Maximum Flow Rate {m3/s}
0.924, !- Motor Efficiency
1.0, !- Motor In Airstream Fraction
CAV_bas_HeatC-CAV_FanNode, !- Air Inlet Node Name
CAV_bas Supply Equipment Outlet Node; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: FAN:SIMPLE:VARIABLEVOLUME ===========
Fan:VariableVolume,
VAV_bot WITH REHEAT Fan, !- Name
HVACOperationSchd, !- Availability Schedule Name
0.6084, !- Fan Total Efficiency
1389.42, !- Pressure Rise {Pa}
AUTOSIZE, !- Maximum Flow Rate {m3/s}
Fraction, !- Fan Power Minimum Flow Rate Input Method
0.25, !- Fan Power Minimum Flow Fraction
, !- Fan Power Minimum Air Flow Rate {m3/s}
0.936, !- Motor Efficiency
1.0, !- Motor In Airstream Fraction
0.0408, !- Fan Power Coefficient 1
0.088, !- Fan Power Coefficient 2
-0.0729, !- Fan Power Coefficient 3
0.9437, !- Fan Power Coefficient 4
0, !- Fan Power Coefficient 5
VAV_bot WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Inlet Node Name
VAV_bot WITH REHEAT Supply Equipment Outlet Node; !- Air Outlet Node Name
Fan:VariableVolume,
VAV_mid WITH REHEAT Fan, !- Name
HVACOperationSchd, !- Availability Schedule Name
0.6084, !- Fan Total Efficiency
1389.42, !- Pressure Rise {Pa}
AUTOSIZE, !- Maximum Flow Rate {m3/s}
Fraction, !- Fan Power Minimum Flow Rate Input Method
0.25, !- Fan Power Minimum Flow Fraction
, !- Fan Power Minimum Air Flow Rate {m3/s}
0.936, !- Motor Efficiency
1.0, !- Motor In Airstream Fraction
0.0408, !- Fan Power Coefficient 1
0.088, !- Fan Power Coefficient 2
-0.0729, !- Fan Power Coefficient 3
0.9437, !- Fan Power Coefficient 4
0, !- Fan Power Coefficient 5
VAV_mid WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Inlet Node Name
VAV_mid WITH REHEAT Supply Equipment Outlet Node; !- Air Outlet Node Name
Fan:VariableVolume,
VAV_top WITH REHEAT Fan, !- Name
HVACOperationSchd, !- Availability Schedule Name
0.6084, !- Fan Total Efficiency
1389.42, !- Pressure Rise {Pa}
AUTOSIZE, !- Maximum Flow Rate {m3/s}
Fraction, !- Fan Power Minimum Flow Rate Input Method
0.25, !- Fan Power Minimum Flow Fraction
, !- Fan Power Minimum Air Flow Rate {m3/s}
0.936, !- Motor Efficiency
1.0, !- Motor In Airstream Fraction
0.0408, !- Fan Power Coefficient 1
0.088, !- Fan Power Coefficient 2
-0.0729, !- Fan Power Coefficient 3
0.9437, !- Fan Power Coefficient 4
0, !- Fan Power Coefficient 5
VAV_top WITH REHEAT_HeatC-VAV WITH REHEAT FanNode, !- Air Inlet Node Name
VAV_top WITH REHEAT Supply Equipment Outlet Node; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: FAN:ONOFF ===========
Fan:OnOff,
DataCenter Basement Supply Fan, !- Name
Always_On, !- Availability Schedule Name
0.6175, !- Fan Total Efficiency
1018.41, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.95, !- Motor Efficiency
1, !- Motor In Airstream Fraction
DataCenter Basement Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter Basement Supply Fan Outlet; !- Air Outlet Node Name
Fan:OnOff,
DataCenter bot Supply Fan, !- Name
Always_On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
DataCenter bot Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter bot Supply Fan Outlet; !- Air Outlet Node Name
Fan:OnOff,
DataCenter mid Supply Fan, !- Name
Always_On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
DataCenter mid Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter mid Supply Fan Outlet; !- Air Outlet Node Name
Fan:OnOff,
DataCenter top Supply Fan, !- Name
Always_On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
DataCenter top Mixed Air Outlet, !- Air Inlet Node Name
AirLoop DataCenter top Supply Fan Outlet; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: FLUIDPROPERTIES:GLYCOLCONCENTRATIONS ===========
FluidProperties:GlycolConcentration,
EthyleneGlycol40Percent, !- Name
EthyleneGlycol, !- Glycol Type
, !- User Defined Glycol Name
0.4; !- Glycol Concentration
HeatExchanger:AirToAir:SensibleAndLatent,
VAV_bot WITH REHEAT OA Heat Recovery, !- Name
Always_On, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.70, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.70, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
VAV_bot WITH REHEAT_OAInlet Node, !- Supply Air Inlet Node Name
VAV_bot WITH REHEAT Heat Recovery Outlet Node, !- Supply Air Outlet Node Name
VAV_bot WITH REHEAT_OARelief Node, !- Exhaust Air Inlet Node Name
VAV_bot WITH REHEAT Heat Recovery Secondary Outlet Node, !- Exhaust Air Outlet Node Name
1506.812, !- Nominal Electric Power {W}
Yes, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
HeatExchanger:AirToAir:SensibleAndLatent,
VAV_mid WITH REHEAT OA Heat Recovery, !- Name
Always_On, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.70, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.70, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
VAV_mid WITH REHEAT_OAInlet Node, !- Supply Air Inlet Node Name
VAV_mid WITH REHEAT Heat Recovery Outlet Node, !- Supply Air Outlet Node Name
VAV_mid WITH REHEAT_OARelief Node, !- Exhaust Air Inlet Node Name
VAV_mid WITH REHEAT Heat Recovery Secondary Outlet Node, !- Exhaust Air Outlet Node Name
1506.812, !- Nominal Electric Power {W}
Yes, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
HeatExchanger:AirToAir:SensibleAndLatent,
VAV_top WITH REHEAT OA Heat Recovery, !- Name
Always_On, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.70, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.70, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.75, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0.60, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
VAV_top WITH REHEAT_OAInlet Node, !- Supply Air Inlet Node Name
VAV_top WITH REHEAT Heat Recovery Outlet Node, !- Supply Air Outlet Node Name
VAV_top WITH REHEAT_OARelief Node, !- Exhaust Air Inlet Node Name
VAV_top WITH REHEAT Heat Recovery Secondary Outlet Node, !- Exhaust Air Outlet Node Name
1506.812, !- Nominal Electric Power {W}
Yes, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Curve:Cubic,
Tower_Fan_Curve, !- Name
0, !- Coefficient1 Constant
0, !- Coefficient2 x
0, !- Coefficient3 x**2
1, !- Coefficient4 x**3
0.0, !- Minimum Value of x
1.0; !- Maximum Value of x
!- =========== ALL OBJECTS IN CLASS: WATER USE EQUIPMENT ===========
WaterUse:Equipment,
Core_bottom sub cat, !- Name
WaterUse, !- End-Use Subcategory
3.66667e-05, !- Peak Flow Rate {m3/s}
BLDG_SWH_SCH, !- Flow Rate Fraction Schedule Name
Core_bottom sub cat Temp Sched, !- Target Temperature Schedule Name
Core_bottom sub catHot Supply Temp Sched, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
Core_bottom, !- Zone Name
Core_bottom sub cat Sensible fract sched, !- Sensible Fraction Schedule Name
Core_bottom sub cat Latent fract sched; !- Latent Fraction Schedule Name
WaterUse:Equipment,
Core_mid sub cat, !- Name
WaterUse, !- End-Use Subcategory
3.66667e-05, !- Peak Flow Rate {m3/s}
BLDG_SWH_SCH, !- Flow Rate Fraction Schedule Name
Core_mid sub cat Temp Sched, !- Target Temperature Schedule Name
Core_mid sub catHot Supply Temp Sched, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
Core_mid, !- Zone Name
Core_mid sub cat Sensible fract sched, !- Sensible Fraction Schedule Name
Core_mid sub cat Latent fract sched; !- Latent Fraction Schedule Name
WaterUse:Equipment,
Core_top sub cat, !- Name
WaterUse, !- End-Use Subcategory
3.66667e-05, !- Peak Flow Rate {m3/s}
BLDG_SWH_SCH, !- Flow Rate Fraction Schedule Name
Core_top sub cat Temp Sched, !- Target Temperature Schedule Name
Core_top sub catHot Supply Temp Sched, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
Core_top, !- Zone Name
Core_top sub cat Sensible fract sched, !- Sensible Fraction Schedule Name
Core_top sub cat Latent fract sched; !- Latent Fraction Schedule Name
!- =========== ALL OBJECTS IN CLASS: WATER USE CONNECTIONS ===========
WaterUse:Connections,
Core_bottom sub cat, !- Name
Core_bottom sub cat Water Inlet Node, !- Inlet Node Name
Core_bottom sub cat Water Outlet Node, !- Outlet Node Name
, !- Supply Water Storage Tank Name
, !- Reclamation Water Storage Tank Name
, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
, !- Drain Water Heat Exchanger Type
, !- Drain Water Heat Exchanger Destination
, !- Drain Water Heat Exchanger U-Factor Times Area {W/K}
Core_bottom sub cat; !- Water Use Equipment 1 Name
WaterUse:Connections,
Core_mid sub cat, !- Name
Core_mid sub cat Water Inlet Node, !- Inlet Node Name
Core_mid sub cat Water Outlet Node, !- Outlet Node Name
, !- Supply Water Storage Tank Name
, !- Reclamation Water Storage Tank Name
, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
, !- Drain Water Heat Exchanger Type
, !- Drain Water Heat Exchanger Destination
, !- Drain Water Heat Exchanger U-Factor Times Area {W/K}
Core_mid sub cat; !- Water Use Equipment 1 Name
WaterUse:Connections,
Core_top sub cat, !- Name
Core_top sub cat Water Inlet Node, !- Inlet Node Name
Core_top sub cat Water Outlet Node, !- Outlet Node Name
, !- Supply Water Storage Tank Name
, !- Reclamation Water Storage Tank Name
, !- Hot Water Supply Temperature Schedule Name
, !- Cold Water Supply Temperature Schedule Name
, !- Drain Water Heat Exchanger Type
, !- Drain Water Heat Exchanger Destination
, !- Drain Water Heat Exchanger U-Factor Times Area {W/K}
Core_top sub cat; !- Water Use Equipment 1 Name
!No PV for this case
EnergyManagementSystem:Sensor,
T_OA, !- Name
, !- Output:Variable or Output:Meter Index Key Name
Site Outdoor Air Drybulb Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_FanMassFlow, !- Name
AirLoop DataCenter Basement Supply Fan Outlet, !- Output:Variable or Output:Meter Index Key Name
System Node Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_Humidifier_Status, !- Name
DataCenter Basement Humidifier, !- Output:Variable or Output:Meter Index Key Name
Humidifier Water Volume Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_CLG_SP, !- Name
Cooling Coil Air Outlet Node AirLoop DataCenter Basement, !- Output:Variable or Output:Meter Index Key Name
System Node Setpoint Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_HeatC_Status, !- Name
HEAT PUMP HEATING MODE AIRLOOP DATACENTER BASEMENT, !- Output:Variable or Output:Meter Index Key Name
Heating Coil Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_AfterHumidifier_Temp, !- Name
DataCenter_Humidifier-DataCenter_ExtraElecHeatCNode, !- Output:Variable or Output:Meter Index Key Name
System Node Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
DataCenter_AfterElecHeatC_Temp, !- Name
DataCenter_EXTRAELECHEATC-DataCenter_EXTRAWATERHEATCNODE, !- Output:Variable or Output:Meter Index Key Name
System Node Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_bot_WITH_REHEAT_OA_VRP, !- Name
VAV_bot WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mechanical Ventilation Requested Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_bot_WITH_REHEAT_OA, !- Name
VAV_bot WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_bot_SUPPLY_FLOW, !- Name
VAV_bot WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Output:Variable or Output:Meter Index Key Name
System Node Standard Density Volume Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_mid_WITH_REHEAT_OA_VRP, !- Name
VAV_mid WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mechanical Ventilation Requested Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_mid_WITH_REHEAT_OA, !- Name
VAV_mid WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_mid_SUPPLY_FLOW, !- Name
VAV_mid WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Output:Variable or Output:Meter Index Key Name
System Node Standard Density Volume Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_top_WITH_REHEAT_OA_VRP, !- Name
VAV_top WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mechanical Ventilation Requested Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_top_WITH_REHEAT_OA, !- Name
VAV_top WITH REHEAT, !- Output:Variable or Output:Meter Index Key Name
Air System Outdoor Air Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
VAV_top_SUPPLY_FLOW, !- Name
VAV_top WITH REHEAT_OA-VAV WITH REHEAT_CoolCNode, !- Output:Variable or Output:Meter Index Key Name
System Node Standard Density Volume Flow Rate; !- Output:Variable or Output:Meter Name
!- =========== ALL OBJECTS IN CLASS: ENERGYMANAGEMENTSYSTEM:ACTUATOR ===========
EnergyManagementSystem:Actuator,
DataCenter_ExtraElecHeatC_SP, !- Name
DataCenter_EXTRAELECHEATC-DataCenter_EXTRAWATERHEATCNODE, !- Actuated Component Unique Name
System Node Setpoint, !- Actuated Component Type
Temperature Setpoint; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
DataCenter_ExtraWaterHeatC_SP, !- Name
AirLoop DataCenter Basement Supply Air Outlet, !- Actuated Component Unique Name
System Node Setpoint, !- Actuated Component Type
Temperature Setpoint; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
DataCenter_ExtraElecHeatC_Status, !- Name
DataCenter_ExtraElecHeatC_Sch, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
DataCenter_ExtraWaterHeatC_Status, !- Name
DataCenter_ExtraWaterHeatC_Sch, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
VAV_bot_WITH_REHEAT_MAX_OA_FRAC, !- Name
VAV_bot WITH REHEAT Max OA Fraction, !- Actuated Component Unique Name
Schedule:Constant, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
VAV_mid_WITH_REHEAT_MAX_OA_FRAC, !- Name
VAV_mid WITH REHEAT Max OA Fraction, !- Actuated Component Unique Name
Schedule:Constant, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
VAV_top_WITH_REHEAT_MAX_OA_FRAC, !- Name
VAV_top WITH REHEAT Max OA Fraction, !- Actuated Component Unique Name
Schedule:Constant, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
!- =========== ALL OBJECTS IN CLASS: ENERGYMANAGEMENTSYSTEM:PROGRAMCALLINGMANAGER ===========
EnergyManagementSystem:ProgramCallingManager,
DataCenter_Main_Manager, !- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
DataCenter_Main; !- Program Name 1
EnergyManagementSystem:Program,
DataCenter_Main, !- Name
IF DataCenter_Humidifier_Status > 0, !- Program Line 1
SET DataCenter_ExtraElecHeatC_Status = 0, !- Program Line 2
SET DataCenter_ExtraElecHeatC_SP = DataCenter_AfterHumidifier_Temp + 0.36, !- <none>
SET DataCenter_ExtraWaterHeatC_SP = DataCenter_CLG_SP, !- <none>
ELSE, !- <none>
SET DataCenter_ExtraElecHeatC_Status = 0, !- <none>
SET DataCenter_ExtraElecHeatC_SP = NULL, !- <none>
ENDIF, !- <none>
IF T_OA < 10 && DataCenter_HeatC_Status >0, !- <none>
SET HeatGain = 0 * (DataCenter_FanDesignMass/1.2) *2118, !- <none>
SET FlowRate = (DataCenter_FanMassFlow/1.2)*2118, !- <none>
SET DataCenter_PreheatDeltaT = HeatGain/(1.08*FlowRate), !- <none>
SET DataCenter_ExtraWaterHeatC_Status = 1, !- <none>
SET DataCenter_ExtraWaterHeatC_SP = DataCenter_AfterElecHeatC_Temp + DataCenter_PreheatDeltaT, !- <none>
ELSE, !- <none>
SET DataCenter_ExtraWaterHeatC_Status = 0, !- <none>
ENDIF; !- <none>
EnergyManagementSystem:ProgramCallingManager,
VAV_bot_WITH_REHEAT_MAX_OA_FRAC_Prog_Manager,!- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
VAV_bot_WITH_REHEAT_MAX_OA_FRAC; !- Program Name 1
EnergyManagementSystem:Program,
VAV_bot_WITH_REHEAT_MAX_OA_FRAC, !- Name
IF VAV_bot_WITH_REHEAT_OA > VAV_bot_WITH_REHEAT_OA_VRP, !- Program Line 1
SET VAV_bot_WITH_REHEAT_MAX_OA_FRAC = NULL, !- Program Line 2
ELSE, !- A4
IF VAV_bot_SUPPLY_FLOW > 0, !- A5
SET VAV_bot_WITH_REHEAT_MAX_OA_FRAC = 2.0304 / VAV_bot_SUPPLY_FLOW,!- A6
ELSE, !- A7
SET VAV_bot_WITH_REHEAT_MAX_OA_FRAC = NULL, !- A8
ENDIF, !- A9
ENDIF; !- A10
EnergyManagementSystem:ProgramCallingManager,
VAV_mid_WITH_REHEAT_MAX_OA_FRAC_Prog_Manager,!- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
VAV_mid_WITH_REHEAT_MAX_OA_FRAC; !- Program Name 1
EnergyManagementSystem:Program,
VAV_mid_WITH_REHEAT_MAX_OA_FRAC, !- Name
IF VAV_mid_WITH_REHEAT_OA > VAV_mid_WITH_REHEAT_OA_VRP, !- Program Line 1
SET VAV_mid_WITH_REHEAT_MAX_OA_FRAC = NULL, !- Program Line 2
ELSE, !- A4
IF VAV_mid_SUPPLY_FLOW > 0, !- A5
SET VAV_mid_WITH_REHEAT_MAX_OA_FRAC = 20.304 / VAV_mid_SUPPLY_FLOW,!- A6
ELSE, !- A7
SET VAV_mid_WITH_REHEAT_MAX_OA_FRAC = NULL, !- A8
ENDIF, !- A9
ENDIF; !- A10
EnergyManagementSystem:ProgramCallingManager,
VAV_top_WITH_REHEAT_MAX_OA_FRAC_Prog_Manager,!- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
VAV_top_WITH_REHEAT_MAX_OA_FRAC; !- Program Name 1
EnergyManagementSystem:Program,
VAV_top_WITH_REHEAT_MAX_OA_FRAC, !- Name
IF VAV_top_WITH_REHEAT_OA > VAV_top_WITH_REHEAT_OA_VRP, !- Program Line 1
SET VAV_top_WITH_REHEAT_MAX_OA_FRAC = NULL, !- Program Line 2
ELSE, !- A4
IF VAV_top_SUPPLY_FLOW > 0, !- A5
SET VAV_top_WITH_REHEAT_MAX_OA_FRAC = 2.0304 / VAV_top_SUPPLY_FLOW,!- A6
ELSE, !- A7
SET VAV_top_WITH_REHEAT_MAX_OA_FRAC = NULL, !- A8
ENDIF, !- A9
ENDIF; !- A10
EnergyManagementSystem:GlobalVariable,
DataCenter_PreheatDeltaT;!- Erl Variable 1 Name
EnergyManagementSystem:OutputVariable,
DataCenter_ExtraElecHeatC_Status, !- Name
DataCenter_ExtraElecHeatC_Status, !- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
; !- Units
EnergyManagementSystem:OutputVariable,
DataCenter_ExtraWaterHeatC_Status, !- Name
DataCenter_ExtraWaterHeatC_Status, !- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
; !- Units
EnergyManagementSystem:OutputVariable,
DataCenter_ExtraElecHeatC_SP, !- Name
DataCenter_ExtraElecHeatC_SP, !- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
; !- Units
EnergyManagementSystem:OutputVariable,
DataCenter_ExtraWaterHeatC_SP, !- Name
DataCenter_ExtraWaterHeatC_SP, !- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
; !- Units
EnergyManagementSystem:OutputVariable,
DataCenter_PreheatDeltaT,!- Name
DataCenter_PreheatDeltaT,!- EMS Variable Name
Averaged, !- Type of Data in Variable
SystemTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
; !- Units
!- =========== ALL OBJECTS IN CLASS: ENERGYMANAGEMENTSYSTEM:INTERNALVARIABLE ===========
EnergyManagementSystem:InternalVariable,
DataCenter_FanDesignMass,!- Name
DataCenter Basement Supply Fan, !- Internal Data Index Key Name
Fan Maximum Mass Flow Rate; !- Internal Data Type
!- =========== ALL OBJECTS IN CLASS: REPORT VARIABLE ===========
! Output:Variable,*,Site Outdoor Air Drybulb Temperature,Hourly;
! Output:Variable,*,Site Outdoor Air Wetbulb Temperature,Hourly;
! Output:Variable,*,Heating Coil Heating Energy,hourly; !- HVAC Sum J ! the total amount of heat transfer taking place in the coil
! Output:Variable,*,Cooling Coil Total Cooling Energy,hourly; !- HVAC Sum J ! Energy removed from air loop by Cooling Coils. total amount of heat transfer taking place in the coil
! Output:Variable,*,Pump Mass Flow Rate,hourly; !- HVAC Average ! the water outlet mass flow rate
! Output:Variable,*,Fan Air Mass Flow Rate,hourly; !- HVAC Average ! the amount of outdoor air entering the zone
! Output:Variable,*,Air System Outdoor Air Mass Flow Rate,hourly; !- HVAC Average ! average outdoor air mass flow rate introduced by the outdoor air controller
! Output:Variable,*,Boiler Heating Energy,hourly; !- HVAC Sum J ! the heating output (load) of the boiler
! Output:Variable,*,Chiller Evaporator Cooling Energy,hourly; !- HVAC Sum J ! the evaporator heat transfer which is the cooling delivered by the chiller
!! Heating coils named as XXX_EXTRAWATERHEATC are dummy heating coils to capture heat transfer from the preheating coil to the bypass air when the air handling units are in the cooling mode.
!! Heating coils named as XXX_ EXTRAELECHEATC are dummy heating coils to capture heat transfer from the electric steam humidifier airstream in the air handling units.
!! The modeling strategy is documented in Section 5.2.2.8 Addendum 90.1-2010as Humidification System Requirements in the “ANSI/ASHRAE/IES Standard 90.1-2013 Determination of Energy Savings: Quantitative Analysis" report.
!! Additional output variables that can be useful to review the mechancial equipment load profiles
! Output:Variable,MinOA_MotorizedDamper_Sched,Schedule Value,Hourly;
! Output:Variable,SHWSys1,Plant Supply Side Heating Demand Rate,Hourly;
! Output:Variable,VAV_bot WITH REHEAT SUPPLY EQUIPMENT OUTLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_mid WITH REHEAT SUPPLY EQUIPMENT OUTLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_top WITH REHEAT SUPPLY EQUIPMENT OUTLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_bot WITH REHEAT_OAINLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_mid WITH REHEAT_OAINLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_top WITH REHEAT_OAINLET NODE,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_bot WITH REHEAT Supply Equipment Outlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_mid WITH REHEAT Supply Equipment Outlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_top WITH REHEAT Supply Equipment Outlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_bot WITH REHEAT Supply Equipment Outlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,VAV_mid WITH REHEAT Supply Equipment Outlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,VAV_top WITH REHEAT Supply Equipment Outlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,*,Boiler Heating Rate,Hourly;
! Output:Variable,*,Chiller Evaporator Cooling Rate,Hourly;
! Output:Variable,*,Air System Cooling Coil Total Cooling Energy,Hourly;
! Output:Variable,*,Air System Heating Coil Total Heating Energy,Hourly;
! Output:Variable,VAV_bot WITH REHEAT Supply Equipment Inlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_mid WITH REHEAT Supply Equipment Inlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_top WITH REHEAT Supply Equipment Inlet Node,System Node Temperature,Hourly;
! Output:Variable,VAV_bot WITH REHEAT Supply Equipment Inlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,VAV_mid WITH REHEAT Supply Equipment Inlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,VAV_top WITH REHEAT Supply Equipment Inlet Node,System Node Wetbulb Temperature,Hourly;
! Output:Variable,VAV_bot WITH REHEAT Supply Equipment Inlet Node,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_mid WITH REHEAT Supply Equipment Inlet Node,System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,VAV_top WITH REHEAT Supply Equipment Inlet Node,System Node Standard Density Volume Flow Rate,Hourly;
! ! Utility and Submeter
!
! Output:Meter,Electricity:Facility,Hourly;
! Output:Meter,Gas:Facility,Hourly;
! Output:Meter,InteriorLights:Electricity,Hourly;
! Output:Meter,ExteriorLights:Electricity,Hourly;
! Output:Meter,InteriorEquipment:Electricity,Hourly;
! Output:Meter,ExteriorEquipment:Electricity,Hourly;
! Output:Meter,Fans:Electricity,Hourly;
! Output:Meter,Pumps:Electricity,Hourly;
! Output:Meter,Heating:Electricity,Hourly;
! Output:Meter,Cooling:Electricity,Hourly;
! Output:Meter,HeatRejection:Electricity,Hourly;
! Output:Meter,Humidifier:Electricity,Hourly;
! Output:Meter,HeatRecovery:Electricity,Hourly;
! Output:Meter,DHW:Electricity,Hourly;
! Output:Meter,Cogeneration:Electricity,Hourly;
! Output:Meter,Refrigeration:Electricity,Hourly;
! Output:Meter,WaterSystems:Electricity,Hourly;
!
! Output:Meter,InteriorLights:Gas,Hourly;
! Output:Meter,ExteriorLights:Gas,Hourly;
! Output:Meter,InteriorEquipment:Gas,Hourly;
! Output:Meter,ExteriorEquipment:Gas,Hourly;
! Output:Meter,Fans:Gas,Hourly;
! Output:Meter,Pumps:Gas,Hourly;
! Output:Meter,Heating:Gas,Hourly;
! Output:Meter,Cooling:Gas,Hourly;
! Output:Meter,HeatRejection:Gas,Hourly;
! Output:Meter,Humidifier:Gas,Hourly;
! Output:Meter,HeatRecovery:Gas,Hourly;
! Output:Meter,DHW:Gas,Hourly;
! Output:Meter,Cogeneration:Gas,Hourly;
! Output:Meter,Refrigeration:Gas,Hourly;
! Output:Meter,WaterSystems:Gas,Hourly;
!- =========== ALL OBJECTS IN CLASS: REPORT ===========
Output:Surfaces:Drawing,DXF;
Output:Surfaces:List,Details;
Output:VariableDictionary,IDF;
Output:Constructions,Constructions;
!- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:STYLE ===========
OutputControl:Table:Style,
CommaAndHTML; !- Column Separator
!- =========== ALL OBJECTS IN CLASS: OUTPUTCONTROL:REPORTINGTOLERANCES ===========
OutputControl:ReportingTolerances,
0.556, !- Tolerance for Time Heating Setpoint Not Met {deltaC}
0.556; !- Tolerance for Time Cooling Setpoint Not Met {deltaC}
!- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:PREDEFINED ===========
Output:Table:SummaryReports,
AllSummaryAndMonthly, !- Report 1 Name
Standard62.1Summary; !- Report 2 Name
!- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:MONTHLY ===========
Output:Meter:MeterFileOnly,InteriorLights:Electricity,Hourly;
Output:Meter:MeterFileOnly,InteriorEquipment:Electricity,Hourly;
Output:Table:Monthly,
NameHolderMonthlySummary TaskPurpose ProgressIndicator, !- Name ProgressIndicator,ForDetermination2019, ...
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeName ASHRAE901, !- Name ASHRAE901, ASHRAE1891, IECC, Title24, ORSC, IGCC, ...
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeYear 2019, !- Name all years for ASHRAE90.1, IECC, ASHRAE189.1
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeAmendment NoneAmend, !- Name StateAmend,EEM, NoneAmend for national or state without amendment
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary PrototypeName OfficeLarge, !- Name 16 Prototypes
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary TaskScope National, !- Name National, State, City
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary State National, !- Name National for national analysis, NewYork, Utah,... for state analysis, or city name for city analysis. Spell out the name of the state without space between words
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary ClimateZone 6A, !- Name 0-8
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary RepresentCity USA_MN_Rochester, !- Name representative city like Honolulu for national, for each state, for city analysis. this is not the city of the weather file. The weather city will be extracted from epw file
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
EnergyManagementSystem:Sensor,
Facility_Int_LTG, !- Name
, !- Output:Variable or Output:Meter Index Key Name
InteriorLights:Electricity; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:GlobalVariable,
Wired_LTG; !- Erl Variable 1 Name
EnergyManagementSystem:Program,
Transformer_Load_Prog, !- Name
SET Wired_LTG = Facility_Int_LTG*0.0281; !- Program Line 1
EnergyManagementSystem:ProgramCallingManager,
Transformer_Load_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
Transformer_Load_Prog; !- Program Name 1
EnergyManagementSystem:OutputVariable,
Wired_LTG, !- Name
Wired_LTG, !- EMS Variable Name
Summed, !- Type of Data in Variable
ZoneTimeStep, !- Update Frequency
, !- EMS Program or Subroutine Name
J; !- Units
Meter:Custom,
Wired_LTG_Electricity, !- Name
Electricity, !- Fuel Type
, !- Key Name 1
Wired_LTG; !- Output Variable or Meter Name 1
Meter:CustomDecrement,
Wired_Int_EQUIP, !- Name
Electricity, !- Fuel Type
InteriorEquipment:Electricity, !- Source Meter Name
, !- Key Name 1
DataCenterPlugLoads:InteriorEquipment:Electricity; !- Output Variable or Meter Name 1
ElectricLoadCenter:Transformer,
Transformer 1, !- Name
Always_On, !- Availability Schedule Name
PowerInFromGrid, !- Transformer Usage
, !- Zone Name
, !- Radiative Fraction
500000, !- Rated Capacity {VA}
3, !- Phase
Aluminum, !- Conductor Material
150, !- Full Load Temperature Rise {C}
0.1, !- Fraction of Eddy Current Losses
NominalEfficiency, !- Performance Input Method
, !- Rated No Load Loss {W}
, !- Rated Load Loss {W}
0.991, !- Nameplate Efficiency
0.35, !- Per Unit Load for Nameplate Efficiency
75, !- Reference Temperature for Nameplate Efficiency {C}
, !- Per Unit Load for Maximum Efficiency
Yes, !- Consider Transformer Loss for Utility Cost
Wired_LTG_Electricity, !- Meter 1 Name
Wired_Int_EQUIP; !- Meter 2 Name
EnergyManagementSystem:Sensor,
Tower_PumpMassFlow, !- Name
TowerWaterSys Supply Inlet Node, !- Output:Variable or Output:Meter Index Key Name
System Node Mass Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Chiller1_Status, !- Name
CoolSys1 Chiller1, !- Output:Variable or Output:Meter Index Key Name
Chiller Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Chiller2_Status, !- Name
CoolSys1 Chiller2, !- Output:Variable or Output:Meter Index Key Name
Chiller Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
SensedCurveInput, !- Name
Tower_Fan_Curve, !- Output:Variable or Output:Meter Index Key Name
Performance Curve Input Variable 1 Value; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
SensedCurveValue, !- Name
Tower_Fan_Curve, !- Output:Variable or Output:Meter Index Key Name
Performance Curve Output Value; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Actuator,
TowerCurveOutput, !- Name
Tower_Fan_Curve, !- Actuated Component Unique Name
Curve, !- Actuated Component Type
Curve Result; !- Actuated Component Control Type
EnergyManagementSystem:Program,
ChangTowerFlow, !- Name
IF Chiller1_Status > 0 && Chiller2_Status == 0 && SensedCurveInput > 0.2, !- Program Line 1
IF (0.5 * SensedCurveInput) > 0.2, !- Program Line 2
SET AirInput = 0.5 * SensedCurveInput, !- <none>
ELSE, !- <none>
SET AirInput = 0.2, !- <none>
ENDIF, !- <none>
SET TowerCurveOutput = 2* (AirInput^3), !- <none>
ELSE, !- <none>
SET TowerCurveOutput = SensedCurveValue, !- <none>
ENDIF; !- <none>
EnergyManagementSystem:ProgramCallingManager,
ChangeTowerFlow_Manager, !- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
ChangTowerFlow; !- Program Name 1
EnergyManagementSystem:GlobalVariable,
BoilerType, !- Erl Variable 1 Name
CapRated, !- Erl Variable 2 Name
EtRated, !- Erl Variable 3 Name
PLRx, !- <none>
Ecx, !- <none>
SkinLossRate; !- <none>
EnergyManagementSystem:Sensor,
BoilerPLR, !- Name
HeatSys1 Boiler, !- Output:Variable or Output:Meter Index Key Name
Boiler Part Load Ratio; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Actuator,
BoilerCurve, !- Name
HEATSYS1 BOILER EFFICIENCY CURVE, !- Actuated Component Unique Name
Curve, !- Actuated Component Type
Curve Result; !- Actuated Component Control Type
EnergyManagementSystem:Program, ! Addendum AM
SetBoilerPar,
SET CapRated = 1953430.325, ! EMS Bolier Nominal Capacity {W}.
SET EtRated = 0.8125, ! EMS Boiler Nominal Thermal Efficiency. overriden by script
SET CapRated = (CapRated *3.412)/1000, !Change from W to MBH
SET SkinLossRate = 0.02,
SET BoilerType = 1,
IF BoilerType == 1,
IF CapRated >10000,
SET PLRx = 0.2,
ELSEIF CapRated >5000,
SET PLRx = 0.25,
ELSEIF CapRated >1000,
SET PLRx = 0.33,
ELSE,
SET BoilerType = 2,
SET PLRx = 0.2,
ENDIF,
ELSE,
SET PLRx = 0.2,
ENDIF,
IF BoilerType == 1,
SET CurveX = 0.975 + 0.305 * PLRx - 0.527 * (PLRx^2) + 0.249 * (PLRx^3),
ELSE,
SET CurveX = 0.907 + 0.320 * PLRx - 0.420 * (PLRx^2) + 0.193 * (PLRx^3),
ENDIF,
SET LoadX = CapRated * PLRx,
SET Etx = CurveX * EtRated,
SET InputEx = LoadX/Etx,
SET SkinEx = CapRated * SkinLossRate,
SET Ecx = (LoadX + SkinEx)/InputEx;
EnergyManagementSystem:Program,
SetBoilerCurve, !- Name
IF BoilerPLR >= PLRx, !- Program Line 1
IF BoilerType == 1, !- Program Line 2
SET BoilerCurve = 0.975 + 0.305*BoilerPLR - 0.527*(BoilerPLR^2) + 0.249*(BoilerPLR^3), !- <none>
ELSE, !- <none>
SET BoilerCurve = 0.907 + 0.320*BoilerPLR - 0.420*(BoilerPLR^2) + 0.193*(BoilerPLR^3), !- <none>
ENDIF, !- <none>
ELSE, !- <none>
IF BoilerPLR == 0, !- <none>
SET BoilerCurve = NULL, !- <none>
ELSE, !- <none>
IF BoilerPLR <0.05, !- <none>
SET BoilerCurve = (0.05/(0.05 + SkinLossRate)) * (Ecx/EtRated), !- <none>
ELSE, !- <none>
SET BoilerCurve = (BoilerPLR/(BoilerPLR + SkinLossRate)) * (Ecx/EtRated), !- <none>
ENDIF, !- <none>
ENDIF, !- <none>
ENDIF; !- <none>
EnergyManagementSystem:ProgramCallingManager,
BoilerParManager, !- Name
BeginNewEnvironment, !- EnergyPlus Model Calling Point
SetBoilerPar; !- Program Name 1
EnergyManagementSystem:ProgramCallingManager,
BoilerCurveManager, !- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
SetBoilerCurve; !- Program Name 1
EnergyManagementSystem:Sensor,
OAT, !- Name
Environment, !- Output:Variable or Output:Meter Index Key Name
Site Outdoor Air Drybulb Temperature; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Actuator,
CLGSETP_SCH_Actuator, !- Name
CLGSETP_SCH_Yes_Optimum, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
CLGSETP_SCH_w_SB_Actuator, !- Name
CLGSETP_SCH_Yes_Optimum_w_SB, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
HTGSETP_SCH_Actuator, !- Name
HTGSETP_SCH_Yes_Optimum, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
HTGSETP_SCH_w_SB_Actuator, !- Name
HTGSETP_SCH_Yes_Optimum_w_SB, !- Actuated Component Unique Name
Schedule:Compact, !- Actuated Component Type
Schedule Value; !- Actuated Component Control Type
EnergyManagementSystem:ProgramCallingManager,
OA_BASED_OPTIMUM_START_EMS_Program Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
OA_BASED_OPTIMUM_START_EMS_Program; !- Program Name 1
EnergyManagementSystem:Program,
OA_BASED_OPTIMUM_START_EMS_Program, !- Name
IF DaylightSavings==0 && DayOfWeek>1 && Hour==4 && OAT<23.9 && OAT>1.7, !- Program Line 1
SET CLGSETP_SCH_Actuator = 26.7, !- Program Line 2
SET HTGSETP_SCH_Actuator = 15.6, !- <none>
SET CLGSETP_SCH_w_SB_Actuator = 26.7, !- <none>
SET HTGSETP_SCH_w_SB_Actuator = 15.6, !- <none>
ELSEIF DaylightSavings==1 && DayOfWeek>1 && Hour==3 && OAT<23.9 && OAT>1.7, !- <none>
SET CLGSETP_SCH_Actuator = 26.7, !- <none>
SET HTGSETP_SCH_Actuator = 15.6, !- <none>
SET CLGSETP_SCH_w_SB_Actuator = 26.7, !- <none>
SET HTGSETP_SCH_w_SB_Actuator = 15.6, !- <none>
ELSE, !- <none>
SET CLGSETP_SCH_Actuator = NULL, !- <none>
SET HTGSETP_SCH_Actuator = NULL, !- <none>
SET CLGSETP_SCH_w_SB_Actuator = NULL, !- <none>
SET HTGSETP_SCH_w_SB_Actuator = NULL, !- <none>
ENDIF; !- <none>
EnergyManagementSystem:InternalVariable,
Chiller2PumpDesignFlow, !- Name
COOLSYS1 CHILLER2 PUMP, !- Internal Data Index Key Name
Pump Maximum Mass Flow Rate; !- Internal Data Type
EnergyManagementSystem:Actuator,
Chiller2PumpStatus, !- Name
COOLSYS1 CHILLER2 PUMP, !- Actuated Component Unique Name
Plant Component Pump:ConstantSpeed, !- Actuated Component Type
On/Off Supervisory; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
Chiller1PumpFlow, !- Name
COOLSYS1 CHILLER1 PUMP, !- Actuated Component Unique Name
Pump, !- Actuated Component Type
Pump Mass Flow Rate; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
Chiller2PumpFlow, !- Name
COOLSYS1 CHILLER2 PUMP, !- Actuated Component Unique Name
Pump, !- Actuated Component Type
Pump Mass Flow Rate; !- Actuated Component Control Type
EnergyManagementSystem:Actuator,
Chiller2Status, !- Name
COOLSYS1 CHILLER2, !- Actuated Component Unique Name
Plant Component Chiller:Electric:ReformulatedEIR, !- Actuated Component Type
On/Off Supervisory; !- Actuated Component Control Type
EnergyManagementSystem:Sensor,
ChillerPlantDemandLoad, !- Name
CoolSys1_Supply, !- Output:Variable or Output:Meter Index Key Name
Plant Supply Side Cooling Demand Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Program, ! Addendum DV
PlantPump_EMS_Program, !
IF ChillerPlantDemandLoad < 1302254.38, ! Addendum DV EMS Chiller Capacity. Will be overriden by sizing script.
SET Chiller2PumpStatus = 0, !- <none>
SET Chiller2Status = 0, !- <none>
SET Chiller2PumpFlow = 0,!- <none>
ELSE, !- <none>
SET Chiller2PumpStatus = 1, !- <none>
SET Chiller2Status = 1, !- <none>
SET Chiller2PumpFlow = Chiller2PumpDesignFlow, !- <none>
ENDIF; !- <none>
EnergyManagementSystem:ProgramCallingManager,
PlantPump_EMS_Program Manager, !- Name
InsideHVACSystemIterationLoop, !- EnergyPlus Model Calling Point
PlantPump_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Basement_LSr, !- Name
Basement, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Basement_Occ_Sensor, !- Name
Basement, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Basement_Area, !- Name
Basement, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Basement_Light_Actuator, !- Name
Basement_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Basement_Light_EMS_Program, !- Name
SET Basement_LSr_IP=0.093*Basement_LSr/Basement_Area, ! Calculate the actual LPD for each hour
IF (Basement_Occ_Sensor <= 0) && (Basement_LSr_IP >= 0.02),
SET Basement_Light_Actuator = 0.02*Basement_Area/0.09290304,
ELSE,
SET Basement_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Basement_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Basement_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Core_bottom_LSr, !- Name
Core_bottom, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Core_bottom_Occ_Sensor, !- Name
Core_bottom, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Core_bottom_Area, !- Name
Core_bottom, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Core_bottom_Light_Actuator, !- Name
Core_bottom_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Core_bottom_Light_EMS_Program, !- Name
SET Core_bottom_LSr_IP=0.093*Core_bottom_LSr/Core_bottom_Area, ! Calculate the actual LPD for each hour
IF (Core_bottom_Occ_Sensor <= 0) && (Core_bottom_LSr_IP >= 0.02),
SET Core_bottom_Light_Actuator = 0.02*Core_bottom_Area/0.09290304,
ELSE,
SET Core_bottom_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Core_bottom_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Core_bottom_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Core_mid_LSr, !- Name
Core_mid, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Core_mid_Occ_Sensor, !- Name
Core_mid, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Core_mid_Area, !- Name
Core_mid, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Core_mid_Light_Actuator, !- Name
Core_mid_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Core_mid_Light_EMS_Program, !- Name
SET Core_mid_LSr_IP=0.093*Core_mid_LSr/Core_mid_Area, ! Calculate the actual LPD for each hour
IF (Core_mid_Occ_Sensor <= 0) && (Core_mid_LSr_IP >= 0.02),
SET Core_mid_Light_Actuator = 0.02*Core_mid_Area/0.09290304,
ELSE,
SET Core_mid_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Core_mid_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Core_mid_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Core_top_LSr, !- Name
Core_top, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Core_top_Occ_Sensor, !- Name
Core_top, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Core_top_Area, !- Name
Core_top, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Core_top_Light_Actuator, !- Name
Core_top_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Core_top_Light_EMS_Program, !- Name
SET Core_top_LSr_IP=0.093*Core_top_LSr/Core_top_Area, ! Calculate the actual LPD for each hour
IF (Core_top_Occ_Sensor <= 0) && (Core_top_LSr_IP >= 0.02),
SET Core_top_Light_Actuator = 0.02*Core_top_Area/0.09290304,
ELSE,
SET Core_top_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Core_top_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Core_top_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_3_LSr, !- Name
Perimeter_bot_ZN_3, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_3_Occ_Sensor, !- Name
Perimeter_bot_ZN_3, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_bot_ZN_3_Area, !- Name
Perimeter_bot_ZN_3, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_bot_ZN_3_Light_Actuator, !- Name
Perimeter_bot_ZN_3_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_bot_ZN_3_Light_EMS_Program, !- Name
SET Perimeter_bot_ZN_3_LSr_IP=0.093*Perimeter_bot_ZN_3_LSr/Perimeter_bot_ZN_3_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_bot_ZN_3_Occ_Sensor <= 0) && (Perimeter_bot_ZN_3_LSr_IP >= 0.02),
SET Perimeter_bot_ZN_3_Light_Actuator = 0.02*Perimeter_bot_ZN_3_Area/0.09290304,
ELSE,
SET Perimeter_bot_ZN_3_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_bot_ZN_3_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_bot_ZN_3_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_2_LSr, !- Name
Perimeter_bot_ZN_2, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_2_Occ_Sensor, !- Name
Perimeter_bot_ZN_2, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_bot_ZN_2_Area, !- Name
Perimeter_bot_ZN_2, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_bot_ZN_2_Light_Actuator, !- Name
Perimeter_bot_ZN_2_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_bot_ZN_2_Light_EMS_Program, !- Name
SET Perimeter_bot_ZN_2_LSr_IP=0.093*Perimeter_bot_ZN_2_LSr/Perimeter_bot_ZN_2_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_bot_ZN_2_Occ_Sensor <= 0) && (Perimeter_bot_ZN_2_LSr_IP >= 0.02),
SET Perimeter_bot_ZN_2_Light_Actuator = 0.02*Perimeter_bot_ZN_2_Area/0.09290304,
ELSE,
SET Perimeter_bot_ZN_2_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_bot_ZN_2_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_bot_ZN_2_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_1_LSr, !- Name
Perimeter_bot_ZN_1, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_1_Occ_Sensor, !- Name
Perimeter_bot_ZN_1, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_bot_ZN_1_Area, !- Name
Perimeter_bot_ZN_1, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_bot_ZN_1_Light_Actuator, !- Name
Perimeter_bot_ZN_1_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_bot_ZN_1_Light_EMS_Program, !- Name
SET Perimeter_bot_ZN_1_LSr_IP=0.093*Perimeter_bot_ZN_1_LSr/Perimeter_bot_ZN_1_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_bot_ZN_1_Occ_Sensor <= 0) && (Perimeter_bot_ZN_1_LSr_IP >= 0.02),
SET Perimeter_bot_ZN_1_Light_Actuator = 0.02*Perimeter_bot_ZN_1_Area/0.09290304,
ELSE,
SET Perimeter_bot_ZN_1_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_bot_ZN_1_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_bot_ZN_1_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_4_LSr, !- Name
Perimeter_bot_ZN_4, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_bot_ZN_4_Occ_Sensor, !- Name
Perimeter_bot_ZN_4, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_bot_ZN_4_Area, !- Name
Perimeter_bot_ZN_4, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_bot_ZN_4_Light_Actuator, !- Name
Perimeter_bot_ZN_4_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_bot_ZN_4_Light_EMS_Program, !- Name
SET Perimeter_bot_ZN_4_LSr_IP=0.093*Perimeter_bot_ZN_4_LSr/Perimeter_bot_ZN_4_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_bot_ZN_4_Occ_Sensor <= 0) && (Perimeter_bot_ZN_4_LSr_IP >= 0.02),
SET Perimeter_bot_ZN_4_Light_Actuator = 0.02*Perimeter_bot_ZN_4_Area/0.09290304,
ELSE,
SET Perimeter_bot_ZN_4_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_bot_ZN_4_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_bot_ZN_4_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_3_LSr, !- Name
Perimeter_mid_ZN_3, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_3_Occ_Sensor, !- Name
Perimeter_mid_ZN_3, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_mid_ZN_3_Area, !- Name
Perimeter_mid_ZN_3, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_mid_ZN_3_Light_Actuator, !- Name
Perimeter_mid_ZN_3_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_mid_ZN_3_Light_EMS_Program, !- Name
SET Perimeter_mid_ZN_3_LSr_IP=0.093*Perimeter_mid_ZN_3_LSr/Perimeter_mid_ZN_3_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_mid_ZN_3_Occ_Sensor <= 0) && (Perimeter_mid_ZN_3_LSr_IP >= 0.02),
SET Perimeter_mid_ZN_3_Light_Actuator = 0.02*Perimeter_mid_ZN_3_Area/0.09290304,
ELSE,
SET Perimeter_mid_ZN_3_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_mid_ZN_3_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_mid_ZN_3_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_2_LSr, !- Name
Perimeter_mid_ZN_2, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_2_Occ_Sensor, !- Name
Perimeter_mid_ZN_2, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_mid_ZN_2_Area, !- Name
Perimeter_mid_ZN_2, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_mid_ZN_2_Light_Actuator, !- Name
Perimeter_mid_ZN_2_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_mid_ZN_2_Light_EMS_Program, !- Name
SET Perimeter_mid_ZN_2_LSr_IP=0.093*Perimeter_mid_ZN_2_LSr/Perimeter_mid_ZN_2_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_mid_ZN_2_Occ_Sensor <= 0) && (Perimeter_mid_ZN_2_LSr_IP >= 0.02),
IF (DaylightSavings==0) && ((Hour < 7) || (Hour > 16)), !- Hour check is to avoid conflict with Add. G
SET Perimeter_mid_ZN_2_Light_Actuator = 0.02*Perimeter_mid_ZN_2_Area/0.09290304,
ELSEIF (DaylightSavings==1) && ((Hour < 6) || (Hour > 15)), !- Hour check is to avoid conflict with Add. G 1
SET Perimeter_mid_ZN_2_Light_Actuator = 0.02*Perimeter_mid_ZN_2_Area/0.09290304,
ELSE,
SET Perimeter_mid_ZN_2_Light_Actuator = NULL,
ENDIF,
ELSE,
SET Perimeter_mid_ZN_2_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_mid_ZN_2_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_mid_ZN_2_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_1_LSr, !- Name
Perimeter_mid_ZN_1, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_1_Occ_Sensor, !- Name
Perimeter_mid_ZN_1, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_mid_ZN_1_Area, !- Name
Perimeter_mid_ZN_1, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_mid_ZN_1_Light_Actuator, !- Name
Perimeter_mid_ZN_1_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_mid_ZN_1_Light_EMS_Program, !- Name
SET Perimeter_mid_ZN_1_LSr_IP=0.093*Perimeter_mid_ZN_1_LSr/Perimeter_mid_ZN_1_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_mid_ZN_1_Occ_Sensor <= 0) && (Perimeter_mid_ZN_1_LSr_IP >= 0.02),
SET Perimeter_mid_ZN_1_Light_Actuator = 0.02*Perimeter_mid_ZN_1_Area/0.09290304,
ELSE,
SET Perimeter_mid_ZN_1_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_mid_ZN_1_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_mid_ZN_1_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_4_LSr, !- Name
Perimeter_mid_ZN_4, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_mid_ZN_4_Occ_Sensor, !- Name
Perimeter_mid_ZN_4, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_mid_ZN_4_Area, !- Name
Perimeter_mid_ZN_4, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_mid_ZN_4_Light_Actuator, !- Name
Perimeter_mid_ZN_4_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_mid_ZN_4_Light_EMS_Program, !- Name
SET Perimeter_mid_ZN_4_LSr_IP=0.093*Perimeter_mid_ZN_4_LSr/Perimeter_mid_ZN_4_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_mid_ZN_4_Occ_Sensor <= 0) && (Perimeter_mid_ZN_4_LSr_IP >= 0.02),
SET Perimeter_mid_ZN_4_Light_Actuator = 0.02*Perimeter_mid_ZN_4_Area/0.09290304,
ELSE,
SET Perimeter_mid_ZN_4_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_mid_ZN_4_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_mid_ZN_4_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_3_LSr, !- Name
Perimeter_top_ZN_3, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_3_Occ_Sensor, !- Name
Perimeter_top_ZN_3, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_top_ZN_3_Area, !- Name
Perimeter_top_ZN_3, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_top_ZN_3_Light_Actuator, !- Name
Perimeter_top_ZN_3_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_top_ZN_3_Light_EMS_Program, !- Name
SET Perimeter_top_ZN_3_LSr_IP=0.093*Perimeter_top_ZN_3_LSr/Perimeter_top_ZN_3_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_top_ZN_3_Occ_Sensor <= 0) && (Perimeter_top_ZN_3_LSr_IP >= 0.02),
SET Perimeter_top_ZN_3_Light_Actuator = 0.02*Perimeter_top_ZN_3_Area/0.09290304,
ELSE,
SET Perimeter_top_ZN_3_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_top_ZN_3_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_top_ZN_3_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_2_LSr, !- Name
Perimeter_top_ZN_2, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_2_Occ_Sensor, !- Name
Perimeter_top_ZN_2, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_top_ZN_2_Area, !- Name
Perimeter_top_ZN_2, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_top_ZN_2_Light_Actuator, !- Name
Perimeter_top_ZN_2_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_top_ZN_2_Light_EMS_Program, !- Name
SET Perimeter_top_ZN_2_LSr_IP=0.093*Perimeter_top_ZN_2_LSr/Perimeter_top_ZN_2_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_top_ZN_2_Occ_Sensor <= 0) && (Perimeter_top_ZN_2_LSr_IP >= 0.02),
SET Perimeter_top_ZN_2_Light_Actuator = 0.02*Perimeter_top_ZN_2_Area/0.09290304,
ELSE,
SET Perimeter_top_ZN_2_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_top_ZN_2_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_top_ZN_2_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_1_LSr, !- Name
Perimeter_top_ZN_1, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_1_Occ_Sensor, !- Name
Perimeter_top_ZN_1, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_top_ZN_1_Area, !- Name
Perimeter_top_ZN_1, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_top_ZN_1_Light_Actuator, !- Name
Perimeter_top_ZN_1_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_top_ZN_1_Light_EMS_Program, !- Name
SET Perimeter_top_ZN_1_LSr_IP=0.093*Perimeter_top_ZN_1_LSr/Perimeter_top_ZN_1_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_top_ZN_1_Occ_Sensor <= 0) && (Perimeter_top_ZN_1_LSr_IP >= 0.02),
SET Perimeter_top_ZN_1_Light_Actuator = 0.02*Perimeter_top_ZN_1_Area/0.09290304,
ELSE,
SET Perimeter_top_ZN_1_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_top_ZN_1_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_top_ZN_1_Light_EMS_Program; !- Program Name 1
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_4_LSr, !- Name
Perimeter_top_ZN_4, !- Output:Variable or Output:Meter Index Key Name
Zone Lights Electric Power; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
Perimeter_top_ZN_4_Occ_Sensor, !- Name
Perimeter_top_ZN_4, !- Output:Variable or Output:Meter Index Key Name
People Occupant Count; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:InternalVariable,
Perimeter_top_ZN_4_Area, !- Name
Perimeter_top_ZN_4, !- Internal Data Index Key Name
Zone Floor Area; !- Internal Data Type
EnergyManagementSystem:Actuator,
Perimeter_top_ZN_4_Light_Actuator, !- Name
Perimeter_top_ZN_4_lights, !- Actuated Component Unique Name
Lights, !- Actuated Component Type
Electric Power Level; !- Actuated Component Control Type
EnergyManagementSystem:Program,
SET_Perimeter_top_ZN_4_Light_EMS_Program, !- Name
SET Perimeter_top_ZN_4_LSr_IP=0.093*Perimeter_top_ZN_4_LSr/Perimeter_top_ZN_4_Area, ! Calculate the actual LPD for each hour
IF (Perimeter_top_ZN_4_Occ_Sensor <= 0) && (Perimeter_top_ZN_4_LSr_IP >= 0.02),
SET Perimeter_top_ZN_4_Light_Actuator = 0.02*Perimeter_top_ZN_4_Area/0.09290304,
ELSE,
SET Perimeter_top_ZN_4_Light_Actuator = NULL,
ENDIF;
EnergyManagementSystem:ProgramCallingManager,
SET_Perimeter_top_ZN_4_Light_EMS_Program_Prog_Manager, !- Name
AfterPredictorAfterHVACManagers, !- EnergyPlus Model Calling Point
SET_Perimeter_top_ZN_4_Light_EMS_Program; !- Program Name 1
HeatExchanger:FluidToFluid,
Bypass Heat exchanger, !- Name
ALWAYS_ON, !- Availability Schedule Name
CoolSys1 Exchancher Supply Inlet Node, !- Loop Demand Side Inlet Node Name
CoolSys1 Exchancher Supply Outlet Node, !- Loop Demand Side Outlet Node Name
autosize, !- Loop Demand Side Design Flow Rate {m3/s}
CoolSys1 Exchancher Demand Inlet Node, !- Loop Supply Side Inlet Node Name
CoolSys1 Exchancher Demand Outlet Node, !- Loop Supply Side Outlet Node Name
autosize, !- Loop Supply Side Design Flow Rate {m3/s}
Ideal, !- Heat Exchange Model Type
autosize, !- Heat Exchanger U-Factor Times Area Value {W/K}
UncontrolledOn, !- Control Type
, !- Heat Exchanger Setpoint Node Name
0.01, !- Minimum Temperature Difference to Activate Heat Exchanger {deltaC}
LoopToLoop, !- Heat Transfer Metering End Use Type
, !- Component Override Loop Supply Side Inlet Node Name
, !- Component Override Loop Demand Side Inlet Node Name
Loop, !- Component Override Cooling Control Temperature Mode
1; !- Sizing Factor