hub/data/schedules/idf_files/ASHRAE901_ApartmentMidRise_STD2019_Rochester.idf
Soroush Samareh Abolhassani 1e591ba5b4 The idf files have been added.
2021-08-30 18:46:35 -04:00

18641 lines
888 KiB
Plaintext

!The DOE Prototype Building Models were developed by Pacific Northwest National Laboratory (PNNL), under contract with the U.S.
!Department of Energy (DOE). These building models were derived from DOE's Commercial Reference Building Models with modifications
!based on input from the ASHRAE Standard 90.1 committee, the Advanced Energy Design Guide series, and building industry experts. The
!prototypes models were developed to quantify energy saving impacts from newly published editions of ASHRAE Standard 90.1, 189.1, IECC,
!and other energy codes and standards. The basic building descriptions can be found in the Scorecards posted at www.energycodes.gov
!website. The recommended citation of the prototype models is
!
!DOE and PNNL. 2020. Commercial Prototype Building Models, Richland, WA, Pacific Northwest National Laboratory. Available at https://www.energycodes.gov/development/commercial/prototype_models.
!
!Detailed descriptions of the prototype model development and addenda modeling strategies can be found in the following reports:
!DOE, 2020. Preliminary Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2019. Report prepared by Zhang, J., M. Rosenberg, J.
!Lerond, Y. Xie, Nambia, C., Y. Chen, R. Hart, M. Halverson, D. Maddox, and S. Goel, Richland, WA, Pacific Northwest National Laboratory.
!
!Zhang, J., Y. Chen, Y. Xie, M. Rosenberg, R. Hart. Energy and Energy Cost Savings Analysis of the 2018 IECC for Commercial Buildings.
!2018. PNNL-28125. Richland, WA: Pacific Northwest National Laboratory.
!
!DOE. 2017. Energy Savings Analysis: ANSI/ASHRAE/IES Standard 90.1-2016. Prepared by Athalye, R.A, M.A. Halverson, M.I. Rosenberg, B. Liu,
!J. Zhang, R. Hart, V.V. Mendon, S. Goel, Y. Chen, Y. Xie, and M. Zhao, Richland, WA, Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/02202018_Standard_90.1-2016_Determination_TSD.pdf.
!
!Zhang, J., Y. Xie, R.A. Athalye, J. Zhuge, M. Rosenberg, R. Hart, and B. Liu. Energy and Energy Cost Savings Analysis of the 2015 IECC
!for Commercial Buildings. 2015. PNNL-24269 Rev. 1. Richland, WA: Pacific Northwest National
!Laboratory. https://www.energycodes.gov/sites/default/files/documents/2015_IECC_Commercial_Analysis.pdf.
!
!Halverson M.A., M.I. Rosenberg, W. Wang, J. Zhang, V.V. Mendon, R.A. Athalye, Y. Xie, R. Hart, S. Goel, 2014. ANSI/ASHRAE/IES Standard
!90.1-2013 Determination of Energy Savings: Quantitative Analysis, PNNL-23479. Richland, WA: Pacific Northwest National Laboratory. https://www.energycodes.gov/sites/default/files/documents/901-2013_finalCommercialDeterminationQuantitativeAnalysis_TSD_0.pdf.
!
!Goel S., R.A. Athalye, W. Wang, J. Zhang, M.I. Rosenberg, Y. Xie, and R. Hart, et al. 2014. Enhancements to ASHRAE Standard 90.1
!Prototype Building Models. PNNL-23269. Richland, WA: Pacific Northwest National Laboratory. https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-23269.pdf.
!
!Zhang J., R.A. Athalye, R. Hart, M.I. Rosenberg, Y. Xie, S. Goel, and V.V. Mendon, et al. 2013. Energy and Energy Cost Savings Analysis
!of the IECC for Commercial Buildings. PNNL-22760. Richland, WA: Pacific Northwest National Laboratory. http://www.pnnl.gov/main/publications/external/technical_reports/PNNL-22760.pdf.
!
!Thornton B.A., M.I. Rosenberg, E.E. Richman, W. Wang, Y. Xie, J. Zhang, H. Cho, VV Mendon, R.A. Athalye, and B. Liu. 2011. Achieving
!the 30% Goal: Energy and Cost Savings Analysis of ASHRAE Standard 90.1-2010. PNNL-20405. Richland, WA: Pacific Northwest National
!Laboratory. https://www.energycodes.gov/sites/default/files/documents/BECP_Energy_Cost_Savings_STD2010_May2011_v00.pdf.
!
!
! WeatherFile: USA_MN_Rochester.Intl.AP.726440_TMY3.epw
! GPARM parameters as input:
! Case = ASHRAE901_ApartmentMidRise_STD2019_Rochester
! SelectedCase =
! annual_run = no
! slab_gtp = National_ApartmentMidRise_ASHRAE901_STD2016_Zone6A_res_MN-Rochester-MN.gtp
! avg_oa_tempt_ip = 43.475
! maxdiff_oa_tempt_ip = 60.3
! ext_wall_type = SteelFramedWall
! res_ext_wall_ufactor = 0.278234887
! roof_type = MetalDeckRoof
! res_roof_ufactor = 0.181704416
! roof_emissEHity = 0.9
! roof_solar_absorp = 0.7
! res_window =
! economizer = NO ECONOMIZER
! skip_economizer_control = Yes
! avg_oa_tempt = 6.375
! maxdiff_oa_tempt = 33.5
! infil = 0.00056896
! LPD_apartment_hardwired = 6.45834625
! LPD_apartment_plugin = 2.906255813
! LPD_office = 7.965293709
! LPD_corridor = 5.295843925
! oa_apartment = 0.000294087
! oa_office = 0.000431773
! oa_corridor = 0.000304781
! exterior_light_watts = 1651
! door_infil = 0.327531218
! frac_ofpk = 0.131
! economizer_lockout = LockoutWithHeating
! BLDG_ELEVATORS_LIGHTS_FAN_SCH = ELEV_LIGHT_FAN_SCH_ADD_DF
! BLDG_ELEVATORS_LIGHTS_FAN_POWER = 63
! EQP_OFF_SCH = EQP_OFF_SCH_ADV
! pv_generator = no
! pv_surface_area = 0
! STD189_overhang = no
! swh_et = 1
! swh_ua = 2.012559766
! ext_lgt_sch = Exterior_Lgt_ALWAYS_ON
! LTG_SCH_SET = LTG_SET_STD2013
! wwr = 0.2
! HTGSETP_OFF_SCH = HTGSETP_OFF_SCH_NO_OPTIMUM
! CLGSETP_OFF_SCH = CLGSETP_OFF_SCH_No_Optimum
! pipe_heat_loss_Gapts = 87
! pipe_heat_loss_Mapts = 73
! skip_EMSprogram = yes
! Wfile_TMY3 = USA_MN_Rochester.Intl.AP.726440_TMY3.epw
! loadProfile = No
! Door_Switch_Enabled_Thermostat_Reset = TRUE
! receptacle_ctrl_occ_reduction_frac = 0.92575
! receptacle_ctrl_unocc_reduction_frac = 0.6625
! CodeName = ASHRAE90.1_STD2019
! CZ_City_Old = Burlington
! CZ_Label = 6A
! Split_GSW_ERV = Yes
! Split_GNW_ERV = Yes
! Split_GNE_ERV = Yes
! Split_GN1_ERV = Yes
! Split_GN2_ERV = Yes
! Split_GS1_ERV = Yes
! Split_GS2_ERV = Yes
! Split_MSW_ERV = Yes
! Split_MNW_ERV = Yes
! Split_MSE_ERV = Yes
! Split_MNE_ERV = Yes
! Split_MN1_ERV = Yes
! Split_MN2_ERV = Yes
! Split_MS1_ERV = Yes
! Split_MS2_ERV = Yes
! Split_TSW_ERV = Yes
! Split_TNW_ERV = Yes
! Split_TSE_ERV = Yes
! Split_TNE_ERV = Yes
! Split_TN1_ERV = Yes
! Split_TN2_ERV = Yes
! Split_TS1_ERV = Yes
! Split_TS2_ERV = Yes
! Split_GSW_ERV_power = 69.299602
! Split_GNW_ERV_power = 68.6212775
! Split_GNE_ERV_power = 68.6212775
! Split_GN1_ERV_power = 68.6212775
! Split_GN2_ERV_power = 68.6212775
! Split_GS1_ERV_power = 68.6212775
! Split_GS2_ERV_power = 68.6212775
! Split_MSW_ERV_power = 68.621241625
! Split_MNW_ERV_power = 68.621241625
! Split_MSE_ERV_power = 68.621241625
! Split_MNE_ERV_power = 68.621241625
! Split_MN1_ERV_power = 68.621241625
! Split_MN2_ERV_power = 68.621241625
! Split_MS1_ERV_power = 68.621241625
! Split_MS2_ERV_power = 68.621241625
! Split_TSW_ERV_power = 68.6212775
! Split_TNW_ERV_power = 68.6212775
! Split_TSE_ERV_power = 68.6212775
! Split_TNE_ERV_power = 68.6212775
! Split_TN1_ERV_power = 68.6212775
! Split_TN2_ERV_power = 68.6212775
! Split_TS1_ERV_power = 68.6212775
! Split_TS2_ERV_power = 68.6212775
! office_standby_mode = Yes
! res_window_u_factor = 0.36
! res_window_shgc = 0.37
! resLSG = 1.1
! AnalysisPurpose = ProgressIndicator
! AnalysisCodeName = ASHRAE901
! AnalysisCodeYear = 2019
! AnalysisAmendment = NoneAmend
! AnalysisPrototype = ApartmentMidRise
! AnalysisScope = National
! AnalysisState = National
! AnalysisClimateZone = 6A
! AnalysisCity = USA_MN_Rochester
! var_Ffactor_IP = 0.434
! var_Cfactor_IP = 0.063
! APT_SWH_flow = 3.66e-06
! VT_Elec_Wheater = No
! specify overhang_pf for 1891 codes
!- =========== ALL OBJECTS IN CLASS: VERSION ===========
Version,9.0;
!- =========== ALL OBJECTS IN CLASS: BUILDING ===========
Building,
ApartmentMidRise, !- Name
0, !- North Axis {deg}
City, !- Terrain
0.04, !- Loads Convergence Tolerance Value
0.4, !- Temperature Convergence Tolerance Value {deltaC}
FullExterior, !- Solar Distribution
25, !- Maximum Number of Warmup Days
6; !- Minimum Number of Warmup Days
!- =========== ALL OBJECTS IN CLASS: TIMESTEP IN HOUR ===========
Timestep,6;
ConvergenceLimits,
1, !- Minimum System Timestep {minutes}
20; !- Maximum HVAC Iterations
!- =========== ALL OBJECTS IN CLASS: INSIDE CONVECTION ALGORITHM ===========
SurfaceConvectionAlgorithm:Inside,TARP;
!- =========== ALL OBJECTS IN CLASS: OUTSIDE CONVECTION ALGORITHM ===========
SurfaceConvectionAlgorithm:Outside,TARP;
!- =========== ALL OBJECTS IN CLASS: SOLUTION ALGORITHM ===========
HeatBalanceAlgorithm,ConductionTransferFunction;
!- =========== ALL OBJECTS IN CLASS: RUN CONTROL ===========
SimulationControl,
Yes, !- Do Zone Sizing Calculation
Yes, !- Do System Sizing Calculation
No, !- Do Plant Sizing Calculation
No, !- Run Simulation for Sizing Periods
YES; !- Run Simulation for Weather File Run Periods
!- =========== ALL OBJECTS IN CLASS: RUNPERIOD ===========
RunPeriod,
, !- Name
1, !- Begin Month
1, !- Begin Day of Month
, !- Begin Year
12, !- End Month
31, !- End Day of Month
, !- End Year
Sunday, ! Day of Week for Start Day
No, !- Use Weather File Holidays and Special Days
No, !- Use Weather File Daylight Saving Period
Yes, !- Apply Weekend Holiday Rule
Yes, !- Use Weather File Rain Indicators
Yes; !- Use Weather File Snow Indicators
!- =========== ALL OBJECTS IN CLASS: SPECIALDAYPERIOD ===========
RunPeriodControl:SpecialDays,
New Year's Day, !- Name
Jan 1, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
MLK Day, !- Name
3rd Monday in January, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Presidents Day, !- Name
3rd Monday in February, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Memorial Day, !- Name
Last Monday in May, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Independence Day, !- Name
July 4, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Labor day, !- Name
1st Monday in September, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Columbus Day, !- Name
2nd Monday in October, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Thanksgiving, !- Name
4th Thursday in November,!- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Veterans Day, !- Name
November 11, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
RunPeriodControl:SpecialDays,
Christmas, !- Name
December 25, !- Start Date
1, !- Duration {days}
Holiday; !- Special Day Type
!- =========== ALL OBJECTS IN CLASS: DAYLIGHTSAVINGPERIOD ===========
RunPeriodControl:DaylightSavingTime,
2nd Sunday in March, !- Start Date
1st Sunday in November; !- End Date
!- =========== ALL OBJECTS IN CLASS: LOCATION ===========
! Site:Location and design-day objects created by:
! ../../_p.bin/ddy2idf /projects/bigsim/weather/EnergyPlus/tmy3.new/all/USA_MN_Rochester.Intl.AP.726440_TMY3.ddy
!
Site:Location,
Rochester International Arpt_MN_USA Design_Conditions, !- Site:Location Name
43.90, !- Latitude {N+ S-}
-92.50, !- Longitude {W- E+}
-6.00, !- Time Zone Relative to GMT {GMT+/-}
398.00; !- Elevation {m}
SizingPeriod:DesignDay,
Rochester International Arpt Ann Htg 99.6% Condns DB, !- Name
1, !- Month
21, !- Day of Month
WinterDesignDay,!- Day Type
-26.2, !- Maximum Dry-Bulb Temperature {C}
0.0, !- Daily Dry-Bulb Temperature Range {C}
DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type
, !- Dry-Bulb Temperature Range Modifier Schedule Name
Wetbulb, !- Humidity Condition Type
-26.2, !- Wetbulb at Maximum Dry-Bulb {C}
, !- Humidity Indicating Day Schedule Name
, !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir}
, !- Enthalpy at Maximum Dry-Bulb {J/kg}
, !- Daily WetBulb Temperature Range {deltaC}
96634., !- Barometric Pressure {Pa}
5.7, !- Wind Speed {m/s} design conditions vs. traditional 6.71 m/s (15 mph)
310, !- Wind Direction {Degrees; N=0, S=180}
No, !- Rain {Yes/No}
No, !- Snow on ground {Yes/No}
No, !- Daylight Savings Time Indicator
ASHRAEClearSky, !- Solar Model Indicator
, !- Beam Solar Day Schedule Name
, !- Diffuse Solar Day Schedule Name
, !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub)
, !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud)
0.00; !- Clearness {0.0 to 1.1}
SizingPeriod:DesignDay,
Rochester International Arpt Ann Clg .4% Condns DB=>MWB, !- Name
7, !- Month
21, !- Day of Month
SummerDesignDay,!- Day Type
31.2, !- Maximum Dry-Bulb Temperature {C}
10.6, !- Daily Dry-Bulb Temperature Range {C}
DefaultMultipliers, !- Dry-Bulb Temperature Range Modifier Type
, !- Dry-Bulb Temperature Range Modifier Schedule Name
Wetbulb, !- Humidity Condition Type
23.1, !- Wetbulb at Maximum Dry-Bulb {C}
, !- Humidity Indicating Day Schedule Name
, !- Humidity Ratio at Maximum Dry-Bulb {kgWater/kgDryAir}
, !- Enthalpy at Maximum Dry-Bulb {J/kg}
, !- Daily WetBulb Temperature Range {deltaC}
96634., !- Barometric Pressure {Pa}
6.7, !- Wind Speed {m/s} design conditions vs. traditional 3.35 m/s (7mph)
200, !- Wind Direction {Degrees; N=0, S=180}
No, !- Rain {Yes/No}
No, !- Snow on ground {Yes/No}
No, !- Daylight Savings Time Indicator
ASHRAETau, !- Solar Model Indicator
, !- Beam Solar Day Schedule Name
, !- Diffuse Solar Day Schedule Name
0.404, !- ASHRAE Clear Sky Optical Depth for Beam Irradiance (taub)
2.226; !- ASHRAE Clear Sky Optical Depth for Diffuse Irradiance (taud)
!- =========== ALL OBJECTS IN CLASS: WATER MAINS TEMPERATURES ===========
Site:WaterMainsTemperature,
Correlation, !- Calculation Method
, !- Temperature Schedule Name
6.375, !- Annual average outdoor air temperature {C}
33.5; !- Maximum difference in monthly average outdoor air temperatures {C}
!- =========== ALL OBJECTS IN CLASS: Site:GroundTemperature:FCfactorMethod ===========
Site:GroundTemperature:FCfactorMethod,
7.4, !- January Ground Temperature {C}
-0.0, !- February Ground Temperature {C}
-7.6, !- March Ground Temperature {C}
-12.6, !- April Ground Temperature {C}
-7.7, !- May Ground Temperature {C}
0.3, !- June Ground Temperature {C}
7.0, !- July Ground Temperature {C}
14.2, !- August Ground Temperature {C}
19.2, !- September Ground Temperature {C}
20.9, !- October Ground Temperature {C}
20.0, !- November Ground Temperature {C}
15.4; !- December Ground Temperature {C}
!- =========== Opaque Constructions ===========
!
!- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR ===========
Material,
Std Wood 6inch, !- Name
MediumSmooth, !- Roughness
0.15, !- Thickness {m}
0.12, !- Conductivity {W/m-K}
540.0000, !- Density {kg/m3}
1210, !- Specific Heat {J/kg-K}
0.9000000, !- Thermal Absorptance
0.7000000, !- Solar Absorptance
0.7000000; !- Visible Absorptance
Material,
AC02 Acoustic Ceiling, !- Name
MediumSmooth, !- Roughness
1.2700000E-02, !- Thickness {m}
5.7000000E-02, !- Conductivity {W/m-K}
288.0000, !- Density {kg/m3}
1339.000, !- Specific Heat {J/kg-K}
0.9000000, !- Thermal Absorptance
0.7000000, !- Solar Absorptance
0.2000000; !- Visible Absorptance
Material,
F07 25mm stucco, !- Name
Smooth, !- Roughness
0.0254, !- Thickness {m}
0.72, !- Conductivity {W/m-K}
1856, !- Density {kg/m3}
840, !- Specific Heat {J/kg-K}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material,
F08 Metal surface, !- Name
Smooth, !- Roughness
0.0008, !- Thickness {m}
45.28, !- Conductivity {W/m-K}
7824, !- Density {kg/m3}
500; !- Specific Heat {J/kg-K}
Material,
F08 Metal roof surface, !- Name
Smooth, !- Roughness
0.0008, !- Thickness {m}
45.28, !- Conductivity {W/m-K}
7824, !- Density {kg/m3}
500, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
F12 Asphalt shingles, !- Name
VeryRough, !- Roughness
0.0032, !- Thickness {m}
0.04, !- Conductivity {W/m-K}
1120, !- Density {kg/m3}
1260, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
F13 Built-up roofing, !- Name
Rough, !- Roughness
0.0095, !- Thickness {m}
0.16, !- Conductivity {W/m-K}
1120, !- Density {kg/m3}
1460, !- Specific Heat {J/kg-K}
0.9, !- Absorptance:Thermal
0.7; !- Absorptance:Solar
Material,
G01 13mm gypsum board, !- Name
Smooth, !- Roughness
0.0127, !- Thickness {m}
0.1600, !- Conductivity {W/m-K}
800.0000, !- Density {kg/m3}
1090.0000, !- Specific Heat {J/kg-K}
0.9000, !- Absorptance:Thermal
0.7000, !- Absorptance:Solar
0.5000; !- Absorptance:Visible
Material,
G01 16mm gypsum board, !- Name
MediumSmooth, !- Roughness
0.0159, !- Thickness {m}
0.16, !- Conductivity {W/m-K}
800, !- Density {kg/m3}
1090; !- Specific Heat {J/kg-K}
Material,
G02 16mm plywood, !- Name
Smooth, !- Roughness
0.0159, !- Thickness {m}
0.12, !- Conductivity {W/m-K}
544, !- Density {kg/m3}
1210; !- Specific Heat {J/kg-K}
Material,
M14 150mm heavyweight concrete roof, !- Name
MediumRough, !- Roughness
0.1524, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
100mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1016, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
200mm Normalweight concrete wall, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.2032, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
100mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1016, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
150mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.1524, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
200mm Normalweight concrete floor, !- Name - based on 90.1-2004 Appendix-Table A3-1B
MediumRough, !- Roughness
0.2032, !- Thickness {m}
2.31, !- Conductivity {W/m-K}
2322, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
M10 200mm concrete block wall, !- Name
MediumRough, !- Roughness
0.2032, !- Thickness {m}
0.72, !- Conductivity {W/m-K}
800, !- Density {kg/m3}
832; !- Specific Heat {J/kg-K}
Material,
M10 200mm concrete block basement wall, !- Name
MediumRough, !- Roughness
0.2032, !- Thickness {m}
1.326, !- Conductivity {W/m-K}
1842, !- Density {kg/m3}
912; !- Specific Heat {J/kg-K}
Material:NoMass,
CP02 CARPET PAD, !- Name
VeryRough, !- Roughness
0.21648, !- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.8; !- Visible Absorptance
Material:NoMass,
Air_Wall_Material, !- Name
Rough, !- Roughness
0.2079491, !- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7; !- Solar Absorptance
Material:NoMass,
Nonres_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Absorptance:Thermal
0.7, !- Absorptance:Solar
0.7; !- Absorptance:Visible
Material:NoMass,
Res_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
5.30668495131472,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Roof_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Nonres_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Res_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
3.21036415428069,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Exterior_Wall_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Nonres_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Res_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Semiheated_Floor_Insulation, !- Name
MediumSmooth, !- Roughness
0.0299387330245182,
!- Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
Material:NoMass,
Std Opaque Door Panel, !- Name
MediumRough, !- Roughness
0.123456790123457, !- (corresponds to default RSI-0.12327 or R-0.7) Thermal Resistance {m2-K/W}
0.9, !- Thermal Absorptance
0.7, !- Solar Absorptance
0.7; !- Visible Absorptance
!- =========== ALL OBJECTS IN CLASS: CONSTRUCTION ===========
Construction,
InteriorFurnishings, !- Name
Std Wood 6inch; !- Outside Layer
Construction,
Air_Wall, !- Name
Air_Wall_Material; !- Outside Layer
Construction,
DropCeiling, !- Name
AC02 Acoustic Ceiling; !- Outside Layer
Construction,
OpaqueDoor, !- Name
Std Opaque Door Panel; !- Outside Layer
Construction,
AtticRoofDeck, !- Name
F12 Asphalt shingles, !- Outside Layer
G02 16mm plywood; !- Layer 2
Construction,
int_wall, !- Name
G01 13mm gypsum board, !- Outside Layer
G01 13mm gypsum board; !- Layer 2
Construction,
ext_slab_8in_with_carpet,!- Name
200mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
ext_slab_8in, !- Name
200mm Normalweight concrete floor; !- Outside Layer
Construction,
ext_slab_6in_with_carpet,!- Name
150mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
ext_slab_6in, !- Name
150mm Normalweight concrete floor; !- Outside Layer
Construction,
int_slab_floor, !- Name
100mm Normalweight concrete floor, !- Outside Layer
CP02 CARPET PAD; !- Layer 2
Construction,
int_slab_ceiling, !- Name
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor; !- Layer 2
Construction,
basement_wall, !- Name
M10 200mm concrete block basement wall; !- Outside Layer
Construction,
int_wood_floor, !- Name
AC02 Acoustic Ceiling, !- Outside Layer
G02 16mm plywood, !- Layer 2
CP02 CARPET PAD; !- Layer 3
Construction,
ext_soffit_floor, !- Name
G02 16mm plywood; !- Outside Layer
Construction,
nonres_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Nonres_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
res_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Res_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
semiheated_roof, !- Name
F13 Built-up roofing, !- Outside Layer
Semiheated_Roof_Insulation, !- Layer #2
F08 Metal surface; !- Layer #3
Construction,
nonres_ext_wall, !- Name
F07 25mm stucco, !- Outside Layer
G01 16mm gypsum board, !- Layer #2
Nonres_Exterior_Wall_Insulation, !- Layer #3
G01 16mm gypsum board; !- Layer #4
Construction,
res_ext_wall, !- Name
F07 25mm stucco, !- Outside Layer
G01 16mm gypsum board, !- Layer #1
Res_Exterior_Wall_Insulation, !- Layer #2
G01 16mm gypsum board; !- Layer #3
Construction,
semiheated_ext_wall, !- Name
F07 25mm stucco, !- Outside Layer
G01 16mm gypsum board, !- Layer #1
Semiheated_Exterior_Wall_Insulation, !- Layer #2
G01 16mm gypsum board; !- Layer #3
Construction,
nonres_floor, !- Name
Nonres_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
res_floor, !- Name
Res_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
semiheated_floor, !- Name
Semiheated_Floor_Insulation, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
CP02 CARPET PAD; !- Layer #2
Construction,
nonres_floor_ceiling, !- Name - reverse ordered layers for nonres_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Nonres_Floor_Insulation; !- Layer #2
Construction,
res_floor_ceiling, !- Name - reverse ordered layers for res_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Res_Floor_Insulation; !- Layer #2
Construction,
semiheated_floor_ceiling, !- Name - reverse ordered layers for semiheated_floor
CP02 CARPET PAD, !- Outside Layer
100mm Normalweight concrete floor, !- Layer #1
Semiheated_Floor_Insulation; !- Layer #2
!- =========== ALL OBJECTS IN CLASS: WINDOWMATERIAL:SIMPLEGLAZINGSYSTEM ===========
WindowMaterial:SimpleGlazingSystem,
Res Window Glazing Layer, !- Name
2.0441736, !- U-Factor {W/m2-K}
0.37, !- Solar Heat Gain Coefficient
0.407; !- Visible Transmittance
Construction,
ResWindow_U__SHGC_0.37, !- Name
Res Window Glazing Layer; !- Outside Layer
!- =========== ALL OBJECTS IN CLASS: ZONE ===========
Construction:FfactorGroundFloor,
gFloorC_Ffactor, !- Name
0.751254, !- F-Factor
77.65845299, !- Area
3.352599999999999; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorN1A_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328000002, !- Area
11.5818; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorN2A_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328000002, !- Area
11.581800000000001; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorNEA_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328000002, !- Area
19.201400000000003; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorNWA_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328000001, !- Area
19.2014; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorS1A_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328, !- Area
11.5818; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorS2A_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328, !- Area
11.581800000000001; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorSWA_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328, !- Area
19.2014; !- PerimeterExposed
Construction:FfactorGroundFloor,
gGFloorSEA_Ffactor, !- Name
0.751254, !- F-Factor
88.24868328000002, !- Area
19.2014; !- PerimeterExposed
Zone,
G SW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
0, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G NW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
Office, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
0, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G NE Apartment, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G N1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G N2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G S1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
0, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G S2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
0, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M SW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
0, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M NW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M SE Apartment, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
0, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M NE Apartment, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M N1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M N2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M S1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
0, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M S2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
0, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T SW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
0, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T NW Apartment, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T SE Apartment, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
0, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T NE Apartment, !- Name
0, !- Direction of Relative North {deg}
34.7455054899131, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T N1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T N2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
9.29594664423115, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T S1 Apartment, !- Name
0, !- Direction of Relative North {deg}
11.5818351633044, !- X Origin {m}
0, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T S2 Apartment, !- Name
0, !- Direction of Relative North {deg}
23.1636703266088, !- X Origin {m}
0, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
T Corridor, !- Name
, !- Direction of Relative North {deg}
0, !- X Origin {m}
7.61962839691078, !- Y Origin {m}
9.14355407629293, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
G Corridor, !- Name
0, !- Direction of Relative North {deg}
0, !- X Origin {m}
7.61962839691078, !- Y Origin {m}
0, !- Z Origin {m}
1, !- Type
1; !- Multiplier
Zone,
M Corridor, !- Name
, !- Direction of Relative North {deg}
0, !- X Origin {m}
7.61962839691078, !- Y Origin {m}
3.04785135876431, !- Z Origin {m}
1, !- Type
1; !- Multiplier
!- =========== ALL OBJECTS IN CLASS: ZONE LIST ===========
ZoneList,
Mid Floor List, !- Name
M SW Apartment, !- Zone 1 Name
M NW Apartment, !- Zone 2 Name
M SE Apartment, !- Zone 3 Name
M NE Apartment, !- Zone 4 Name
M N1 Apartment, !- Zone 5 Name
M N2 Apartment, !- Zone 6 Name
M S1 Apartment, !- Zone 7 Name
M S2 Apartment, !- Zone 8 Name
M Corridor; !- Zone 9 Name
!- =========== ALL OBJECTS IN CLASS: ZONE GROUP ===========
ZoneGroup,
Middle Floors, !- Name
Mid Floor List, !- Zone List Name
2; !- Zone List Multiplier
!- =========== ALL OBJECTS IN CLASS: SURFACEGEOMETRY ===========
GlobalGeometryRules,
LowerLeftCorner, !- Starting Vertex Position
CW, !- Vertex Entry Direction
Relative; !- Coordinate System
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER ===========
BuildingSurface:Detailed,
g SWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SWall S1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G S1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SWall S2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G S2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
Office, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NWall N1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G N1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NWall N2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G N2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g WWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g WWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
Office, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor SWA, !- Name
Floor, !- Surface Type
gGFloorSWA_Ffactor, !- Construction Name
G SW Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor SEA, !- Name
Floor, !- Surface Type
gGFloorSEA_Ffactor, !- Construction Name
Office, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor N1A, !- Name
Floor, !- Surface Type
gGFloorN1A_Ffactor, !- Construction Name
G N1 Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor N2A, !- Name
Floor, !- Surface Type
gGFloorN2A_Ffactor, !- Construction Name
G N2 Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor S1A, !- Name
Floor, !- Surface Type
gGFloorS1A_Ffactor, !- Construction Name
G S1 Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor S2A, !- Name
Floor, !- Surface Type
gGFloorS2A_Ffactor, !- Construction Name
G S2 Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor NEA, !- Name
Floor, !- Surface Type
gGFloorNEA_Ffactor, !- Construction Name
G NE Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g GFloor NWA, !- Name
Floor, !- Surface Type
gGFloorNWA_Ffactor, !- Construction Name
G NW Apartment, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin SWA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G SW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin SWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin SEA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
Office, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin SEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin N1A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G N1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin N1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin N2A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G N2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin N2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin S1A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G S1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin S1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin S2A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G S2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin S2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin NEA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G NE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin NEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceilin NWA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G NW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceilin NWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NWall N1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T N1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NWall N2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T N2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t WWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t WWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T SE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor SWA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T SW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor SWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor SEA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T SE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor SEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor N1A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T N1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor N1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor N2A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T N2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor N2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor S1A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T S1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor S1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor S2A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T S2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor S2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor NEA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T NE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor NEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t GFloor NWA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T NW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
t GFloor NWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof SWA, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof SEA, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T SE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof N1A, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T N1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof N2A, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T N2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof S1A, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T S1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof S2A, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T S2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof NEA, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof NWA, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SWall S1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T S1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SWall S2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T S2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T SE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NWall N1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M N1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NWall N2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M N2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m WWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m WWall NWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M NW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M SE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EWall NEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M NE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor SWA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M SW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor SWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor SEA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M SE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor SEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor N1A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M N1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor N1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor N2A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M N2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor N2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor S1A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M S1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor S1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor S2A, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M S2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor S2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor NEA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M NE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor NEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m GFloor NWA, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M NW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m GFloor NWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin SWA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M SW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin SWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin SEA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M SE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin SEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin N1A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M N1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin N1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin N2A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M N2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin N2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin S1A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M S1 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin S1A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin S2A, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M S2 Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin S2A, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin NEA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M NE Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin NEA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceilin NWA, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M NW Apartment, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceilin NWA, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SWall SWA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M SW Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SWall S1A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M S1 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SWall S2A, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M S2 Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SWall SEA, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M SE Apartment, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m WWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,1.676318,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
M Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
46.327341,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,1.676318,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Ceiling C, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
M Corridor, !- Zone Name
Surface, !- Outside Boundary Condition
m Ceiling C, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m Floor C, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
M Corridor, !- Zone Name
Surface, !- Outside Boundary Condition
m Floor C, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,1.676318,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t WWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,1.676318,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
T Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
46.327341,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,1.676318,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Roof C, !- Name
Roof, !- Surface Type
res_roof, !- Construction Name
T Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t Floor C, !- Name
Floor, !- Surface Type
ext_slab_8in_with_carpet,!- Construction Name
T Corridor, !- Zone Name
Surface, !- Outside Boundary Condition
t Floor C, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,1.676318,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g WWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,1.676318,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EWall C, !- Name
Wall, !- Surface Type
res_ext_wall, !- Construction Name
G Corridor, !- Zone Name
Outdoors, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
SunExposed, !- Sun Exposure
WindExposed, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
46.327341,0.000000,0, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,1.676318,0; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Ceiling C, !- Name
Ceiling, !- Surface Type
int_slab_ceiling, !- Construction Name
G Corridor, !- Zone Name
Surface, !- Outside Boundary Condition
g Ceiling C, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
0.000000,1.676318,3.047851, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,3.047851, !- X,Y,Z ==> Vertex 3 {m}
46.327341,0.000000,3.047851; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g Floor C, !- Name
Floor, !- Surface Type
gFloorC_Ffactor, !- Construction Name
G Corridor, !- Zone Name
GroundFCfactorMethod, !- Outside Boundary Condition
, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341,0.000000,0.000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341,1.676318,0.000000, !- X,Y,Z ==> Vertex 3 {m}
0.000000,1.676318,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NIWall SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G S1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NIWall S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G S2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NIWall S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
Office, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g NIWall SEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
Office, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SIWall NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G N1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SIWall N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G N2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SIWall N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g EIWALL N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G NE Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
g SIWall NEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
G NE Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
G Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NIWall SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M S1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NIWall S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M S2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NIWall S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M SE Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m NIWall SEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M SE Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SIWall NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M N1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SIWall N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M N2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SIWall N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m EIWALL N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M NE Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
m SIWall NEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
M NE Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
M Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NIWall SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL SWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T SW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T S1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NIWall S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL S1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T S1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T S2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NIWall S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL S2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T S2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T SE Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t NIWall SEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T SE Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,7.619628,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 2 {m}
0.000000,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
0.000000,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SIWall NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL NWA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T NW Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T N1 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SIWall N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL N1A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T N1 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T N2 Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SIWall N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t EIWALL N2A, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T N2 Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T NE Apartment, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
11.581835,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,7.619628,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,7.619628,0.000000; !- X,Y,Z ==> Vertex 4 {m}
BuildingSurface:Detailed,
t SIWall NEA, !- Name
Wall, !- Surface Type
int_wall, !- Construction Name
T NE Apartment, !- Zone Name
Zone, !- Outside Boundary Condition
T Corridor, !- Outside Boundary Condition Object
NoSun, !- Sun Exposure
NoWind, !- Wind Exposure
autocalculate, !- View Factor to Ground
4, !- Number of Vertices
0.000000,0.000000,0.000000, !- X,Y,Z ==> Vertex 1 {m}
0.000000,0.000000,3.047851, !- X,Y,Z ==> Vertex 2 {m}
11.581835,0.000000,3.047851, !- X,Y,Z ==> Vertex 3 {m}
11.581835,0.000000,0.000000; !- X,Y,Z ==> Vertex 4 {m}
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:SUB ===========
FenestrationSurface:Detailed,
GWindow1 S SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g SWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 S S1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g SWall S1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 S S2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g SWall S2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 S SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g SWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 S SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m SWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 S S1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m SWall S1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 S S2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m SWall S2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 S SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m SWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 S SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t SWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 S S1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t SWall S1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 S S2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t SWall S2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 S SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t SWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
2.895, !- Vertex 1 X-coordinate {m}
0, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
2.895, !- Vertex 2 X-coordinate {m}
0, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
8.68601049868766, !- Vertex 3 X-coordinate {m}
0, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
8.68601049868766, !- Vertex 4 X-coordinate {m}
0, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 W NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g WWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 W SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g WWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 W NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m WWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 W SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m WWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 W NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t WWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 W SWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t WWall SWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
0, !- Vertex 1 X-coordinate {m}
5.678, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
0, !- Vertex 2 X-coordinate {m}
5.678, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
0, !- Vertex 3 X-coordinate {m}
1.868, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
0, !- Vertex 4 X-coordinate {m}
1.868, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 E NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g EWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 E SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g EWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 E NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m EWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 E SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m EWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 E NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t EWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 E SEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t EWall SEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
11.5818, !- Vertex 1 X-coordinate {m}
1.9049, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
11.5818, !- Vertex 2 X-coordinate {m}
1.9049, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
11.5818, !- Vertex 3 X-coordinate {m}
5.7149, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
11.5818, !- Vertex 4 X-coordinate {m}
5.7149, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 N NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g NWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 N N1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g NWall N1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 N N2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g NWall N2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
GWindow1 N NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g NWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 N NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m NWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 N N1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m NWall N1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 N N2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m NWall N2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
MWindow1 N NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
m NWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 N NWA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t NWall NWA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 N N1A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t NWall N1A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 N N2A, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t NWall N2A, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
TWindow1 N NEA, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
t NWall NEA, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
8.686, !- Vertex 1 X-coordinate {m}
7.6196, !- Vertex 1 Y-coordinate {m}
0.954, !- Vertex 1 Z-coordinate {m}
8.686, !- Vertex 2 X-coordinate {m}
7.6196, !- Vertex 2 Y-coordinate {m}
2.1732, !- Vertex 2 Z-coordinate {m}
2.89498950131234, !- Vertex 3 X-coordinate {m}
7.6196, !- Vertex 3 Y-coordinate {m}
2.1732, !- Vertex 3 Z-coordinate {m}
2.89498950131234, !- Vertex 4 X-coordinate {m}
7.6196, !- Vertex 4 Y-coordinate {m}
0.954; !- Vertex 4 Z-coordinate {m}
FenestrationSurface:Detailed,
Entrance Door, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name of the Surface
g EWall C, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
46.327341000000,0.050800000000,0.025400000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341000000,0.050800000000,2.133500000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341000000,1.625500000000,2.133500000000, !- X,Y,Z ==> Vertex 3 {m}
46.327341000000,1.625500000000,0.025400000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
MWindow14, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name
m EWall C, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
46.327341000000,0.381000000000,0.954000000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341000000,0.381000000000,2.173100000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341000000,1.295300000000,2.173100000000, !- X,Y,Z ==> Vertex 3 {m}
46.327341000000,1.295300000000,0.954000000000; !- X,Y,Z ==> Vertex 4 {m}
FenestrationSurface:Detailed,
TWindow14, !- Name
Window, !- Surface Type
ResWindow_U__SHGC_0.37, !- Construction Name
t EWall C, !- Building Surface Name
, !- Outside Boundary Condition Object
autocalculate, !- View Factor to Ground
, !- Frame and Divider Name
1, !- Multiplier
4, !- Number of Vertices
46.327341000000,0.381000000000,0.954000000000, !- X,Y,Z ==> Vertex 1 {m}
46.327341000000,0.381000000000,2.173100000000, !- X,Y,Z ==> Vertex 2 {m}
46.327341000000,1.295300000000,2.173100000000, !- X,Y,Z ==> Vertex 3 {m}
46.327341000000,1.295300000000,0.954000000000; !- X,Y,Z ==> Vertex 4 {m}
!- =========== ALL OBJECTS IN CLASS: SURFACE:HEATTRANSFER:INTERNALMASS ===========
InternalMass,
G InternalMass SWA, !- Name
InteriorFurnishings, !- Construction Name
G SW Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass NWA, !- Name
InteriorFurnishings, !- Construction Name
G NW Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass SEA, !- Name
InteriorFurnishings, !- Construction Name
Office, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass NEA, !- Name
InteriorFurnishings, !- Construction Name
G NE Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass N1A, !- Name
InteriorFurnishings, !- Construction Name
G N1 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass N2A, !- Name
InteriorFurnishings, !- Construction Name
G N2 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass S1A, !- Name
InteriorFurnishings, !- Construction Name
G S1 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
G InternalMass S2A, !- Name
InteriorFurnishings, !- Construction Name
G S2 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
M InternalMass SWA, !- Name
InteriorFurnishings, !- Construction Name
M SW Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass NWA, !- Name
InteriorFurnishings, !- Construction Name
M NW Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass SEA, !- Name
InteriorFurnishings, !- Construction Name
M SE Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass NEA, !- Name
InteriorFurnishings, !- Construction Name
M NE Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass N1A, !- Name
InteriorFurnishings, !- Construction Name
M N1 Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass N2A, !- Name
InteriorFurnishings, !- Construction Name
M N2 Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass S1A, !- Name
InteriorFurnishings, !- Construction Name
M S1 Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
M InternalMass S2A, !- Name
InteriorFurnishings, !- Construction Name
M S2 Apartment, !- Zone Name
176.498545342438; !- Surface Area {m2}
InternalMass,
T InternalMass SWA, !- Name
InteriorFurnishings, !- Construction Name
T SW Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass NWA, !- Name
InteriorFurnishings, !- Construction Name
T NW Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass SEA, !- Name
InteriorFurnishings, !- Construction Name
T SE Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass NEA, !- Name
InteriorFurnishings, !- Construction Name
T NE Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass N1A, !- Name
InteriorFurnishings, !- Construction Name
T N1 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass N2A, !- Name
InteriorFurnishings, !- Construction Name
T N2 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass S1A, !- Name
InteriorFurnishings, !- Construction Name
T S1 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
InternalMass,
T InternalMass S2A, !- Name
InteriorFurnishings, !- Construction Name
T S2 Apartment, !- Zone Name
88.249272671219; !- Surface Area {m2}
!- =========== ALL OBJECTS IN CLASS: SCHEDULETYPE ===========
ScheduleTypeLimits,
Fraction, !- Name
0, !- Lower Limit Value
1, !- Upper Limit Value
Continuous; !- Numeric Type
ScheduleTypeLimits,
Temperature, !- Name
-100, !- Lower Limit Value
100, !- Upper Limit Value
Continuous; !- Numeric Type
ScheduleTypeLimits,
Any Number; !- Name
ScheduleTypeLimits,
COMPACT HVAC Any Number; !- Name
!- =========== ALL OBJECTS IN CLASS: SCHEDULE:COMPACT ===========
Schedule:Compact,
OCC_APT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 7:00,1.0, !- Field 3
Until: 8:00,0.85, !- Field 5
Until: 9:00,0.39, !- Field 7
Until: 16:00,0.25, !- Field 9
Until: 17:00,0.3, !- Field 11
Until: 18:00,0.52, !- Field 13
Until: 21:00,0.87, !- Field 15
Until: 24:00,1.0; !- Field 17
Schedule:Compact,
OCC_OFF_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: Weekdays, !- Field 2
Until: 8:00,0.0, !- Field 3
Until: 12:00,1.0, !- Field 5
Until: 13:00,0.5, !- Field 7
Until: 17:00,1.0, !- Field 9
Until: 24:00,0.0, !- Field 11
For AllOtherDays, !- Field 13
Until: 24:00,0.0; !- Field 14
Schedule:Compact,
OCC_OFF_w_SB_SCH, !-Name
Fraction, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0,
Until: 08:00, 0,
Until: 09:00, 1,
Until: 10:00, 1,
Until: 11:00, 1,
Until: 12:00, 1,
Until: 13:00, 0,
Until: 14:00, 1,
Until: 15:00, 0,
Until: 16:00, 1,
Until: 17:00, 1,
Until: 18:00, 0,
Until: 19:00, 0,
Until: 20:00, 0,
Until: 21:00, 0,
Until: 22:00, 0,
Until: 23:00, 0,
Until: 24:00, 0,
For: AllOtherDays,
Until: 01:00, 0,
Until: 02:00, 0,
Until: 03:00, 0,
Until: 04:00, 0,
Until: 05:00, 0,
Until: 06:00, 0,
Until: 07:00, 0,
Until: 08:00, 0,
Until: 09:00, 0,
Until: 10:00, 0,
Until: 11:00, 0,
Until: 12:00, 0,
Until: 13:00, 0,
Until: 14:00, 0,
Until: 15:00, 0,
Until: 16:00, 0,
Until: 17:00, 0,
Until: 18:00, 0,
Until: 19:00, 0,
Until: 20:00, 0,
Until: 21:00, 0,
Until: 22:00, 0,
Until: 23:00, 0,
Until: 24:00, 0;
Schedule:Compact,
LTG_APT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 4:00,0.011316031, !- Field 3
Until: 5:00,0.033948092, !- Field 5
Until: 6:00,0.0735542, !- Field 7
Until: 7:00,0.079212215, !- Field 9
Until: 8:00,0.0735542, !- Field 11
Until: 9:00,0.033948092, !- Field 13
Until: 15:00,0.022632061,!- Field 15
Until: 16:00,0.039606108,!- Field 17
Until: 17:00,0.079212215,!- Field 19
Until: 18:00,0.113160307,!- Field 21
Until: 19:00,0.152766415,!- Field 23
Until: 21:00,0.181056492,!- Field 25
Until: 22:00,0.124476338,!- Field 27
Until: 23:00,0.067896184,!- Field 29
Until: 24:00,0.028290077;!- Field 31
Schedule:Compact,
LTG_COR_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.53144; !- Field 3
Schedule:Compact,
LTG_OFF_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 2
Until: 24:00,1, !- Field 3
For: WinterDesignDay, !- Field 5
Until: 24:00,0, !- Field 6
For: Weekdays, !- Field 8
Until: 8:00,0.18, !- Field 9
Until: 12:00,0.76932, !- Field 11
Until: 13:00,0.68384, !- Field 13
Until: 17:00,0.76932, !- Field 15
Until: 24:00,0.18, !- Field 17
For: AllOtherDays, !- Field 19
Until: 24:00,0.18; !- Field 20
Schedule:Compact,
EQP_APT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 1:00,0.45, !- Field 3
Until: 2:00,0.41, !- Field 5
Until: 3:00,0.39, !- Field 7
Until: 5:00,0.38, !- Field 9
Until: 6:00,0.43, !- Field 11
Until: 7:00,0.54, !- Field 13
Until: 8:00,0.65, !- Field 15
Until: 9:00,0.66, !- Field 17
Until: 10:00,0.67, !- Field 19
Until: 11:00,0.69, !- Field 21
Until: 12:00,0.70, !- Field 23
Until: 13:00,0.69, !- Field 25
Until: 14:00,0.66, !- Field 27
Until: 15:00,0.65, !- Field 29
Until: 16:00,0.68, !- Field 31
Until: 17:00,0.80, !- Field 33
Until: 19:00,1.0, !- Field 35
Until: 20:00,0.93, !- Field 37
Until: 21:00,0.89, !- Field 39
Until: 22:00,0.85, !- Field 41
Until: 23:00,0.71, !- Field 43
Until: 24:00,0.58; !- Field 45
Schedule:Compact,
EQP_OFF_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 19
Until: 24:00,1, !- Field 20
For: WinterDesignDay, !- Field 21
Until: 24:00,0, !- Field 22
For: Weekdays, !- Field 2
Until: 7:00,0.218625, !- Field 3
Until: 8:00,0.33125, !- Field 5
Until: 12:00,0.92575, !- Field 7
Until: 13:00,0.870205, !- Field 9
Until: 17:00,0.92575, !- Field 11
Until: 18:00,0.33125, !- Field 13
Until: 24:00,0.218625, !- Field 15
For AllOtherDays, !- Field 17
Until: 24:00,0.218625; !- Field 18
Schedule:Compact,
INF_APT_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
INF_OFF_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
INF_COR_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1.0; !- Field 3
Schedule:Compact,
INFIL_Door_Opening_SCH, !- Name
fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 06:00,0.0, !- Field 3
Until: 07:00,0.131, !- Field 5
Until: 08:00,1.0, !- Field 7
Until: 17:00,0.131, !- Field 9
Until: 18:00,1.0, !- Field 11
Until: 22:00,0.131, !- Field 13
Until: 24:00,0.0; !- Field 15
Schedule:Compact,
HTGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00,21.1; !- Field 3
Schedule:Compact,
CLGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00,24; !- Field 3
Schedule:Compact,
S HTGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00, !- Field 3
21.1; !- Field 4
Schedule:Compact,
S CLGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00, !- Field 3
24; !- Field 4
Schedule:Compact,
N HTGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00, !- Field 3
21.1; !- Field 4
Schedule:Compact,
N CLGSETP_APT_SCH, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR:AllDays, !- Field 2
UNTIL: 24:00, !- Field 3
24; !- Field 4
Schedule:Compact,
HTGSETP_OFF_SCH_NO_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: WinterDesignDay, !- Field 2
UNTIL: 7:00,15.6, !- Field 3
UNTIL: 8:00,18.3, !- Field 5
UNTIL:17:00,21.1, !- Field 7
UNTIL: 18:00,18.3, !- Field 9
UNTIL: 24:00,15.6, !- Field 11
FOR: Weekdays, !- Field 13
UNTIL: 7:00,15.6, !- Field 14
UNTIL: 8:00,21.1, !- Field 16
UNTIL:17:00,21.1, !- Field 18
UNTIL: 18:00,18.3, !- Field 20
UNTIL: 24:00,15.6, !- Field 22
FOR: SummerDesignDay AllOtherDays, !- Field 24
UNTIL: 24:00,15.6; !- Field 25
Schedule:Compact,
HTGSETP_OFF_SCH_NO_OPTIMUM_W_SB, !-Name
Temperature, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 15.6,
Until: 02:00, 15.6,
Until: 03:00, 15.6,
Until: 04:00, 15.6,
Until: 05:00, 15.6,
Until: 06:00, 15.6,
Until: 07:00, 15.6,
Until: 08:00, 21.1,
Until: 09:00, 21.1,
Until: 10:00, 21.1,
Until: 11:00, 21.1,
Until: 12:00, 21.1,
Until: 13:00, 20.5444444444444,
Until: 14:00, 21.1,
Until: 15:00, 20.5444444444444,
Until: 16:00, 21.1,
Until: 17:00, 21.1,
Until: 18:00, 18.3,
Until: 19:00, 15.6,
Until: 20:00, 15.6,
Until: 21:00, 15.6,
Until: 22:00, 15.6,
Until: 23:00, 15.6,
Until: 24:00, 15.6,
For: WinterDesignDay,
Until: 7:00,15.6,
Until: 8:00,18.3,
Until:17:00,21.1,
Until: 18:00,18.3,
Until: 24:00,15.6,
For: SummerDesignDay,
Until: 24:00,15.6,
For: AllOtherDays,
Until: 01:00, 15.6,
Until: 02:00, 15.6,
Until: 03:00, 15.6,
Until: 04:00, 15.6,
Until: 05:00, 15.6,
Until: 06:00, 15.6,
Until: 07:00, 15.6,
Until: 08:00, 15.6,
Until: 09:00, 15.6,
Until: 10:00, 15.6,
Until: 11:00, 15.6,
Until: 12:00, 15.6,
Until: 13:00, 15.6,
Until: 14:00, 15.6,
Until: 15:00, 15.6,
Until: 16:00, 15.6,
Until: 17:00, 15.6,
Until: 18:00, 15.6,
Until: 19:00, 15.6,
Until: 20:00, 15.6,
Until: 21:00, 15.6,
Until: 22:00, 15.6,
Until: 23:00, 15.6,
Until: 24:00, 15.6;
Schedule:Compact,
HTGSETP_OFF_SCH_YES_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: WinterDesignDay, !- Field 2
UNTIL: 7:00,15.6, !- Field 3
UNTIL: 8:00,18.3, !- Field 5
UNTIL: 17:00,21.1, !- Field 7
UNTIL: 18:00,18.3, !- Field 9
UNTIL: 24:00,15.6, !- Field 11
FOR: Weekdays, !- Field 13
UNTIL: 7:00,15.6, !- Field 14
UNTIL: 8:00,17.8, !- Field 16
UNTIL: 9:00,20.0, !- Field 18
UNTIL: 17:00,21.1, !- Field 20
UNTIL: 18:00,18.3, !- Field 22
UNTIL: 24:00,15.6, !- Field 24
FOR: SummerDesignDay AllOtherDays, !- Field 26
UNTIL: 24:00,15.6; !- Field 27
Schedule:Compact,
CLGSETP_OFF_SCH_NO_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: SummerDesignDay, !- Field 2
UNTIL: 7:00,29.4, !- Field 3
UNTIL: 8:00,26.7, !- Field 5
UNTIL:17:00,24, !- Field 7
UNTIL: 18:00,26.7, !- Field 9
UNTIL: 24:00,29.4, !- Field 11
FOR:Weekdays, !- Field 13
UNTIL: 7:00,29.4, !- Field 14
UNTIL: 8:00,24, !- Field 16
UNTIL:17:00,24, !- Field 18
UNTIL: 18:00,26.7, !- Field 20
UNTIL: 24:00,29.4, !- Field 22
FOR: WinterDesignDay AllOtherDays, !- Field 24
UNTIL: 24:00,29.4; !- Field 25
Schedule:Compact,
CLGSETP_OFF_SCH_NO_OPTIMUM_W_SB, !-Name
Temperature, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 29.4,
Until: 02:00, 29.4,
Until: 03:00, 29.4,
Until: 04:00, 29.4,
Until: 05:00, 29.4,
Until: 06:00, 29.4,
Until: 07:00, 29.4,
Until: 08:00, 23.9,
Until: 09:00, 23.9,
Until: 10:00, 23.9,
Until: 11:00, 23.9,
Until: 12:00, 23.9,
Until: 13:00, 24.4555555555556,
Until: 14:00, 23.9,
Until: 15:00, 24.4555555555556,
Until: 16:00, 23.9,
Until: 17:00, 23.9,
Until: 18:00, 26.7,
Until: 19:00, 29.4,
Until: 20:00, 29.4,
Until: 21:00, 29.4,
Until: 22:00, 29.4,
Until: 23:00, 29.4,
Until: 24:00, 29.4,
For: SummerDesignDay,
Until: 7:00,29.4,
Until: 8:00,26.7,
Until:17:00,23.9,
Until: 18:00,26.7,
Until: 24:00,29.4,
For: WinterDesignDay,
Until: 24:00,29.4,
For: AllOtherDays,
Until: 01:00, 29.4,
Until: 02:00, 29.4,
Until: 03:00, 29.4,
Until: 04:00, 29.4,
Until: 05:00, 29.4,
Until: 06:00, 29.4,
Until: 07:00, 29.4,
Until: 08:00, 29.4,
Until: 09:00, 29.4,
Until: 10:00, 29.4,
Until: 11:00, 29.4,
Until: 12:00, 29.4,
Until: 13:00, 29.4,
Until: 14:00, 29.4,
Until: 15:00, 29.4,
Until: 16:00, 29.4,
Until: 17:00, 29.4,
Until: 18:00, 29.4,
Until: 19:00, 29.4,
Until: 20:00, 29.4,
Until: 21:00, 29.4,
Until: 22:00, 29.4,
Until: 23:00, 29.4,
Until: 24:00, 29.4;
Schedule:Compact,
CLGSETP_OFF_SCH_YES_OPTIMUM, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: SummerDesignDay, !- Field 2
UNTIL: 7:00,29.4, !- Field 3
UNTIL: 8:00,26.7, !- Field 5
UNTIL: 17:00,24, !- Field 7
UNTIL: 18:00,26.7, !- Field 9
UNTIL: 24:00,29.4, !- Field 11
FOR:Weekdays, !- Field 13
UNTIL: 7:00,29.4, !- Field 14
UNTIL: 8:00,27.8, !- Field 16
UNTIL: 9:00,25.6, !- Field 18
UNTIL: 17:00,24, !- Field 20
UNTIL: 18:00,26.7, !- Field 22
UNTIL: 24:00,29.4, !- Field 24
FOR: WinterDesignDay AllOtherDays, !- Field 26
UNTIL: 24:00,29.4; !- Field 27
Schedule:Compact,
CLGSETP_OFF_SCH_No_Setback, !- Name
Temperature, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: SummerDesignDay, !- Field 2
UNTIL: 7:00,29.4, !- Field 3
UNTIL: 8:00,26.7, !- Field 5
UNTIL: 17:00,23.9, !- Field 7
UNTIL: 18:00,26.7, !- Field 9
UNTIL: 24:00,29.4, !- Field 11
FOR:Weekdays, !- Field 13
UNTIL: 7:00,23.9, !- Field 14
UNTIL: 8:00,23.9, !- Field 16
UNTIL:17:00,23.9, !- Field 18
UNTIL: 18:00,23.9, !- Field 20
UNTIL: 24:00,23.9, !- Field 22
FOR: WinterDesignDay AllOtherDays, !- Field 24
UNTIL: 24:00,23.9; !- Field 25
Schedule:Compact,
Activity Schedule, !- Name
Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,95; !- Field 3
Schedule:Compact,
All Off, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0.0; !- Field 3
Schedule:Compact,
All On, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
AllOn_Except_DD, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 1
Until: 24:00,0, !- Field 2
For: WinterDesignDay, !- Field 3
Until: 24:00,0, !- Field 4
For: AllOtherDays, !- Field 5
Until: 24:00,1; !- Field 6
Schedule:Compact,
Exterior_Lgt_ALWAYS_ON, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
COMPACT HVAC-ALWAYS 1, !- Name
COMPACT HVAC Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
ZONE CONTROL TYPE SCHED, !- Name
Control Type, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: SummerDesignDay, !- Field 5
Until: 24:00,2, !- Field 6
For: WinterDesignDay, !- Field 8
Until: 24:00,1, !- Field 9
For: Weekdays Weekends Holidays Customday1 Customday2 AllOtherDays, !- Field 2
Until: 24:00,4; !- Field 3
Schedule:Compact,
FAN_OFF_w_SB_SCH, !-Name
Fraction, !-Schedule Type Limits Name
Through: 12/31,
For: Weekdays,
Until: 01:00, 1,
Until: 02:00, 1,
Until: 03:00, 1,
Until: 04:00, 1,
Until: 05:00, 1,
Until: 06:00, 1,
Until: 07:00, 1,
Until: 08:00, 1,
Until: 09:00, 1,
Until: 10:00, 1,
Until: 11:00, 1,
Until: 12:00, 1,
Until: 13:00, 0,
Until: 14:00, 1,
Until: 15:00, 0,
Until: 16:00, 1,
Until: 17:00, 1,
Until: 18:00, 1,
Until: 19:00, 1,
Until: 20:00, 1,
Until: 21:00, 1,
Until: 22:00, 1,
Until: 23:00, 1,
Until: 24:00, 1,
For: AllOtherDays,
Until: 01:00, 1,
Until: 02:00, 1,
Until: 03:00, 1,
Until: 04:00, 1,
Until: 05:00, 1,
Until: 06:00, 1,
Until: 07:00, 1,
Until: 08:00, 1,
Until: 09:00, 1,
Until: 10:00, 1,
Until: 11:00, 1,
Until: 12:00, 1,
Until: 13:00, 1,
Until: 14:00, 1,
Until: 15:00, 1,
Until: 16:00, 1,
Until: 17:00, 1,
Until: 18:00, 1,
Until: 19:00, 1,
Until: 20:00, 1,
Until: 21:00, 1,
Until: 22:00, 1,
Until: 23:00, 1,
Until: 24:00, 1;
Schedule:Compact,
COMPACT HVAC-ALWAYS 4, !- Name
COMPACT HVAC Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,4; !- Field 3
Schedule:Compact,
COMPACT HVAC-ALWAYS 0, !- Name
COMPACT HVAC Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,0; !- Field 3
Schedule:Compact,
APT_DHW_SCH, !- Name
Fraction, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: AllDays, !- Field 2
UNTIL: 1:00,0.08, !- Field 3
UNTIL: 2:00,0.04, !- Field 5
UNTIL: 3:00,0.01, !- Field 7
UNTIL: 4:00,0.01, !- Field 9
UNTIL: 5:00,0.04, !- Field 11
UNTIL: 6:00,0.27, !- Field 13
UNTIL: 7:00,0.94, !- Field 15
UNTIL: 8:00,1.00, !- Field 17
UNTIL: 9:00,0.96, !- Field 19
UNTIL: 10:00,0.84, !- Field 21
UNTIL: 11:00,0.76, !- Field 23
UNTIL: 12:00,0.61, !- Field 25
UNTIL: 13:00,0.53, !- Field 27
UNTIL: 14:00,0.47, !- Field 29
UNTIL: 15:00,0.41, !- Field 31
UNTIL: 16:00,0.47, !- Field 33
UNTIL: 17:00,0.55, !- Field 35
UNTIL: 18:00,0.73, !- Field 37
UNTIL: 19:00,0.86, !- Field 39
UNTIL: 20:00,0.82, !- Field 41
UNTIL: 21:00,0.75, !- Field 43
UNTIL: 22:00,0.61, !- Field 45
UNTIL: 23:00,0.53, !- Field 47
UNTIL: 24:00,0.29; !- Field 49
Schedule:Compact,
Hot Water Setpoint Temp Schedule, !- Name
Any Number, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: AllDays, !- Field 2
UNTIL: 24:00,60.0; !- Field 3
Schedule:Compact,
Constant Mains Temp Schedule, !- Name
Any Number, !- Schedule Type Limits Name
THROUGH: 12/31, !- Field 1
FOR: AllDays, !- Field 2
UNTIL: 24:00,12.0; !- Field 3
Schedule:Compact,
COMPACT HVAC-ALWAYS 18.3333338190008, !- Name
COMPACT HVAC Any Number, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,18.3333338190008; !- Field 3
Schedule:Compact,
Exterior_Ltg_Sch, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 07:00,1.0, !- Field 3
Until: 19:00,0.0, !- Field 5
Until: 24:00,1.0; !- Field 7
SCHEDULE:COMPACT,
BLDG_ELEVATORS, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 24:00,0.05, !- Field 3
For: SummerDesignDay, !- Field 5
Until: 24:00,0.5, !- Field 6
For: Allotherdays, !- Field 8
Until: 04:00,0.05, !- Field 9
Until: 05:00,0.10, !- Field 11
Until: 06:00,0.20, !- Field 13
Until: 07:00,0.40, !- Field 15
Until: 09:00,0.50, !- Field 17
Until: 10:00,0.35, !- Field 19
Until: 16:00,0.15, !- Field 21
Until: 17:00,0.35, !- Field 23
Until: 19:00,0.50, !- Field 25
Until: 21:00,0.40, !- Field 27
Until: 22:00,0.30, !- Field 29
Until: 23:00,0.20, !- Field 31
Until: 24:00,0.10; !- Field 33
Schedule:Compact,
ELEV_LIGHT_FAN_SCH_24_7, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: AllDays, !- Field 2
Until: 24:00,1; !- Field 3
Schedule:Compact,
ELEV_LIGHT_FAN_SCH_ADD_DF, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay, !- Field 2
Until: 24:00,0.05, !- Field 3
For: SummerDesignDay, !- Field 5
Until: 24:00,0.5, !- Field 6
For: Allotherdays, !- Field 8
Until: 04:00,0.05, !- Field 9
Until: 05:00,0.10, !- Field 11
Until: 06:00,0.20, !- Field 13
Until: 07:00,0.40, !- Field 15
Until: 09:00,0.50, !- Field 17
Until: 10:00,0.35, !- Field 19
Until: 16:00,0.15, !- Field 21
Until: 17:00,0.35, !- Field 23
Until: 19:00,0.50, !- Field 25
Until: 21:00,0.40, !- Field 27
Until: 22:00,0.30, !- Field 29
Until: 23:00,0.20, !- Field 31
Until: 24:00,0.10; !- Field 33
!- =========== ALL OBJECTS IN CLASS: PEOPLE ===========
People,
Occup_GSW, !- Name
G SW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GNW, !- Name
G NW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_Office, !- Name
Office, !- Zone or ZoneList Name
OCC_OFF_w_SB_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
1, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GNE, !- Name
G NE Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GN1, !- Name
G N1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GN2, !- Name
G N2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GS1, !- Name
G S1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_GS2, !- Name
G S2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MSW, !- Name
M SW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MNW, !- Name
M NW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MSE, !- Name
M SE Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MNE, !- Name
M NE Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MN1, !- Name
M N1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MN2, !- Name
M N2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MS1, !- Name
M S1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_MS2, !- Name
M S2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TSW, !- Name
T SW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TNW, !- Name
T NW Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TSE, !- Name
T SE Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TNE, !- Name
T NE Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TN1, !- Name
T N1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TN2, !- Name
T N2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TS1, !- Name
T S1 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
People,
Occup_TS2, !- Name
T S2 Apartment, !- Zone or ZoneList Name
OCC_APT_SCH, !- Number of People Schedule Name
People, !- Number of People Calculation Method
2.5, !- Number of People
, !- People per Zone Floor Area {person/m2}
, !- Zone Floor Area per Person {m2/person}
1, !- Fraction Radiant
autosize, !- Sensible Heat Fraction
Activity Schedule; !- Activity Level Schedule Name
!- =========== ALL OBJECTS IN CLASS: LIGHTS ===========
Lights,
Lighting_hardwired_GSW, !- Name
G SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GNW, !- Name
G NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_Office, !- Name
Office, !- Zone or ZoneList Name
LTG_OFF_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
7.965293709, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GNE, !- Name
G NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GN1, !- Name
G N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GN2, !- Name
G N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GS1, !- Name
G S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GS2, !- Name
G S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MSW, !- Name
M SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MNW, !- Name
M NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MSE, !- Name
M SE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MNE, !- Name
M NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MN1, !- Name
M N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MN2, !- Name
M N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MS1, !- Name
M S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MS2, !- Name
M S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TSW, !- Name
T SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TNW, !- Name
T NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TSE, !- Name
T SE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TNE, !- Name
T NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TN1, !- Name
T N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TN2, !- Name
T N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TS1, !- Name
T S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TS2, !- Name
T S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
6.45834625, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_GC, !- Name
G Corridor, !- Zone or ZoneList Name
LTG_COR_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
5.295843925,!- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_MC, !- Name
M Corridor, !- Zone or ZoneList Name
LTG_COR_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
5.295843925,!- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_hardwired_TC, !- Name
T Corridor, !- Zone or ZoneList Name
LTG_COR_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_hardwired Level {W}
5.295843925,!- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsWired, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GSW, !- Name
G SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GNW, !- Name
G NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GNE, !- Name
G NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GN1, !- Name
G N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GN2, !- Name
G N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GS1, !- Name
G S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_GS2, !- Name
G S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MSW, !- Name
M SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MNW, !- Name
M NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MSE, !- Name
M SE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MNE, !- Name
M NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MN1, !- Name
M N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MN2, !- Name
M N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MS1, !- Name
M S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_MS2, !- Name
M S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TSW, !- Name
T SW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TNW, !- Name
T NW Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TSE, !- Name
T SE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TNE, !- Name
T NE Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TN1, !- Name
T N1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TN2, !- Name
T N2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TS1, !- Name
T S1 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
Lights,
Lighting_plugin_TS2, !- Name
T S2 Apartment, !- Zone or ZoneList Name
LTG_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Lighting_plugin Level {W}
2.906255813, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Return Air Fraction
0.6000, !- Fraction Radiant
0.2000, !- Fraction Visible
1.0000, !- Fraction Replaceable
LightsPlugIn, !- End-Use Subcategory
No; !- Return Air Fraction Calculated from Plenum Temperature
!- =========== ALL OBJECTS IN CLASS: ELECTRIC EQUIPMENT ===========
ElectricEquipment,
Plug_GSW, !- Name
G SW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GNW, !- Name
G NW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_Office, !- Name
Office, !- Zone or ZoneList Name
EQP_OFF_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GNE, !- Name
G NE Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GN1, !- Name
G N1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GN2, !- Name
G N2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GS1, !- Name
G S1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_GS2, !- Name
G S2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MSW, !- Name
M SW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MNW, !- Name
M NW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MSE, !- Name
M SE Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MNE, !- Name
M NE Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MN1, !- Name
M N1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MN2, !- Name
M N2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MS1, !- Name
M S1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_MS2, !- Name
M S2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TSW, !- Name
T SW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TNW, !- Name
T NW Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TSE, !- Name
T SE Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TNE, !- Name
T NE Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TN1, !- Name
T N1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TN2, !- Name
T N2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TS1, !- Name
T S1 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
Plug_TS2, !- Name
T S2 Apartment, !- Zone or ZoneList Name
EQP_APT_SCH, !- Schedule Name
Watts/Area, !- Design Level Calculation Method
, !- Design Level {W}
6.67, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0, !- Fraction Latent
0.5, !- Fraction Radiant
0, !- Fraction Lost
MiscPlug; !- End-Use Subcategory
ElectricEquipment,
G Corridor_Elevators_Equip, !- Name
G Corridor, !- Zone or ZoneList Name
BLDG_ELEVATORS, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
16054.9450549451, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.0000, !- Fraction Radiant
0.9500, !- Fraction Lost
ElevatorLift; !- End-Use Subcategory
ElectricEquipment,
Elevators_Lights_Fan, !- Name
G Corridor, !- Zone or ZoneList Name
ELEV_LIGHT_FAN_SCH_ADD_DF, !- Schedule Name
EquipmentLevel, !- Design Level Calculation Method
63, !- Design Level {W}
, !- Watts per Zone Floor Area {W/m2}
, !- Watts per Person {W/person}
0.0000, !- Fraction Latent
0.0000, !- Fraction Radiant
0.9500, !- Fraction Lost
ElevatorLightsFan; !- End-Use Subcategory
!- =========== ALL OBJECTS IN CLASS: INFILTRATION ===========
ZoneInfiltration:DesignFlowRate,
Infil_GSW, !- Name
G SW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GNW, !- Name
G NW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_Office, !- Name
Office, !- Zone or ZoneList Name
INF_OFF_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GNE, !- Name
G NE Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GN1, !- Name
G N1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GN2, !- Name
G N2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GS1, !- Name
G S1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GS2, !- Name
G S2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MSW, !- Name
M SW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MNW, !- Name
M NW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MSE, !- Name
M SE Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MNE, !- Name
M NE Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MN1, !- Name
M N1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MN2, !- Name
M N2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MS1, !- Name
M S1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MS2, !- Name
M S2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_SW, !- Name
T SW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000226844352, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_NW, !- Name
T NW Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000226844352, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_SE, !- Name
T SE Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000226844352, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_NE, !- Name
T NE Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000226844352, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_TN1, !- Name
T N1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000162551872, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_TN2, !- Name
T N2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000162551872, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_TS1, !- Name
T S1 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000162551872, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_TS2, !- Name
T S2 Apartment, !- Zone or ZoneList Name
INF_APT_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.000162551872, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_GC, !- Name
G Corridor, !- Zone or ZoneList Name
INF_COR_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Door_Infil_GC, !- Name
G Corridor, !- Zone or ZoneList Name
INFIL_Door_Opening_SCH, !- Schedule Name
Flow/Zone, !- Design Flow Rate Calculation Method
0.327531218, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
1.0, !- Constant Term Coefficient
0.0, !- Temperature Term Coefficient
0.0, !- Velocity Term Coefficient
0.0; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_MC, !- Name
M Corridor, !- Zone or ZoneList Name
INF_COR_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
0.00056896, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
ZoneInfiltration:DesignFlowRate,
Infil_TC, !- Name
T Corridor, !- Zone or ZoneList Name
INF_COR_SCH, !- Schedule Name
Flow/ExteriorArea, !- Design Flow Rate Calculation Method
0, !- Design Flow Rate {m3/s}
, !- Flow per Zone Floor Area {m3/s-m2}
6.6170048e-05, !- Flow per Exterior Surface Area {m3/s-m2}
, !- Air Changes per Hour {1/hr}
0, !- Constant Term Coefficient
0.0000, !- Temperature Term Coefficient
0.2240, !- Velocity Term Coefficient
0.0000; !- Velocity Squared Term Coefficient
!- =========== ALL OBJECTS IN CLASS: EXTERIORLIGHTS ===========
Exterior:Lights,
Facade Lighting, !- Name
Exterior_Lgt_ALWAYS_ON, !- Schedule Name
1651, !- Design Level {W}
AstronomicalClock, !- Control Option
General; !- End-Use Subcategory
!- =========== ALL OBJECTS IN CLASS: SIZING PARAMETERS ===========
Sizing:Parameters,
1.2, !- Heating Sizing Factor
1.2, !- Cooling Sizing Factor
6; !- Timesteps in Averaging Window
!- =========== ALL OBJECTS IN CLASS: ZONE SIZING ===========
Sizing:Zone,
G SW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G SW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G SW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
0.0070800009, !- Outdoor Air Flow per Person {m3/s-person}
0.0003048006, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G NW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G NW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G NW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
Office, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA Office, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA Office, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000431773, !- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G NE Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G NE Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G NE Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G N1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G N1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G N1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G N2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G N2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G N2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G S1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G S1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G S1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
G S2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA G S2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA G S2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M SW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M SW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M SW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M NW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M NW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M NW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M SE Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M SE Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M SE Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M NE Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M NE Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M NE Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M N1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M N1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M N1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M N2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M N2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M N2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M S1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M S1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M S1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
M S2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA M S2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA M S2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T SW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T SW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T SW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T NW Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T NW Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T NW Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T SE Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T SE Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T SE Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T NE Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T NE Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T NE Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T N1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T N1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T N1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T N2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T N2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T N2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T S1 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T S1 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T S1 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
Sizing:Zone,
T S2 Apartment, !- Zone or ZoneList Name
SupplyAirTemperature, !- Zone Cooling Design Supply Air Temperature Input Method
12.8, !- Zone Cooling Design Supply Air Temperature {C}
, !- Zone Cooling Design Supply Air Temperature Difference {deltaC}
SupplyAirTemperature, !- Zone Heating Design Supply Air Temperature Input Method
40, !- Zone Heating Design Supply Air Temperature {C}
, !- Zone Heating Design Supply Air Temperature Difference {deltaC}
0.008, !- Zone Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Zone Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
SZ DSOA T S2 Apartment, !- Design Specification Outdoor Air Object Name
, !- Zone Heating Sizing Factor
, !- Zone Cooling Sizing Factor
DesignDay, !- Cooling Design Air Flow Method
0, !- Cooling Design Air Flow Rate {m3/s}
, !- Cooling Minimum Air Flow per Zone Floor Area {m3/s-m2}
, !- Cooling Minimum Air Flow {m3/s}
0, !- Cooling Minimum Air Flow Fraction
DesignDay, !- Heating Design Air Flow Method
0, !- Heating Design Air Flow Rate {m3/s}
, !- Heating Maximum Air Flow per Zone Floor Area {m3/s-m2}
, !- Heating Maximum Air Flow {m3/s}
0; !- Heating Maximum Air Flow Fraction
DesignSpecification:OutdoorAir,
SZ DSOA T S2 Apartment, !- Name
Flow/Area, !- Outdoor Air Method
7.08000089882824E-03, !- Outdoor Air Flow per Person {m3/s-person}
0.000294087,!- Outdoor Air Flow per Zone Floor Area {m3/s-m2}
0.0; !- Outdoor Air Flow per Zone {m3/s}
!- =========== ALL OBJECTS IN CLASS: SYSTEM SIZING ===========
Sizing:System,
Split GSW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GNW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split Office, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GNE, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GN1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GN2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GS1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split GS2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MSW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MNW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MSE, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MNE, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MN1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MN2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MS1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split MS2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TSW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TNW, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TSE, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TNE, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TN1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TN2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TS1, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
Sizing:System,
Split TS2, !- AirLoop Name
Sensible, !- Type of Load to Size On
autosize, !- Design Outdoor Air Flow Rate {m3/s}
1, !- Central Heating Maximum System Air Flow Ratio
7, !- Preheat Design Temperature {C}
0.008, !- Preheat Design Humidity Ratio {kgWater/kgDryAir}
11, !- Precool Design Temperature {C}
0.008, !- Precool Design Humidity Ratio {kgWater/kgDryAir}
12.8, !- Central Cooling Design Supply Air Temperature {C}
40, !- Central Heating Design Supply Air Temperature {C}
NonCoincident, !- Type of Zone Sum to Use
No, !- 100% Outdoor Air in Cooling
No, !- 100% Outdoor Air in Heating
0.008, !- Central Cooling Design Supply Air Humidity Ratio {kgWater/kgDryAir}
0.008, !- Central Heating Design Supply Air Humidity Ratio {kgWater/kgDryAir}
DesignDay, !- Cooling Supply Air Flow Rate Method
0, !- Cooling Supply Air Flow Rate {m3/s}
, !- Cooling Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Cooling Fraction of Autosized Cooling Supply Air Flow Rate
, !- Cooling Supply Air Flow Rate Per Unit Cooling Capacity {m3/s-W}
DesignDay, !- Heating Supply Air Flow Rate Method
0, !- Heating Supply Air Flow Rate {m3/s}
, !- Heating Supply Air Flow Rate Per Floor Area {m3/s-m2}
, !- Heating Fraction of Autosized Heating Supply Air Flow Rate
, !- Heating Fraction of Autosized Cooling Supply Air Flow Rate
, !- Heating Supply Air Flow Rate Per Unit Heating Capacity {m3/s-W}
ZoneSum; !- System Outdoor Air Method
!- =========== ALL OBJECTS IN CLASS: CURVE:BIQUADRATIC ===========
Curve:Biquadratic,
Split DX Coil Cap-FT, !- Name
0.766955E+00, !- Coefficient1 Constant
0.107757E-01, !- Coefficient2 x
-0.414720E-04, !- Coefficient3 x**2
0.134964E-02, !- Coefficient4 y
-0.261144E-03, !- Coefficient5 y**2
0.457488E-03, !- Coefficient6 x*y
12.77778, !- Minimum Value of x
23.88889, !- Maximum Value of x
23.88889, !- Minimum Value of y
46.11111; !- Maximum Value of y
Curve:Biquadratic,
Split DX Coil EIR-FT, !- Name
0.7915314928, !- Coefficient1 Constant
0, !- Coefficient2 x
-.00054871, !- Coefficient3 x**2
0.000949448, !- Coefficient4 y
0.000165481745, !- Coefficient5 y**2
0.0002782677, !- Coefficient6 x*y
12.77778, !- Minimum Value of x
23.88889, !- Maximum Value of x
23.88889, !- Minimum Value of y
46.11111; !- Maximum Value of y
!- =========== ALL OBJECTS IN CLASS: CURVE:QUADRATIC ===========
Curve:Quadratic,
Split DX Coil Cap-FF, !- Name
0.8, !- Coefficient1 Constant
0.2, !- Coefficient2 x
0, !- Coefficient3 x**2
0.5, !- Minimum Value of x
1.5; !- Maximum Value of x
Curve:Quadratic,
Split DX Coil EIR-FF, !- Name
1.1552, !- Coefficient1 Constant
-0.1808, !- Coefficient2 x
0.0256, !- Coefficient3 x**2
0.5, !- Minimum Value of x
1.5; !- Maximum Value of x
Curve:Quadratic,
Split DX Coil PLF, !- Name
0.85, !- Coefficient1 Constant
0.15, !- Coefficient2 x
0, !- Coefficient3 x**2
0, !- Minimum Value of x
1; !- Maximum Value of x
!- =========== ALL OBJECTS IN CLASS: BRANCH LIST ===========
BranchList,
Split GSW Branches, !- Name
Split GSW Main Branch; !- Branch 1 Name
BranchList,
Split GNW Branches, !- Name
Split GNW Main Branch; !- Branch 1 Name
BranchList,
Split Office Branches, !- Name
Split Office Main Branch;!- Branch 1 Name
BranchList,
Split GNE Branches, !- Name
Split GNE Main Branch; !- Branch 1 Name
BranchList,
Split GN1 Branches, !- Name
Split GN1 Main Branch; !- Branch 1 Name
BranchList,
Split GN2 Branches, !- Name
Split GN2 Main Branch; !- Branch 1 Name
BranchList,
Split GS1 Branches, !- Name
Split GS1 Main Branch; !- Branch 1 Name
BranchList,
Split GS2 Branches, !- Name
Split GS2 Main Branch; !- Branch 1 Name
BranchList,
Split MSW Branches, !- Name
Split MSW Main Branch; !- Branch 1 Name
BranchList,
Split MNW Branches, !- Name
Split MNW Main Branch; !- Branch 1 Name
BranchList,
Split MSE Branches, !- Name
Split MSE Main Branch; !- Branch 1 Name
BranchList,
Split MNE Branches, !- Name
Split MNE Main Branch; !- Branch 1 Name
BranchList,
Split MN1 Branches, !- Name
Split MN1 Main Branch; !- Branch 1 Name
BranchList,
Split MN2 Branches, !- Name
Split MN2 Main Branch; !- Branch 1 Name
BranchList,
Split MS1 Branches, !- Name
Split MS1 Main Branch; !- Branch 1 Name
BranchList,
Split MS2 Branches, !- Name
Split MS2 Main Branch; !- Branch 1 Name
BranchList,
Split TSW Branches, !- Name
Split TSW Main Branch; !- Branch 1 Name
BranchList,
Split TNW Branches, !- Name
Split TNW Main Branch; !- Branch 1 Name
BranchList,
Split TSE Branches, !- Name
Split TSE Main Branch; !- Branch 1 Name
BranchList,
Split TNE Branches, !- Name
Split TNE Main Branch; !- Branch 1 Name
BranchList,
Split TN1 Branches, !- Name
Split TN1 Main Branch; !- Branch 1 Name
BranchList,
Split TN2 Branches, !- Name
Split TN2 Main Branch; !- Branch 1 Name
BranchList,
Split TS1 Branches, !- Name
Split TS1 Main Branch; !- Branch 1 Name
BranchList,
Split TS2 Branches, !- Name
Split TS2 Main Branch; !- Branch 1 Name
!- =========== ALL OBJECTS IN CLASS: BRANCH ===========
Branch,
Split GSW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GSW OA System, !- Component 1 Name
Split GSW Air Loop Inlet,!- Component 1 Inlet Node Name
Split GSW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GSW Furnace with DX Cooling, !- Component 2 Name
Split GSW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GSW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GNW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GNW OA System, !- Component 1 Name
Split GNW Air Loop Inlet,!- Component 1 Inlet Node Name
Split GNW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GNW Furnace with DX Cooling, !- Component 2 Name
Split GNW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GNW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split Office Main Branch,!- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split Office OA System, !- Component 1 Name
Split Office Air Loop Inlet, !- Component 1 Inlet Node Name
Split Office Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split Office Furnace with DX Cooling, !- Component 2 Name
Split Office Mixed Air Outlet, !- Component 2 Inlet Node Name
Split Office Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GNE Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GNE OA System, !- Component 1 Name
Split GNE Air Loop Inlet,!- Component 1 Inlet Node Name
Split GNE Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GNE Furnace with DX Cooling, !- Component 2 Name
Split GNE Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GNE Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GN1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GN1 OA System, !- Component 1 Name
Split GN1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split GN1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GN1 Furnace with DX Cooling, !- Component 2 Name
Split GN1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GN1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GN2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GN2 OA System, !- Component 1 Name
Split GN2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split GN2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GN2 Furnace with DX Cooling, !- Component 2 Name
Split GN2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GN2 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GS1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GS1 OA System, !- Component 1 Name
Split GS1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split GS1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GS1 Furnace with DX Cooling, !- Component 2 Name
Split GS1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GS1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split GS2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split GS2 OA System, !- Component 1 Name
Split GS2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split GS2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split GS2 Furnace with DX Cooling, !- Component 2 Name
Split GS2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split GS2 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MSW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MSW OA System, !- Component 1 Name
Split MSW Air Loop Inlet,!- Component 1 Inlet Node Name
Split MSW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MSW Furnace with DX Cooling, !- Component 2 Name
Split MSW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MSW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MNW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MNW OA System, !- Component 1 Name
Split MNW Air Loop Inlet,!- Component 1 Inlet Node Name
Split MNW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MNW Furnace with DX Cooling, !- Component 2 Name
Split MNW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MNW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MSE Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MSE OA System, !- Component 1 Name
Split MSE Air Loop Inlet,!- Component 1 Inlet Node Name
Split MSE Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MSE Furnace with DX Cooling, !- Component 2 Name
Split MSE Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MSE Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MNE Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MNE OA System, !- Component 1 Name
Split MNE Air Loop Inlet,!- Component 1 Inlet Node Name
Split MNE Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MNE Furnace with DX Cooling, !- Component 2 Name
Split MNE Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MNE Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MN1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MN1 OA System, !- Component 1 Name
Split MN1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split MN1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MN1 Furnace with DX Cooling, !- Component 2 Name
Split MN1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MN1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MN2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MN2 OA System, !- Component 1 Name
Split MN2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split MN2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MN2 Furnace with DX Cooling, !- Component 2 Name
Split MN2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MN2 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MS1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MS1 OA System, !- Component 1 Name
Split MS1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split MS1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MS1 Furnace with DX Cooling, !- Component 2 Name
Split MS1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MS1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split MS2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split MS2 OA System, !- Component 1 Name
Split MS2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split MS2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split MS2 Furnace with DX Cooling, !- Component 2 Name
Split MS2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split MS2 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TSW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TSW OA System, !- Component 1 Name
Split TSW Air Loop Inlet,!- Component 1 Inlet Node Name
Split TSW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TSW Furnace with DX Cooling, !- Component 2 Name
Split TSW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TSW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TNW Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TNW OA System, !- Component 1 Name
Split TNW Air Loop Inlet,!- Component 1 Inlet Node Name
Split TNW Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TNW Furnace with DX Cooling, !- Component 2 Name
Split TNW Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TNW Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TSE Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TSE OA System, !- Component 1 Name
Split TSE Air Loop Inlet,!- Component 1 Inlet Node Name
Split TSE Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TSE Furnace with DX Cooling, !- Component 2 Name
Split TSE Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TSE Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TNE Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TNE OA System, !- Component 1 Name
Split TNE Air Loop Inlet,!- Component 1 Inlet Node Name
Split TNE Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TNE Furnace with DX Cooling, !- Component 2 Name
Split TNE Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TNE Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TN1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TN1 OA System, !- Component 1 Name
Split TN1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split TN1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TN1 Furnace with DX Cooling, !- Component 2 Name
Split TN1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TN1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TN2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TN2 OA System, !- Component 1 Name
Split TN2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split TN2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TN2 Furnace with DX Cooling, !- Component 2 Name
Split TN2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TN2 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TS1 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TS1 OA System, !- Component 1 Name
Split TS1 Air Loop Inlet,!- Component 1 Inlet Node Name
Split TS1 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TS1 Furnace with DX Cooling, !- Component 2 Name
Split TS1 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TS1 Air Loop Outlet; !- Component 2 Outlet Node Name
Branch,
Split TS2 Main Branch, !- Name
, !- Pressure Drop Curve Name
AirLoopHVAC:OutdoorAirSystem, !- Component 1 Object Type
Split TS2 OA System, !- Component 1 Name
Split TS2 Air Loop Inlet,!- Component 1 Inlet Node Name
Split TS2 Mixed Air Outlet, !- Component 1 Outlet Node Name
AirLoopHVAC:Unitary:Furnace:HeatCool, !- Component 2 Object Type
Split TS2 Furnace with DX Cooling, !- Component 2 Name
Split TS2 Mixed Air Outlet, !- Component 2 Inlet Node Name
Split TS2 Air Loop Outlet; !- Component 2 Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: AIR PRIMARY LOOP ===========
AirLoopHVAC,
Split GSW, !- Name
, !- Controller List Name
Split GSW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GSW Branches, !- Branch List Name
, !- Connector List Name
Split GSW Air Loop Inlet,!- Supply Side Inlet Node Name
Split GSW Return Air Outlet, !- Demand Side Outlet Node Name
Split GSW Supply Path Inlet, !- Demand Side Inlet Node Names
Split GSW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GNW, !- Name
, !- Controller List Name
Split GNW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GNW Branches, !- Branch List Name
, !- Connector List Name
Split GNW Air Loop Inlet,!- Supply Side Inlet Node Name
Split GNW Return Air Outlet, !- Demand Side Outlet Node Name
Split GNW Supply Path Inlet, !- Demand Side Inlet Node Names
Split GNW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split Office, !- Name
, !- Controller List Name
Split Office Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split Office Branches, !- Branch List Name
, !- Connector List Name
Split Office Air Loop Inlet, !- Supply Side Inlet Node Name
Split Office Return Air Outlet, !- Demand Side Outlet Node Name
Split Office Supply Path Inlet, !- Demand Side Inlet Node Names
Split Office Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GNE, !- Name
, !- Controller List Name
Split GNE Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GNE Branches, !- Branch List Name
, !- Connector List Name
Split GNE Air Loop Inlet,!- Supply Side Inlet Node Name
Split GNE Return Air Outlet, !- Demand Side Outlet Node Name
Split GNE Supply Path Inlet, !- Demand Side Inlet Node Names
Split GNE Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GN1, !- Name
, !- Controller List Name
Split GN1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GN1 Branches, !- Branch List Name
, !- Connector List Name
Split GN1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split GN1 Return Air Outlet, !- Demand Side Outlet Node Name
Split GN1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split GN1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GN2, !- Name
, !- Controller List Name
Split GN2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GN2 Branches, !- Branch List Name
, !- Connector List Name
Split GN2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split GN2 Return Air Outlet, !- Demand Side Outlet Node Name
Split GN2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split GN2 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GS1, !- Name
, !- Controller List Name
Split GS1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GS1 Branches, !- Branch List Name
, !- Connector List Name
Split GS1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split GS1 Return Air Outlet, !- Demand Side Outlet Node Name
Split GS1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split GS1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split GS2, !- Name
, !- Controller List Name
Split GS2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split GS2 Branches, !- Branch List Name
, !- Connector List Name
Split GS2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split GS2 Return Air Outlet, !- Demand Side Outlet Node Name
Split GS2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split GS2 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MSW, !- Name
, !- Controller List Name
Split MSW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MSW Branches, !- Branch List Name
, !- Connector List Name
Split MSW Air Loop Inlet,!- Supply Side Inlet Node Name
Split MSW Return Air Outlet, !- Demand Side Outlet Node Name
Split MSW Supply Path Inlet, !- Demand Side Inlet Node Names
Split MSW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MNW, !- Name
, !- Controller List Name
Split MNW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MNW Branches, !- Branch List Name
, !- Connector List Name
Split MNW Air Loop Inlet,!- Supply Side Inlet Node Name
Split MNW Return Air Outlet, !- Demand Side Outlet Node Name
Split MNW Supply Path Inlet, !- Demand Side Inlet Node Names
Split MNW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MSE, !- Name
, !- Controller List Name
Split MSE Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MSE Branches, !- Branch List Name
, !- Connector List Name
Split MSE Air Loop Inlet,!- Supply Side Inlet Node Name
Split MSE Return Air Outlet, !- Demand Side Outlet Node Name
Split MSE Supply Path Inlet, !- Demand Side Inlet Node Names
Split MSE Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MNE, !- Name
, !- Controller List Name
Split MNE Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MNE Branches, !- Branch List Name
, !- Connector List Name
Split MNE Air Loop Inlet,!- Supply Side Inlet Node Name
Split MNE Return Air Outlet, !- Demand Side Outlet Node Name
Split MNE Supply Path Inlet, !- Demand Side Inlet Node Names
Split MNE Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MN1, !- Name
, !- Controller List Name
Split MN1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MN1 Branches, !- Branch List Name
, !- Connector List Name
Split MN1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split MN1 Return Air Outlet, !- Demand Side Outlet Node Name
Split MN1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split MN1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MN2, !- Name
, !- Controller List Name
Split MN2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MN2 Branches, !- Branch List Name
, !- Connector List Name
Split MN2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split MN2 Return Air Outlet, !- Demand Side Outlet Node Name
Split MN2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split MN2 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MS1, !- Name
, !- Controller List Name
Split MS1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MS1 Branches, !- Branch List Name
, !- Connector List Name
Split MS1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split MS1 Return Air Outlet, !- Demand Side Outlet Node Name
Split MS1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split MS1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split MS2, !- Name
, !- Controller List Name
Split MS2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split MS2 Branches, !- Branch List Name
, !- Connector List Name
Split MS2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split MS2 Return Air Outlet, !- Demand Side Outlet Node Name
Split MS2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split MS2 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TSW, !- Name
, !- Controller List Name
Split TSW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TSW Branches, !- Branch List Name
, !- Connector List Name
Split TSW Air Loop Inlet,!- Supply Side Inlet Node Name
Split TSW Return Air Outlet, !- Demand Side Outlet Node Name
Split TSW Supply Path Inlet, !- Demand Side Inlet Node Names
Split TSW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TNW, !- Name
, !- Controller List Name
Split TNW Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TNW Branches, !- Branch List Name
, !- Connector List Name
Split TNW Air Loop Inlet,!- Supply Side Inlet Node Name
Split TNW Return Air Outlet, !- Demand Side Outlet Node Name
Split TNW Supply Path Inlet, !- Demand Side Inlet Node Names
Split TNW Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TSE, !- Name
, !- Controller List Name
Split TSE Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TSE Branches, !- Branch List Name
, !- Connector List Name
Split TSE Air Loop Inlet,!- Supply Side Inlet Node Name
Split TSE Return Air Outlet, !- Demand Side Outlet Node Name
Split TSE Supply Path Inlet, !- Demand Side Inlet Node Names
Split TSE Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TNE, !- Name
, !- Controller List Name
Split TNE Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TNE Branches, !- Branch List Name
, !- Connector List Name
Split TNE Air Loop Inlet,!- Supply Side Inlet Node Name
Split TNE Return Air Outlet, !- Demand Side Outlet Node Name
Split TNE Supply Path Inlet, !- Demand Side Inlet Node Names
Split TNE Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TN1, !- Name
, !- Controller List Name
Split TN1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TN1 Branches, !- Branch List Name
, !- Connector List Name
Split TN1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split TN1 Return Air Outlet, !- Demand Side Outlet Node Name
Split TN1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split TN1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TN2, !- Name
, !- Controller List Name
Split TN2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TN2 Branches, !- Branch List Name
, !- Connector List Name
Split TN2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split TN2 Return Air Outlet, !- Demand Side Outlet Node Name
Split TN2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split TN2 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TS1, !- Name
, !- Controller List Name
Split TS1 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TS1 Branches, !- Branch List Name
, !- Connector List Name
Split TS1 Air Loop Inlet,!- Supply Side Inlet Node Name
Split TS1 Return Air Outlet, !- Demand Side Outlet Node Name
Split TS1 Supply Path Inlet, !- Demand Side Inlet Node Names
Split TS1 Air Loop Outlet; !- Supply Side Outlet Node Names
AirLoopHVAC,
Split TS2, !- Name
, !- Controller List Name
Split TS2 Availability Managers, !- Availability Manager List Name
autosize, !- Design Supply Air Flow Rate {m3/s}
Split TS2 Branches, !- Branch List Name
, !- Connector List Name
Split TS2 Air Loop Inlet,!- Supply Side Inlet Node Name
Split TS2 Return Air Outlet, !- Demand Side Outlet Node Name
Split TS2 Supply Path Inlet, !- Demand Side Inlet Node Names
Split TS2 Air Loop Outlet; !- Supply Side Outlet Node Names
!- =========== ALL OBJECTS IN CLASS: CONTROLLER LIST ===========
AirLoopHVAC:ControllerList,
Split GSW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GSW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GNW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GNW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split Office OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split Office OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GNE OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GNE OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GN1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GN1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GN2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GN2 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GS1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GS1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split GS2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split GS2 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MSW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MSW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MNW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MNW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MSE OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MSE OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MNE OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MNE OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MN1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MN1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MN2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MN2 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MS1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MS1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split MS2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split MS2 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TSW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TSW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TNW OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TNW OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TSE OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TSE OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TNE OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TNE OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TN1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TN1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TN2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TN2 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TS1 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TS1 OA Controller; !- Controller 1 Name
AirLoopHVAC:ControllerList,
Split TS2 OA System Controllers, !- Name
Controller:OutdoorAir, !- Controller 1 Object Type
Split TS2 OA Controller; !- Controller 1 Name
!- =========== ALL OBJECTS IN CLASS: AIR LOOP EQUIPMENT LIST ===========
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GSW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GSW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GNW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GNW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split Office OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split Office OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GNE OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GNE OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GN1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GN1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GN2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GN2 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GS1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GS1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split GS2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split GS2 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MSW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MSW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MNW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MNW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MSE OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MSE OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MNE OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MNE OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MN1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MN1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MN2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MN2 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MS1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MS1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split MS2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split MS2 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TSW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TSW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TNW OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TNW OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TSE OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TSE OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TNE OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TNE OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TN1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TN1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TN2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TN2 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TS1 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TS1 OA Mixing Box; !- Component 1 Name
AirLoopHVAC:OutdoorAirSystem:EquipmentList,
Split TS2 OA System Equipment, !- Name
OutdoorAir:Mixer, !- Component 1 Object Type
Split TS2 OA Mixing Box; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR SYSTEM ===========
AirLoopHVAC:OutdoorAirSystem,
Split GSW OA System, !- Name
Split GSW OA System Controllers, !- Controller List Name
Split GSW OA System Equipment, !- Outdoor Air Equipment List Name
Split GSW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GNW OA System, !- Name
Split GNW OA System Controllers, !- Controller List Name
Split GNW OA System Equipment, !- Outdoor Air Equipment List Name
Split GNW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split Office OA System, !- Name
Split Office OA System Controllers, !- Controller List Name
Split Office OA System Equipment, !- Outdoor Air Equipment List Name
Split Office Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GNE OA System, !- Name
Split GNE OA System Controllers, !- Controller List Name
Split GNE OA System Equipment, !- Outdoor Air Equipment List Name
Split GNE Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GN1 OA System, !- Name
Split GN1 OA System Controllers, !- Controller List Name
Split GN1 OA System Equipment, !- Outdoor Air Equipment List Name
Split GN1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GN2 OA System, !- Name
Split GN2 OA System Controllers, !- Controller List Name
Split GN2 OA System Equipment, !- Outdoor Air Equipment List Name
Split GN2 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GS1 OA System, !- Name
Split GS1 OA System Controllers, !- Controller List Name
Split GS1 OA System Equipment, !- Outdoor Air Equipment List Name
Split GS1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split GS2 OA System, !- Name
Split GS2 OA System Controllers, !- Controller List Name
Split GS2 OA System Equipment, !- Outdoor Air Equipment List Name
Split GS2 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MSW OA System, !- Name
Split MSW OA System Controllers, !- Controller List Name
Split MSW OA System Equipment, !- Outdoor Air Equipment List Name
Split MSW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MNW OA System, !- Name
Split MNW OA System Controllers, !- Controller List Name
Split MNW OA System Equipment, !- Outdoor Air Equipment List Name
Split MNW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MSE OA System, !- Name
Split MSE OA System Controllers, !- Controller List Name
Split MSE OA System Equipment, !- Outdoor Air Equipment List Name
Split MSE Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MNE OA System, !- Name
Split MNE OA System Controllers, !- Controller List Name
Split MNE OA System Equipment, !- Outdoor Air Equipment List Name
Split MNE Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MN1 OA System, !- Name
Split MN1 OA System Controllers, !- Controller List Name
Split MN1 OA System Equipment, !- Outdoor Air Equipment List Name
Split MN1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MN2 OA System, !- Name
Split MN2 OA System Controllers, !- Controller List Name
Split MN2 OA System Equipment, !- Outdoor Air Equipment List Name
Split MN2 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MS1 OA System, !- Name
Split MS1 OA System Controllers, !- Controller List Name
Split MS1 OA System Equipment, !- Outdoor Air Equipment List Name
Split MS1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split MS2 OA System, !- Name
Split MS2 OA System Controllers, !- Controller List Name
Split MS2 OA System Equipment, !- Outdoor Air Equipment List Name
Split MS2 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TSW OA System, !- Name
Split TSW OA System Controllers, !- Controller List Name
Split TSW OA System Equipment, !- Outdoor Air Equipment List Name
Split TSW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TNW OA System, !- Name
Split TNW OA System Controllers, !- Controller List Name
Split TNW OA System Equipment, !- Outdoor Air Equipment List Name
Split TNW Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TSE OA System, !- Name
Split TSE OA System Controllers, !- Controller List Name
Split TSE OA System Equipment, !- Outdoor Air Equipment List Name
Split TSE Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TNE OA System, !- Name
Split TNE OA System Controllers, !- Controller List Name
Split TNE OA System Equipment, !- Outdoor Air Equipment List Name
Split TNE Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TN1 OA System, !- Name
Split TN1 OA System Controllers, !- Controller List Name
Split TN1 OA System Equipment, !- Outdoor Air Equipment List Name
Split TN1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TN2 OA System, !- Name
Split TN2 OA System Controllers, !- Controller List Name
Split TN2 OA System Equipment, !- Outdoor Air Equipment List Name
Split TN2 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TS1 OA System, !- Name
Split TS1 OA System Controllers, !- Controller List Name
Split TS1 OA System Equipment, !- Outdoor Air Equipment List Name
Split TS1 Availability Managers; !- Availability Manager List Name
AirLoopHVAC:OutdoorAirSystem,
Split TS2 OA System, !- Name
Split TS2 OA System Controllers, !- Controller List Name
Split TS2 OA System Equipment, !- Outdoor Air Equipment List Name
Split TS2 Availability Managers; !- Availability Manager List Name
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR NODE ===========
OutdoorAir:Node,
Split GSW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GNW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split Office Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GNE Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GN1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GN2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GS1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split GS2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MSW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MNW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MSE Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MNE Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MN1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MN2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MS1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split MS2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TSW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TNW Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TSE Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TNE Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TN1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TN2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TS1 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
OutdoorAir:Node,
Split TS2 Cooling Coil Condenser Inlet, !- Name
-1; !- Height Above Ground {m}
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR INLET NODE LIST ===========
OutdoorAir:NodeList,
Split GSW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GNW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split Office Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GNE Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GN1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GN2 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GS1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split GS2 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MSW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MNW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MSE Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MNE Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MN1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MN2 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MS1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split MS2 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TSW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TNW Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TSE Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TNE Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TN1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TN2 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TS1 Outside Air Inlet; !- Node or NodeList Name 1
OutdoorAir:NodeList,
Split TS2 Outside Air Inlet; !- Node or NodeList Name 1
!- =========== ALL OBJECTS IN CLASS: OUTSIDE AIR MIXER ===========
OutdoorAir:Mixer,
Split GSW OA Mixing Box, !- Name
Split GSW Mixed Air Outlet, !- Mixed Air Node Name
Split GSW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GSW Relief Air Outlet, !- Relief Air Stream Node Name
Split GSW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GNW OA Mixing Box, !- Name
Split GNW Mixed Air Outlet, !- Mixed Air Node Name
Split GNW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GNW Relief Air Outlet, !- Relief Air Stream Node Name
Split GNW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split Office OA Mixing Box, !- Name
Split Office Mixed Air Outlet, !- Mixed Air Node Name
Split Office Outside Air Inlet, !- Outdoor Air Stream Node Name
Split Office Relief Air Outlet, !- Relief Air Stream Node Name
Split Office Air Loop Inlet; !- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GNE OA Mixing Box, !- Name
Split GNE Mixed Air Outlet, !- Mixed Air Node Name
Split GNE Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GNE Relief Air Outlet, !- Relief Air Stream Node Name
Split GNE Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GN1 OA Mixing Box, !- Name
Split GN1 Mixed Air Outlet, !- Mixed Air Node Name
Split GN1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GN1 Relief Air Outlet, !- Relief Air Stream Node Name
Split GN1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GN2 OA Mixing Box, !- Name
Split GN2 Mixed Air Outlet, !- Mixed Air Node Name
Split GN2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GN2 Relief Air Outlet, !- Relief Air Stream Node Name
Split GN2 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GS1 OA Mixing Box, !- Name
Split GS1 Mixed Air Outlet, !- Mixed Air Node Name
Split GS1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GS1 Relief Air Outlet, !- Relief Air Stream Node Name
Split GS1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split GS2 OA Mixing Box, !- Name
Split GS2 Mixed Air Outlet, !- Mixed Air Node Name
Split GS2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split GS2 Relief Air Outlet, !- Relief Air Stream Node Name
Split GS2 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MSW OA Mixing Box, !- Name
Split MSW Mixed Air Outlet, !- Mixed Air Node Name
Split MSW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MSW Relief Air Outlet, !- Relief Air Stream Node Name
Split MSW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MNW OA Mixing Box, !- Name
Split MNW Mixed Air Outlet, !- Mixed Air Node Name
Split MNW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MNW Relief Air Outlet, !- Relief Air Stream Node Name
Split MNW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MSE OA Mixing Box, !- Name
Split MSE Mixed Air Outlet, !- Mixed Air Node Name
Split MSE Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MSE Relief Air Outlet, !- Relief Air Stream Node Name
Split MSE Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MNE OA Mixing Box, !- Name
Split MNE Mixed Air Outlet, !- Mixed Air Node Name
Split MNE Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MNE Relief Air Outlet, !- Relief Air Stream Node Name
Split MNE Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MN1 OA Mixing Box, !- Name
Split MN1 Mixed Air Outlet, !- Mixed Air Node Name
Split MN1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MN1 Relief Air Outlet, !- Relief Air Stream Node Name
Split MN1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MN2 OA Mixing Box, !- Name
Split MN2 Mixed Air Outlet, !- Mixed Air Node Name
Split MN2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MN2 Relief Air Outlet, !- Relief Air Stream Node Name
Split MN2 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MS1 OA Mixing Box, !- Name
Split MS1 Mixed Air Outlet, !- Mixed Air Node Name
Split MS1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MS1 Relief Air Outlet, !- Relief Air Stream Node Name
Split MS1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split MS2 OA Mixing Box, !- Name
Split MS2 Mixed Air Outlet, !- Mixed Air Node Name
Split MS2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split MS2 Relief Air Outlet, !- Relief Air Stream Node Name
Split MS2 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TSW OA Mixing Box, !- Name
Split TSW Mixed Air Outlet, !- Mixed Air Node Name
Split TSW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TSW Relief Air Outlet, !- Relief Air Stream Node Name
Split TSW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TNW OA Mixing Box, !- Name
Split TNW Mixed Air Outlet, !- Mixed Air Node Name
Split TNW Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TNW Relief Air Outlet, !- Relief Air Stream Node Name
Split TNW Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TSE OA Mixing Box, !- Name
Split TSE Mixed Air Outlet, !- Mixed Air Node Name
Split TSE Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TSE Relief Air Outlet, !- Relief Air Stream Node Name
Split TSE Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TNE OA Mixing Box, !- Name
Split TNE Mixed Air Outlet, !- Mixed Air Node Name
Split TNE Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TNE Relief Air Outlet, !- Relief Air Stream Node Name
Split TNE Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TN1 OA Mixing Box, !- Name
Split TN1 Mixed Air Outlet, !- Mixed Air Node Name
Split TN1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TN1 Relief Air Outlet, !- Relief Air Stream Node Name
Split TN1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TN2 OA Mixing Box, !- Name
Split TN2 Mixed Air Outlet, !- Mixed Air Node Name
Split TN2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TN2 Relief Air Outlet, !- Relief Air Stream Node Name
Split TN2 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TS1 OA Mixing Box, !- Name
Split TS1 Mixed Air Outlet, !- Mixed Air Node Name
Split TS1 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TS1 Relief Air Outlet, !- Relief Air Stream Node Name
Split TS1 Air Loop Inlet;!- Return Air Stream Node Name
OutdoorAir:Mixer,
Split TS2 OA Mixing Box, !- Name
Split TS2 Mixed Air Outlet, !- Mixed Air Node Name
Split TS2 Outside Air Inlet, !- Outdoor Air Stream Node Name
Split TS2 Relief Air Outlet, !- Relief Air Stream Node Name
Split TS2 Air Loop Inlet;!- Return Air Stream Node Name
!- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER LIST ===========
AvailabilityManagerAssignmentList,
Split GSW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GSW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GNW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GNW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split Office Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split Office Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GNE Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GNE Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GN1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GN1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GN2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GN2 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GS1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GS1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split GS2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split GS2 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MSW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MSW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MNW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MNW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MSE Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MSE Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MNE Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MNE Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MN1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MN1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MN2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MN2 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MS1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MS1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split MS2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split MS2 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TSW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TSW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TNW Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TNW Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TSE Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TSE Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TNE Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TNE Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TN1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TN1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TN2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TN2 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TS1 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TS1 Availability; !- Availability Manager 1 Name
AvailabilityManagerAssignmentList,
Split TS2 Availability Managers, !- Name
AvailabilityManager:Scheduled, !- Availability Manager 1 Object Type
Split TS2 Availability; !- Availability Manager 1 Name
!- =========== ALL OBJECTS IN CLASS: SYSTEM AVAILABILITY MANAGER:SCHEDULED ===========
AvailabilityManager:Scheduled,
Split GSW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GNW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split Office Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GNE Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GN1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GN2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GS1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split GS2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MSW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MNW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MSE Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MNE Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MN1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MN2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MS1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split MS2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TSW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TNW Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TSE Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TNE Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TN1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TN2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TS1 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
AvailabilityManager:Scheduled,
Split TS2 Availability, !- Name
COMPACT HVAC-ALWAYS 1; !- Schedule Name
!- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:SINGLE ZONE HEATING & COOLING ===========
SetpointManager:SingleZone:Heating,
Split GSW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G SW Apartment, !- Control Zone Name
G SW Apartment Zone Air Node, !- Zone Node Name
G SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GSW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GNW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G NW Apartment, !- Control Zone Name
G NW Apartment Zone Air Node, !- Zone Node Name
G NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GNW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split Office Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
Office, !- Control Zone Name
Office Zone Air Node, !- Zone Node Name
Office Zone Equip Inlet, !- Zone Inlet Node Name
Split Office Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GNE Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G NE Apartment, !- Control Zone Name
G NE Apartment Zone Air Node, !- Zone Node Name
G NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GNE Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GN1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G N1 Apartment, !- Control Zone Name
G N1 Apartment Zone Air Node, !- Zone Node Name
G N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GN1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GN2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G N2 Apartment, !- Control Zone Name
G N2 Apartment Zone Air Node, !- Zone Node Name
G N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GN2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GS1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G S1 Apartment, !- Control Zone Name
G S1 Apartment Zone Air Node, !- Zone Node Name
G S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GS1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split GS2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G S2 Apartment, !- Control Zone Name
G S2 Apartment Zone Air Node, !- Zone Node Name
G S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GS2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MSW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M SW Apartment, !- Control Zone Name
M SW Apartment Zone Air Node, !- Zone Node Name
M SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MSW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MNW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M NW Apartment, !- Control Zone Name
M NW Apartment Zone Air Node, !- Zone Node Name
M NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MNW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MSE Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M SE Apartment, !- Control Zone Name
M SE Apartment Zone Air Node, !- Zone Node Name
M SE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MSE Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MNE Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M NE Apartment, !- Control Zone Name
M NE Apartment Zone Air Node, !- Zone Node Name
M NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MNE Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MN1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M N1 Apartment, !- Control Zone Name
M N1 Apartment Zone Air Node, !- Zone Node Name
M N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MN1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MN2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M N2 Apartment, !- Control Zone Name
M N2 Apartment Zone Air Node, !- Zone Node Name
M N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MN2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MS1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M S1 Apartment, !- Control Zone Name
M S1 Apartment Zone Air Node, !- Zone Node Name
M S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MS1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split MS2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M S2 Apartment, !- Control Zone Name
M S2 Apartment Zone Air Node, !- Zone Node Name
M S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MS2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TSW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T SW Apartment, !- Control Zone Name
T SW Apartment Zone Air Node, !- Zone Node Name
T SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TSW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TNW Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T NW Apartment, !- Control Zone Name
T NW Apartment Zone Air Node, !- Zone Node Name
T NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TNW Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TSE Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T SE Apartment, !- Control Zone Name
T SE Apartment Zone Air Node, !- Zone Node Name
T SE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TSE Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TNE Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T NE Apartment, !- Control Zone Name
T NE Apartment Zone Air Node, !- Zone Node Name
T NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TNE Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TN1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T N1 Apartment, !- Control Zone Name
T N1 Apartment Zone Air Node, !- Zone Node Name
T N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TN1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TN2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T N2 Apartment, !- Control Zone Name
T N2 Apartment Zone Air Node, !- Zone Node Name
T N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TN2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TS1 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T S1 Apartment, !- Control Zone Name
T S1 Apartment Zone Air Node, !- Zone Node Name
T S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TS1 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Heating,
Split TS2 Supply Air Temp Manager - Htg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T S2 Apartment, !- Control Zone Name
T S2 Apartment Zone Air Node, !- Zone Node Name
T S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TS2 Heating Coil Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GSW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G SW Apartment, !- Control Zone Name
G SW Apartment Zone Air Node, !- Zone Node Name
G SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GSW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GNW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G NW Apartment, !- Control Zone Name
G NW Apartment Zone Air Node, !- Zone Node Name
G NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GNW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split Office Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
Office, !- Control Zone Name
Office Zone Air Node, !- Zone Node Name
Office Zone Equip Inlet, !- Zone Inlet Node Name
Split Office Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GNE Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G NE Apartment, !- Control Zone Name
G NE Apartment Zone Air Node, !- Zone Node Name
G NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GNE Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GN1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G N1 Apartment, !- Control Zone Name
G N1 Apartment Zone Air Node, !- Zone Node Name
G N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GN1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GN2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G N2 Apartment, !- Control Zone Name
G N2 Apartment Zone Air Node, !- Zone Node Name
G N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GN2 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GS1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G S1 Apartment, !- Control Zone Name
G S1 Apartment Zone Air Node, !- Zone Node Name
G S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GS1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split GS2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
G S2 Apartment, !- Control Zone Name
G S2 Apartment Zone Air Node, !- Zone Node Name
G S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split GS2 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MSW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M SW Apartment, !- Control Zone Name
M SW Apartment Zone Air Node, !- Zone Node Name
M SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MSW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MNW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M NW Apartment, !- Control Zone Name
M NW Apartment Zone Air Node, !- Zone Node Name
M NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MNW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MSE Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M SE Apartment, !- Control Zone Name
M SE Apartment Zone Air Node, !- Zone Node Name
M SE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MSE Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MNE Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M NE Apartment, !- Control Zone Name
M NE Apartment Zone Air Node, !- Zone Node Name
M NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MNE Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MN1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M N1 Apartment, !- Control Zone Name
M N1 Apartment Zone Air Node, !- Zone Node Name
M N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MN1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MN2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M N2 Apartment, !- Control Zone Name
M N2 Apartment Zone Air Node, !- Zone Node Name
M N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MN2 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MS1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M S1 Apartment, !- Control Zone Name
M S1 Apartment Zone Air Node, !- Zone Node Name
M S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MS1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split MS2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
M S2 Apartment, !- Control Zone Name
M S2 Apartment Zone Air Node, !- Zone Node Name
M S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split MS2 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TSW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T SW Apartment, !- Control Zone Name
T SW Apartment Zone Air Node, !- Zone Node Name
T SW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TSW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TNW Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T NW Apartment, !- Control Zone Name
T NW Apartment Zone Air Node, !- Zone Node Name
T NW Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TNW Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TSE Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T SE Apartment, !- Control Zone Name
T SE Apartment Zone Air Node, !- Zone Node Name
T SE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TSE Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TNE Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T NE Apartment, !- Control Zone Name
T NE Apartment Zone Air Node, !- Zone Node Name
T NE Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TNE Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TN1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T N1 Apartment, !- Control Zone Name
T N1 Apartment Zone Air Node, !- Zone Node Name
T N1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TN1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TN2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T N2 Apartment, !- Control Zone Name
T N2 Apartment Zone Air Node, !- Zone Node Name
T N2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TN2 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TS1 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T S1 Apartment, !- Control Zone Name
T S1 Apartment Zone Air Node, !- Zone Node Name
T S1 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TS1 Air Loop Outlet; !- Setpoint Node or NodeList Name
SetpointManager:SingleZone:Cooling,
Split TS2 Supply Air Temp Manager - Clg, !- Name
Temperature, !- Control Variable
12.8, !- Minimum Supply Air Temperature {C}
40.0, !- Maximum Supply Air Temperature {C}
T S2 Apartment, !- Control Zone Name
T S2 Apartment Zone Air Node, !- Zone Node Name
T S2 Apartment Zone Equip Inlet, !- Zone Inlet Node Name
Split TS2 Air Loop Outlet; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:MIXED AIR ===========
SetpointManager:MixedAir,
Split GSW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GSW Air Loop Outlet, !- Reference Setpoint Node Name
Split GSW Mixed Air Outlet, !- Fan Inlet Node Name
Split GSW Supply Fan Outlet, !- Fan Outlet Node Name
Split GSW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GNW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GNW Air Loop Outlet, !- Reference Setpoint Node Name
Split GNW Mixed Air Outlet, !- Fan Inlet Node Name
Split GNW Supply Fan Outlet, !- Fan Outlet Node Name
Split GNW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split Office Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split Office Air Loop Outlet, !- Reference Setpoint Node Name
Split Office Mixed Air Outlet, !- Fan Inlet Node Name
Split Office Supply Fan Outlet, !- Fan Outlet Node Name
Split Office Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GNE Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GNE Air Loop Outlet, !- Reference Setpoint Node Name
Split GNE Mixed Air Outlet, !- Fan Inlet Node Name
Split GNE Supply Fan Outlet, !- Fan Outlet Node Name
Split GNE Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GN1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GN1 Air Loop Outlet, !- Reference Setpoint Node Name
Split GN1 Mixed Air Outlet, !- Fan Inlet Node Name
Split GN1 Supply Fan Outlet, !- Fan Outlet Node Name
Split GN1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GN2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GN2 Air Loop Outlet, !- Reference Setpoint Node Name
Split GN2 Mixed Air Outlet, !- Fan Inlet Node Name
Split GN2 Supply Fan Outlet, !- Fan Outlet Node Name
Split GN2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GS1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GS1 Air Loop Outlet, !- Reference Setpoint Node Name
Split GS1 Mixed Air Outlet, !- Fan Inlet Node Name
Split GS1 Supply Fan Outlet, !- Fan Outlet Node Name
Split GS1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split GS2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split GS2 Air Loop Outlet, !- Reference Setpoint Node Name
Split GS2 Mixed Air Outlet, !- Fan Inlet Node Name
Split GS2 Supply Fan Outlet, !- Fan Outlet Node Name
Split GS2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MSW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MSW Air Loop Outlet, !- Reference Setpoint Node Name
Split MSW Mixed Air Outlet, !- Fan Inlet Node Name
Split MSW Supply Fan Outlet, !- Fan Outlet Node Name
Split MSW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MNW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MNW Air Loop Outlet, !- Reference Setpoint Node Name
Split MNW Mixed Air Outlet, !- Fan Inlet Node Name
Split MNW Supply Fan Outlet, !- Fan Outlet Node Name
Split MNW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MSE Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MSE Air Loop Outlet, !- Reference Setpoint Node Name
Split MSE Mixed Air Outlet, !- Fan Inlet Node Name
Split MSE Supply Fan Outlet, !- Fan Outlet Node Name
Split MSE Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MNE Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MNE Air Loop Outlet, !- Reference Setpoint Node Name
Split MNE Mixed Air Outlet, !- Fan Inlet Node Name
Split MNE Supply Fan Outlet, !- Fan Outlet Node Name
Split MNE Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MN1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MN1 Air Loop Outlet, !- Reference Setpoint Node Name
Split MN1 Mixed Air Outlet, !- Fan Inlet Node Name
Split MN1 Supply Fan Outlet, !- Fan Outlet Node Name
Split MN1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MN2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MN2 Air Loop Outlet, !- Reference Setpoint Node Name
Split MN2 Mixed Air Outlet, !- Fan Inlet Node Name
Split MN2 Supply Fan Outlet, !- Fan Outlet Node Name
Split MN2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MS1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MS1 Air Loop Outlet, !- Reference Setpoint Node Name
Split MS1 Mixed Air Outlet, !- Fan Inlet Node Name
Split MS1 Supply Fan Outlet, !- Fan Outlet Node Name
Split MS1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split MS2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split MS2 Air Loop Outlet, !- Reference Setpoint Node Name
Split MS2 Mixed Air Outlet, !- Fan Inlet Node Name
Split MS2 Supply Fan Outlet, !- Fan Outlet Node Name
Split MS2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TSW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TSW Air Loop Outlet, !- Reference Setpoint Node Name
Split TSW Mixed Air Outlet, !- Fan Inlet Node Name
Split TSW Supply Fan Outlet, !- Fan Outlet Node Name
Split TSW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TNW Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TNW Air Loop Outlet, !- Reference Setpoint Node Name
Split TNW Mixed Air Outlet, !- Fan Inlet Node Name
Split TNW Supply Fan Outlet, !- Fan Outlet Node Name
Split TNW Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TSE Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TSE Air Loop Outlet, !- Reference Setpoint Node Name
Split TSE Mixed Air Outlet, !- Fan Inlet Node Name
Split TSE Supply Fan Outlet, !- Fan Outlet Node Name
Split TSE Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TNE Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TNE Air Loop Outlet, !- Reference Setpoint Node Name
Split TNE Mixed Air Outlet, !- Fan Inlet Node Name
Split TNE Supply Fan Outlet, !- Fan Outlet Node Name
Split TNE Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TN1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TN1 Air Loop Outlet, !- Reference Setpoint Node Name
Split TN1 Mixed Air Outlet, !- Fan Inlet Node Name
Split TN1 Supply Fan Outlet, !- Fan Outlet Node Name
Split TN1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TN2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TN2 Air Loop Outlet, !- Reference Setpoint Node Name
Split TN2 Mixed Air Outlet, !- Fan Inlet Node Name
Split TN2 Supply Fan Outlet, !- Fan Outlet Node Name
Split TN2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TS1 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TS1 Air Loop Outlet, !- Reference Setpoint Node Name
Split TS1 Mixed Air Outlet, !- Fan Inlet Node Name
Split TS1 Supply Fan Outlet, !- Fan Outlet Node Name
Split TS1 Mixed Air Outlet; !- Setpoint Node or NodeList Name
SetpointManager:MixedAir,
Split TS2 Outdoor Air Temp Manager, !- Name
Temperature, !- Control Variable
Split TS2 Air Loop Outlet, !- Reference Setpoint Node Name
Split TS2 Mixed Air Outlet, !- Fan Inlet Node Name
Split TS2 Supply Fan Outlet, !- Fan Outlet Node Name
Split TS2 Mixed Air Outlet; !- Setpoint Node or NodeList Name
!- =========== ALL OBJECTS IN CLASS: CONTROLLER:OUTSIDE AIR ===========
Controller:OutdoorAir,
Split GSW OA Controller, !- Name
Split GSW Relief Air Outlet, !- Relief Air Outlet Node Name
Split GSW Air Loop Inlet,!- Return Air Node Name
Split GSW Mixed Air Outlet, !- Mixed Air Node Name
Split GSW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split GNW OA Controller, !- Name
Split GNW Relief Air Outlet, !- Relief Air Outlet Node Name
Split GNW Air Loop Inlet,!- Return Air Node Name
Split GNW Mixed Air Outlet, !- Mixed Air Node Name
Split GNW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split Office OA Controller, !- Name
Split Office Relief Air Outlet, !- Relief Air Outlet Node Name
Split Office Air Loop Inlet, !- Return Air Node Name
Split Office Mixed Air Outlet, !- Mixed Air Node Name
Split Office Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum; !- Minimum Limit Type
Controller:OutdoorAir,
Split GNE OA Controller, !- Name
Split GNE Relief Air Outlet, !- Relief Air Outlet Node Name
Split GNE Air Loop Inlet,!- Return Air Node Name
Split GNE Mixed Air Outlet, !- Mixed Air Node Name
Split GNE Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split GN1 OA Controller, !- Name
Split GN1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split GN1 Air Loop Inlet,!- Return Air Node Name
Split GN1 Mixed Air Outlet, !- Mixed Air Node Name
Split GN1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split GN2 OA Controller, !- Name
Split GN2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split GN2 Air Loop Inlet,!- Return Air Node Name
Split GN2 Mixed Air Outlet, !- Mixed Air Node Name
Split GN2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split GS1 OA Controller, !- Name
Split GS1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split GS1 Air Loop Inlet,!- Return Air Node Name
Split GS1 Mixed Air Outlet, !- Mixed Air Node Name
Split GS1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split GS2 OA Controller, !- Name
Split GS2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split GS2 Air Loop Inlet,!- Return Air Node Name
Split GS2 Mixed Air Outlet, !- Mixed Air Node Name
Split GS2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MSW OA Controller, !- Name
Split MSW Relief Air Outlet, !- Relief Air Outlet Node Name
Split MSW Air Loop Inlet,!- Return Air Node Name
Split MSW Mixed Air Outlet, !- Mixed Air Node Name
Split MSW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MNW OA Controller, !- Name
Split MNW Relief Air Outlet, !- Relief Air Outlet Node Name
Split MNW Air Loop Inlet,!- Return Air Node Name
Split MNW Mixed Air Outlet, !- Mixed Air Node Name
Split MNW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MSE OA Controller, !- Name
Split MSE Relief Air Outlet, !- Relief Air Outlet Node Name
Split MSE Air Loop Inlet,!- Return Air Node Name
Split MSE Mixed Air Outlet, !- Mixed Air Node Name
Split MSE Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MNE OA Controller, !- Name
Split MNE Relief Air Outlet, !- Relief Air Outlet Node Name
Split MNE Air Loop Inlet,!- Return Air Node Name
Split MNE Mixed Air Outlet, !- Mixed Air Node Name
Split MNE Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MN1 OA Controller, !- Name
Split MN1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split MN1 Air Loop Inlet,!- Return Air Node Name
Split MN1 Mixed Air Outlet, !- Mixed Air Node Name
Split MN1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MN2 OA Controller, !- Name
Split MN2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split MN2 Air Loop Inlet,!- Return Air Node Name
Split MN2 Mixed Air Outlet, !- Mixed Air Node Name
Split MN2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MS1 OA Controller, !- Name
Split MS1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split MS1 Air Loop Inlet,!- Return Air Node Name
Split MS1 Mixed Air Outlet, !- Mixed Air Node Name
Split MS1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split MS2 OA Controller, !- Name
Split MS2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split MS2 Air Loop Inlet,!- Return Air Node Name
Split MS2 Mixed Air Outlet, !- Mixed Air Node Name
Split MS2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TSW OA Controller, !- Name
Split TSW Relief Air Outlet, !- Relief Air Outlet Node Name
Split TSW Air Loop Inlet,!- Return Air Node Name
Split TSW Mixed Air Outlet, !- Mixed Air Node Name
Split TSW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TNW OA Controller, !- Name
Split TNW Relief Air Outlet, !- Relief Air Outlet Node Name
Split TNW Air Loop Inlet,!- Return Air Node Name
Split TNW Mixed Air Outlet, !- Mixed Air Node Name
Split TNW Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TSE OA Controller, !- Name
Split TSE Relief Air Outlet, !- Relief Air Outlet Node Name
Split TSE Air Loop Inlet,!- Return Air Node Name
Split TSE Mixed Air Outlet, !- Mixed Air Node Name
Split TSE Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TNE OA Controller, !- Name
Split TNE Relief Air Outlet, !- Relief Air Outlet Node Name
Split TNE Air Loop Inlet,!- Return Air Node Name
Split TNE Mixed Air Outlet, !- Mixed Air Node Name
Split TNE Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TN1 OA Controller, !- Name
Split TN1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split TN1 Air Loop Inlet,!- Return Air Node Name
Split TN1 Mixed Air Outlet, !- Mixed Air Node Name
Split TN1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TN2 OA Controller, !- Name
Split TN2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split TN2 Air Loop Inlet,!- Return Air Node Name
Split TN2 Mixed Air Outlet, !- Mixed Air Node Name
Split TN2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TS1 OA Controller, !- Name
Split TS1 Relief Air Outlet, !- Relief Air Outlet Node Name
Split TS1 Air Loop Inlet,!- Return Air Node Name
Split TS1 Mixed Air Outlet, !- Mixed Air Node Name
Split TS1 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
Controller:OutdoorAir,
Split TS2 OA Controller, !- Name
Split TS2 Relief Air Outlet, !- Relief Air Outlet Node Name
Split TS2 Air Loop Inlet,!- Return Air Node Name
Split TS2 Mixed Air Outlet, !- Mixed Air Node Name
Split TS2 Outside Air Inlet, !- Actuator Node Name
autosize, !- Minimum Outdoor Air Flow Rate {m3/s}
autosize, !- Maximum Outdoor Air Flow Rate {m3/s}
NoEconomizer, !- Economizer Control Type
ModulateFlow, !- Economizer Control Action Type
, !- Economizer Maximum Limit Dry-Bulb Temperature {C}
, !- Economizer Maximum Limit Enthalpy {J/kg}
, !- Economizer Maximum Limit Dewpoint Temperature {C}
, !- Electronic Enthalpy Limit Curve Name
, !- Economizer Minimum Limit Dry-Bulb Temperature {C}
LockoutWithHeating, !- Lockout Type
FixedMinimum, !- Minimum Limit Type
All Off, !- Minimum Outdoor Air Schedule Name
, !- Minimum Fraction of Outdoor Air Schedule Name
, !- Maximum Fraction of Outdoor Air Schedule Name
, !- Mechanical Ventilation Controller Name
, !- Time of Day Economizer Control Schedule Name
, !- High Humidity Control
, !- Humidistat Control Zone Name
, !- High Humidity Outdoor Air Flow Ratio
, !- Control High Indoor Humidity Based on Outdoor Humidity Ratio
BypassWhenWithinEconomizerLimits; !- Heat Recovery Bypass Control Type
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G SW Apartment ERV, !- Name
All On, !- Availability Schedule Name
G SW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G SW Apartment ERV Sup Fan, !- Supply Air Fan Name
G SW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G SW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G SW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G SW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G SW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G SW Apartment Outside Air Node, !- Supply Air Inlet Node Name
G SW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G SW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G SW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G SW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G SW Apartment ERV Outlet Node, !- Air Inlet Node Name
G SW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G SW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G SW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G SW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G NW Apartment ERV, !- Name
All On, !- Availability Schedule Name
G NW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G NW Apartment ERV Sup Fan, !- Supply Air Fan Name
G NW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G NW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G NW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G NW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G NW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G NW Apartment Outside Air Node, !- Supply Air Inlet Node Name
G NW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G NW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G NW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G NW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G NW Apartment ERV Outlet Node, !- Air Inlet Node Name
G NW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G NW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G NW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G NW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G NE Apartment ERV, !- Name
All On, !- Availability Schedule Name
G NE Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G NE Apartment ERV Sup Fan, !- Supply Air Fan Name
G NE Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G NE Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G NE Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G NE Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G NE Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G NE Apartment Outside Air Node, !- Supply Air Inlet Node Name
G NE Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G NE Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G NE Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G NE Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G NE Apartment ERV Outlet Node, !- Air Inlet Node Name
G NE Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G NE Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G NE Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G NE Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G N1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
G N1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G N1 Apartment ERV Sup Fan, !- Supply Air Fan Name
G N1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G N1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G N1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G N1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G N1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G N1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
G N1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G N1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G N1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G N1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G N1 Apartment ERV Outlet Node, !- Air Inlet Node Name
G N1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G N1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G N1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G N1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G N2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
G N2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G N2 Apartment ERV Sup Fan, !- Supply Air Fan Name
G N2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G N2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G N2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G N2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G N2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G N2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
G N2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G N2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G N2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G N2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G N2 Apartment ERV Outlet Node, !- Air Inlet Node Name
G N2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G N2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G N2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G N2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G S1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
G S1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G S1 Apartment ERV Sup Fan, !- Supply Air Fan Name
G S1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G S1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G S1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G S1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G S1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G S1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
G S1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G S1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G S1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G S1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G S1 Apartment ERV Outlet Node, !- Air Inlet Node Name
G S1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G S1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G S1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G S1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
G S2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
G S2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
G S2 Apartment ERV Sup Fan, !- Supply Air Fan Name
G S2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
G S2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
G S2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
G S2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
G S2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
G S2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
G S2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
G S2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
G S2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
G S2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G S2 Apartment ERV Outlet Node, !- Air Inlet Node Name
G S2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
G S2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
G S2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
G S2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M SW Apartment ERV, !- Name
All On, !- Availability Schedule Name
M SW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M SW Apartment ERV Sup Fan, !- Supply Air Fan Name
M SW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M SW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M SW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M SW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M SW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M SW Apartment Outside Air Node, !- Supply Air Inlet Node Name
M SW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M SW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M SW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M SW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M SW Apartment ERV Outlet Node, !- Air Inlet Node Name
M SW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M SW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M SW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M SW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M NW Apartment ERV, !- Name
All On, !- Availability Schedule Name
M NW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M NW Apartment ERV Sup Fan, !- Supply Air Fan Name
M NW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M NW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M NW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M NW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M NW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M NW Apartment Outside Air Node, !- Supply Air Inlet Node Name
M NW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M NW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M NW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M NW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M NW Apartment ERV Outlet Node, !- Air Inlet Node Name
M NW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M NW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M NW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M NW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M SE Apartment ERV, !- Name
All On, !- Availability Schedule Name
M SE Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M SE Apartment ERV Sup Fan, !- Supply Air Fan Name
M SE Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M SE Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M SE Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M SE Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M SE Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M SE Apartment Outside Air Node, !- Supply Air Inlet Node Name
M SE Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M SE Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M SE Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M SE Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M SE Apartment ERV Outlet Node, !- Air Inlet Node Name
M SE Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M SE Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M SE Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M SE Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M NE Apartment ERV, !- Name
All On, !- Availability Schedule Name
M NE Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M NE Apartment ERV Sup Fan, !- Supply Air Fan Name
M NE Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M NE Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M NE Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M NE Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M NE Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M NE Apartment Outside Air Node, !- Supply Air Inlet Node Name
M NE Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M NE Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M NE Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M NE Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M NE Apartment ERV Outlet Node, !- Air Inlet Node Name
M NE Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M NE Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M NE Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M NE Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M N1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
M N1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M N1 Apartment ERV Sup Fan, !- Supply Air Fan Name
M N1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M N1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M N1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M N1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M N1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M N1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
M N1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M N1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M N1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M N1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M N1 Apartment ERV Outlet Node, !- Air Inlet Node Name
M N1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M N1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M N1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M N1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M N2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
M N2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M N2 Apartment ERV Sup Fan, !- Supply Air Fan Name
M N2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M N2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M N2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M N2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M N2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M N2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
M N2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M N2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M N2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M N2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M N2 Apartment ERV Outlet Node, !- Air Inlet Node Name
M N2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M N2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M N2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M N2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M S1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
M S1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M S1 Apartment ERV Sup Fan, !- Supply Air Fan Name
M S1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M S1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M S1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M S1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M S1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M S1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
M S1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M S1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M S1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M S1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M S1 Apartment ERV Outlet Node, !- Air Inlet Node Name
M S1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M S1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M S1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M S1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
M S2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
M S2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
M S2 Apartment ERV Sup Fan, !- Supply Air Fan Name
M S2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
M S2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
M S2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
M S2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
M S2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
M S2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
M S2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
M S2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
M S2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
M S2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M S2 Apartment ERV Outlet Node, !- Air Inlet Node Name
M S2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
M S2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
M S2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
M S2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T SW Apartment ERV, !- Name
All On, !- Availability Schedule Name
T SW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T SW Apartment ERV Sup Fan, !- Supply Air Fan Name
T SW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T SW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T SW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T SW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T SW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T SW Apartment Outside Air Node, !- Supply Air Inlet Node Name
T SW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T SW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T SW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T SW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T SW Apartment ERV Outlet Node, !- Air Inlet Node Name
T SW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T SW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T SW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T SW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T NW Apartment ERV, !- Name
All On, !- Availability Schedule Name
T NW Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T NW Apartment ERV Sup Fan, !- Supply Air Fan Name
T NW Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T NW Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T NW Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T NW Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T NW Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T NW Apartment Outside Air Node, !- Supply Air Inlet Node Name
T NW Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T NW Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T NW Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T NW Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T NW Apartment ERV Outlet Node, !- Air Inlet Node Name
T NW Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T NW Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T NW Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T NW Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T SE Apartment ERV, !- Name
All On, !- Availability Schedule Name
T SE Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T SE Apartment ERV Sup Fan, !- Supply Air Fan Name
T SE Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T SE Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T SE Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T SE Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T SE Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T SE Apartment Outside Air Node, !- Supply Air Inlet Node Name
T SE Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T SE Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T SE Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T SE Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T SE Apartment ERV Outlet Node, !- Air Inlet Node Name
T SE Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T SE Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T SE Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T SE Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T NE Apartment ERV, !- Name
All On, !- Availability Schedule Name
T NE Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T NE Apartment ERV Sup Fan, !- Supply Air Fan Name
T NE Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T NE Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T NE Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T NE Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T NE Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T NE Apartment Outside Air Node, !- Supply Air Inlet Node Name
T NE Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T NE Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T NE Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T NE Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T NE Apartment ERV Outlet Node, !- Air Inlet Node Name
T NE Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T NE Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T NE Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T NE Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T N1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
T N1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T N1 Apartment ERV Sup Fan, !- Supply Air Fan Name
T N1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T N1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T N1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T N1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T N1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T N1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
T N1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T N1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T N1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T N1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T N1 Apartment ERV Outlet Node, !- Air Inlet Node Name
T N1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T N1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T N1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T N1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T N2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
T N2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T N2 Apartment ERV Sup Fan, !- Supply Air Fan Name
T N2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T N2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T N2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T N2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T N2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T N2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
T N2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T N2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T N2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T N2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T N2 Apartment ERV Outlet Node, !- Air Inlet Node Name
T N2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T N2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T N2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T N2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T S1 Apartment ERV, !- Name
All On, !- Availability Schedule Name
T S1 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T S1 Apartment ERV Sup Fan, !- Supply Air Fan Name
T S1 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T S1 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T S1 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T S1 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T S1 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T S1 Apartment Outside Air Node, !- Supply Air Inlet Node Name
T S1 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T S1 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T S1 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T S1 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T S1 Apartment ERV Outlet Node, !- Air Inlet Node Name
T S1 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T S1 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T S1 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T S1 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS related to CLASS: ZoneHVAC:EnergyRecoveryVentilator
ZoneHVAC:EnergyRecoveryVentilator,
T S2 Apartment ERV, !- Name
All On, !- Availability Schedule Name
T S2 Apartment OA Heat Exchanger, !- Heat Exchanger Name
0.025957109, !- Supply Air Flow Rate {m3/s}
0.025957109, !- Exhaust Air Flow Rate {m3/s}
T S2 Apartment ERV Sup Fan, !- Supply Air Fan Name
T S2 Apartment ERV Exh Fan, !- Exhaust Air Fan Name
T S2 Apartment ERV Ctrl; !- ERV controller name
ZoneHVAC:EnergyRecoveryVentilator:Controller,
T S2 Apartment ERV Ctrl, !- Name
, !- Temperature High Limit {C}
, !- Temperature Low Limit {C}
, !- Enthalpy High Limit {J/kg}
, !- Dewpoint Temperature Limit {C}
, !- Electronic Enthalpy Limit Curve Name
NoExhaustAirTemperatureLimit, !- Exhaust Air Temperature Limit
NoExhaustAirEnthalpyLimit, !- Exhaust Air Enthalpy Limit
, !- Time of Day Economizer Flow Control S
No, !- High Humidity Control Flag
, !- Humidistat Control Zone Name
1, !- High Humidity Outdoor Air Flow Ratio
No; !- Control High Indoor Humidity Based on Outdoor Humidity ratio
OutdoorAir:Node,
T S2 Apartment Outside Air Node; !- 1st Node name or node list name
HeatExchanger:AirToAir:SensibleAndLatent,
T S2 Apartment OA Heat Exchanger, !- Name
AllOn_Except_DD, !- Availability Schedule Name
AUTOSIZE, !- Nominal Supply Air Flow Rate {m3/s}
0.6, !- Sensible Effectiveness at 100% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Heating Air Flow {dimensionless}
0.623, !- Sensible Effectiveness at 75% Heating Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Heating Air Flow {dimensionless}
0.596, !- Sensible Effectiveness at 100% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 100% Cooling Air Flow {dimensionless}
0.618, !- Sensible Effectiveness at 75% Cooling Air Flow {dimensionless}
0, !- Latent Effectiveness at 75% Cooling Air Flow {dimensionless}
T S2 Apartment Outside Air Node, !- Supply Air Inlet Node Name
T S2 Apartment ERV Outlet Node, !- Supply Air Outlet Node Name
T S2 Apartment Zone Exhaust Node, !- Exhaust Air Inlet Node Name
T S2 Apartment ERV Secondary Outlet Node, !- Exhaust Air Outlet Node Name
0, !- Nominal Electric Power {W}
No, !- Supply Air Outlet Temperature Control
Rotary, !- Heat Exchanger Type
ExhaustOnly, !- Frost Control Type
-23.3, !- Threshold Temperature {C}
0.167, !- Initial Defrost Time Fraction {dimensionless}
1.44; !- Rate of Defrost Time Fraction Increase {1/K}
Fan:OnOff,
T S2 Apartment ERV Sup Fan, !- Name
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T S2 Apartment ERV Outlet Node, !- Air Inlet Node Name
T S2 Apartment ERV Sup Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
T S2 Apartment ERV Exh Fan, !-
All On, !- Availability Schedule Name
0.303158, !- Fan Total Efficiency
270.64755, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.48, !- Motor Efficiency
1, !- Motor In Airstream Fraction
T S2 Apartment ERV Secondary Outlet Node, !- Air Inlet Node Name
T S2 Apartment ERV Exh Fan Outlet Node, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!- =========== ALL OBJECTS IN CLASS: CONTROLLED ZONE EQUIP CONFIGURATION ===========
ZoneHVAC:EquipmentConnections,
G SW Apartment, !- Zone Name
G SW Apartment Equipment,!- Zone Conditioning Equipment List Name
G SW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G SW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G SW Apartment Zone Air Node, !- Zone Air Node Name
G SW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G SW Apartment Zone Inlets, !- Node List Name
G SW Apartment Zone Equip Inlet, !- Node_ID_1
G SW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
G NW Apartment, !- Zone Name
G NW Apartment Equipment,!- Zone Conditioning Equipment List Name
G NW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G NW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G NW Apartment Zone Air Node, !- Zone Air Node Name
G NW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G NW Apartment Zone Inlets, !- Node List Name
G NW Apartment Zone Equip Inlet, !- Node_ID_1
G NW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
Office, !- Zone Name
Office Equipment, !- Zone Conditioning Equipment List Name
Office Zone Equip Inlet, !- Zone Air Inlet Node or NodeList Name
, !- Zone Air Exhaust Node or NodeList Name
Office Zone Air Node, !- Zone Air Node Name
Office Return Outlet; !- Zone Return Air Node or NodeList Name
ZoneHVAC:EquipmentConnections,
G NE Apartment, !- Zone Name
G NE Apartment Equipment,!- Zone Conditioning Equipment List Name
G NE Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G NE Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G NE Apartment Zone Air Node, !- Zone Air Node Name
G NE Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G NE Apartment Zone Inlets, !- Node List Name
G NE Apartment Zone Equip Inlet, !- Node_ID_1
G NE Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
G N1 Apartment, !- Zone Name
G N1 Apartment Equipment,!- Zone Conditioning Equipment List Name
G N1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G N1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G N1 Apartment Zone Air Node, !- Zone Air Node Name
G N1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G N1 Apartment Zone Inlets, !- Node List Name
G N1 Apartment Zone Equip Inlet, !- Node_ID_1
G N1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
G N2 Apartment, !- Zone Name
G N2 Apartment Equipment,!- Zone Conditioning Equipment List Name
G N2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G N2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G N2 Apartment Zone Air Node, !- Zone Air Node Name
G N2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G N2 Apartment Zone Inlets, !- Node List Name
G N2 Apartment Zone Equip Inlet, !- Node_ID_1
G N2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
G S1 Apartment, !- Zone Name
G S1 Apartment Equipment,!- Zone Conditioning Equipment List Name
G S1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G S1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G S1 Apartment Zone Air Node, !- Zone Air Node Name
G S1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G S1 Apartment Zone Inlets, !- Node List Name
G S1 Apartment Zone Equip Inlet, !- Node_ID_1
G S1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
G S2 Apartment, !- Zone Name
G S2 Apartment Equipment,!- Zone Conditioning Equipment List Name
G S2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
G S2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
G S2 Apartment Zone Air Node, !- Zone Air Node Name
G S2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
G S2 Apartment Zone Inlets, !- Node List Name
G S2 Apartment Zone Equip Inlet, !- Node_ID_1
G S2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M SW Apartment, !- Zone Name
M SW Apartment Equipment,!- Zone Conditioning Equipment List Name
M SW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M SW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M SW Apartment Zone Air Node, !- Zone Air Node Name
M SW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M SW Apartment Zone Inlets, !- Node List Name
M SW Apartment Zone Equip Inlet, !- Node_ID_1
M SW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M NW Apartment, !- Zone Name
M NW Apartment Equipment,!- Zone Conditioning Equipment List Name
M NW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M NW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M NW Apartment Zone Air Node, !- Zone Air Node Name
M NW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M NW Apartment Zone Inlets, !- Node List Name
M NW Apartment Zone Equip Inlet, !- Node_ID_1
M NW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M SE Apartment, !- Zone Name
M SE Apartment Equipment,!- Zone Conditioning Equipment List Name
M SE Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M SE Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M SE Apartment Zone Air Node, !- Zone Air Node Name
M SE Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M SE Apartment Zone Inlets, !- Node List Name
M SE Apartment Zone Equip Inlet, !- Node_ID_1
M SE Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M NE Apartment, !- Zone Name
M NE Apartment Equipment,!- Zone Conditioning Equipment List Name
M NE Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M NE Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M NE Apartment Zone Air Node, !- Zone Air Node Name
M NE Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M NE Apartment Zone Inlets, !- Node List Name
M NE Apartment Zone Equip Inlet, !- Node_ID_1
M NE Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M N1 Apartment, !- Zone Name
M N1 Apartment Equipment,!- Zone Conditioning Equipment List Name
M N1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M N1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M N1 Apartment Zone Air Node, !- Zone Air Node Name
M N1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M N1 Apartment Zone Inlets, !- Node List Name
M N1 Apartment Zone Equip Inlet, !- Node_ID_1
M N1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M N2 Apartment, !- Zone Name
M N2 Apartment Equipment,!- Zone Conditioning Equipment List Name
M N2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M N2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M N2 Apartment Zone Air Node, !- Zone Air Node Name
M N2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M N2 Apartment Zone Inlets, !- Node List Name
M N2 Apartment Zone Equip Inlet, !- Node_ID_1
M N2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M S1 Apartment, !- Zone Name
M S1 Apartment Equipment,!- Zone Conditioning Equipment List Name
M S1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M S1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M S1 Apartment Zone Air Node, !- Zone Air Node Name
M S1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M S1 Apartment Zone Inlets, !- Node List Name
M S1 Apartment Zone Equip Inlet, !- Node_ID_1
M S1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
M S2 Apartment, !- Zone Name
M S2 Apartment Equipment,!- Zone Conditioning Equipment List Name
M S2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
M S2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
M S2 Apartment Zone Air Node, !- Zone Air Node Name
M S2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
M S2 Apartment Zone Inlets, !- Node List Name
M S2 Apartment Zone Equip Inlet, !- Node_ID_1
M S2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T SW Apartment, !- Zone Name
T SW Apartment Equipment,!- Zone Conditioning Equipment List Name
T SW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T SW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T SW Apartment Zone Air Node, !- Zone Air Node Name
T SW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T SW Apartment Zone Inlets, !- Node List Name
T SW Apartment Zone Equip Inlet, !- Node_ID_1
T SW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T NW Apartment, !- Zone Name
T NW Apartment Equipment,!- Zone Conditioning Equipment List Name
T NW Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T NW Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T NW Apartment Zone Air Node, !- Zone Air Node Name
T NW Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T NW Apartment Zone Inlets, !- Node List Name
T NW Apartment Zone Equip Inlet, !- Node_ID_1
T NW Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T SE Apartment, !- Zone Name
T SE Apartment Equipment,!- Zone Conditioning Equipment List Name
T SE Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T SE Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T SE Apartment Zone Air Node, !- Zone Air Node Name
T SE Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T SE Apartment Zone Inlets, !- Node List Name
T SE Apartment Zone Equip Inlet, !- Node_ID_1
T SE Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T NE Apartment, !- Zone Name
T NE Apartment Equipment,!- Zone Conditioning Equipment List Name
T NE Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T NE Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T NE Apartment Zone Air Node, !- Zone Air Node Name
T NE Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T NE Apartment Zone Inlets, !- Node List Name
T NE Apartment Zone Equip Inlet, !- Node_ID_1
T NE Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T N1 Apartment, !- Zone Name
T N1 Apartment Equipment,!- Zone Conditioning Equipment List Name
T N1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T N1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T N1 Apartment Zone Air Node, !- Zone Air Node Name
T N1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T N1 Apartment Zone Inlets, !- Node List Name
T N1 Apartment Zone Equip Inlet, !- Node_ID_1
T N1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T N2 Apartment, !- Zone Name
T N2 Apartment Equipment,!- Zone Conditioning Equipment List Name
T N2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T N2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T N2 Apartment Zone Air Node, !- Zone Air Node Name
T N2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T N2 Apartment Zone Inlets, !- Node List Name
T N2 Apartment Zone Equip Inlet, !- Node_ID_1
T N2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T S1 Apartment, !- Zone Name
T S1 Apartment Equipment,!- Zone Conditioning Equipment List Name
T S1 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T S1 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T S1 Apartment Zone Air Node, !- Zone Air Node Name
T S1 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T S1 Apartment Zone Inlets, !- Node List Name
T S1 Apartment Zone Equip Inlet, !- Node_ID_1
T S1 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
ZoneHVAC:EquipmentConnections,
T S2 Apartment, !- Zone Name
T S2 Apartment Equipment,!- Zone Conditioning Equipment List Name
T S2 Apartment Zone Inlets, !- Zone Air Inlet Node or NodeList Name
T S2 Apartment Zone Exhaust Node, !- Zone Air Exhaust Node or NodeList Name
T S2 Apartment Zone Air Node, !- Zone Air Node Name
T S2 Apartment Return Outlet; !- Zone Return Air Node or NodeList Name
NodeList,
T S2 Apartment Zone Inlets, !- Node List Name
T S2 Apartment Zone Equip Inlet, !- Node_ID_1
T S2 Apartment ERV Sup Fan Outlet Node; !- Node_ID_2
!- =========== ALL OBJECTS IN CLASS: ZONE EQUIPMENT LIST ===========
ZoneHVAC:EquipmentList,
G SW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G SW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G SW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G NW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G NW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G NW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
Office Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
Office Direct Air, !- Zone Equipment 1 Name
1, !- Zone Equipment 1 Cooling Sequence
1; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G NE Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G NE Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G NE Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G N1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G N1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G N1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G N2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G N2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G N2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G S1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G S1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G S1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
G S2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
G S2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
G S2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M SW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M SW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M SW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M NW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M NW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M NW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M SE Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M SE Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M SE Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M NE Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M NE Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M NE Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M N1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M N1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M N1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M N2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M N2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M N2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M S1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M S1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M S1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
M S2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
M S2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
M S2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T SW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T SW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T SW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T NW Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T NW Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T NW Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T SE Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T SE Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T SE Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T NE Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T NE Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T NE Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T N1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T N1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T N1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T N2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T N2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T N2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T S1 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T S1 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T S1 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
ZoneHVAC:EquipmentList,
T S2 Apartment Equipment, !- Name
SequentialLoad, !- Load Distribution Scheme
ZoneHVAC:EnergyRecoveryVentilator , !- KEY --Zone Equipment Type 2
T S2 Apartment ERV, !- Zone Equipment 2 Name
1, !- Zone Equipment 2 Cooling Sequence
1, !- Zone Equipment 2 Heating or No-Load Sequence
AirTerminal:SingleDuct:Uncontrolled, !- Zone Equipment 1 Object Type
T S2 Apartment Direct Air, !- Zone Equipment 1 Name
2, !- Zone Equipment 1 Cooling Sequence
2; !- Zone Equipment 1 Heating or No-Load Sequence
!- =========== ALL OBJECTS IN CLASS: FURNACE:HEATCOOL ===========
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GSW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GSW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GSW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G SW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GSW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GSW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GSW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GNW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GNW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GNW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G NW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GNW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GNW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GNW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split Office Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split Office Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split Office Air Loop Outlet, !- Furnace Air Outlet Node Name
FAN_OFF_w_SB_SCH, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
Office, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split Office Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split Office Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split Office Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GNE Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GNE Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GNE Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G NE Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GNE Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GNE Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GNE Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GN1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GN1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GN1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G N1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GN1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GN1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GN1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GN2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GN2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GN2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G N2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GN2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GN2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GN2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GS1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GS1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GS1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G S1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GS1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GS1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GS1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split GS2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split GS2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split GS2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
G S2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split GS2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split GS2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split GS2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MSW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MSW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MSW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M SW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MSW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MSW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MSW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MNW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MNW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MNW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M NW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MNW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MNW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MNW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MSE Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MSE Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MSE Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M SE Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MSE Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MSE Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MSE Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MNE Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MNE Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MNE Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M NE Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MNE Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MNE Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MNE Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MN1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MN1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MN1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M N1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MN1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MN1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MN1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MN2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MN2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MN2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M N2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MN2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MN2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MN2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MS1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MS1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MS1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M S1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MS1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MS1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MS1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split MS2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split MS2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split MS2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
M S2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split MS2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split MS2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split MS2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TSW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TSW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TSW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T SW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TSW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TSW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TSW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TNW Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TNW Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TNW Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T NW Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TNW Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TNW Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TNW Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TSE Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TSE Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TSE Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T SE Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TSE Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TSE Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TSE Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TNE Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TNE Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TNE Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T NE Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TNE Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TNE Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TNE Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TN1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TN1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TN1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T N1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TN1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TN1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TN1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TN2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TN2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TN2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T N2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TN2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TN2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TN2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TS1 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TS1 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TS1 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T S1 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TS1 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TS1 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TS1 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
AirLoopHVAC:Unitary:Furnace:HeatCool,
Split TS2 Furnace with DX Cooling, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Split TS2 Mixed Air Outlet, !- Furnace Air Inlet Node Name
Split TS2 Air Loop Outlet, !- Furnace Air Outlet Node Name
All Off, !- Supply Air Fan Operating Mode Schedule Name
80, !- Maximum Supply Air Temperature {C}
autosize, !- Cooling Supply Air Flow Rate {m3/s}
autosize, !- Heating Supply Air Flow Rate {m3/s}
autosize, !- No Load Supply Air Flow Rate {m3/s}
T S2 Apartment, !- Controlling Zone or Thermostat Location
Fan:OnOff, !- Supply Fan Object Type
Split TS2 Supply Fan, !- Supply Fan Name
BlowThrough, !- Fan Placement
Coil:Heating:Fuel, !- Heating Coil Object Type
Split TS2 Heating Coil, !- Heating Coil Name
Coil:Cooling:DX:SingleSpeed, !- Cooling Coil Object Type
Split TS2 Cooling Coil, !- Cooling Coil Name
None; !- Dehumidification Control Type
!- =========== ALL OBJECTS IN CLASS: DIRECT AIR ===========
AirTerminal:SingleDuct:Uncontrolled,
G SW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G SW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G NW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G NW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
Office Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
Office Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G NE Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G NE Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G N1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G N1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G N2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G N2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G S1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G S1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
G S2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
G S2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M SW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M SW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M NW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M NW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M SE Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M SE Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M NE Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M NE Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M N1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M N1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M N2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M N2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M S1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M S1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
M S2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
M S2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T SW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T SW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T NW Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T NW Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T SE Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T SE Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T NE Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T NE Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T N1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T N1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T N2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T N2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T S1 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T S1 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
AirTerminal:SingleDuct:Uncontrolled,
T S2 Apartment Direct Air, !- Name
COMPACT HVAC-ALWAYS 1, !- Availability Schedule Name
T S2 Apartment Zone Equip Inlet, !- Zone Supply Air Node Name
autosize; !- Maximum Air Flow Rate {m3/s}
!- =========== ALL OBJECTS IN CLASS: ZONE CONTROL:THERMOSTATIC ===========
ZoneControl:Thermostat,
G SW Apartment Thermostat, !- Name
G SW Apartment, !- Zone or ZoneList Name
ZONE CONTROL TYPE SCHED, !- Control Type Schedule Name
ThermostatSetpoint:SingleCooling, !- Control 1 Object Type
AptCoolingSetPoint, !- Control 1 Name
ThermostatSetpoint:SingleHeating, !- Control 2 Object Type
AptHeatingSetPoint, !- Control 2 Name
ThermostatSetpoint:DualSetpoint, !- Control 3 Object Type
S Apartment Dual SP Control; !- Control 3 Name
ZoneControl:Thermostat,
G NW Apartment Thermostat, !- Name
G NW Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
Office Thermostat, !- Name
Office, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
Office Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
G NE Apartment Thermostat, !- Name
G NE Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
G N1 Apartment Thermostat, !- Name
G N1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
G N2 Apartment Thermostat, !- Name
G N2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
G S1 Apartment Thermostat, !- Name
G S1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
G S2 Apartment Thermostat, !- Name
G S2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M SW Apartment Thermostat, !- Name
M SW Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M NW Apartment Thermostat, !- Name
M NW Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M SE Apartment Thermostat, !- Name
M SE Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M NE Apartment Thermostat, !- Name
M NE Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M N1 Apartment Thermostat, !- Name
M N1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M N2 Apartment Thermostat, !- Name
M N2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M S1 Apartment Thermostat, !- Name
M S1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
M S2 Apartment Thermostat, !- Name
M S2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T SW Apartment Thermostat, !- Name
T SW Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T NW Apartment Thermostat, !- Name
T NW Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T SE Apartment Thermostat, !- Name
T SE Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T NE Apartment Thermostat, !- Name
T NE Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T N1 Apartment Thermostat, !- Name
T N1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T N2 Apartment Thermostat, !- Name
T N2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
N Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T S1 Apartment Thermostat, !- Name
T S1 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
ZoneControl:Thermostat,
T S2 Apartment Thermostat, !- Name
T S2 Apartment, !- Zone or ZoneList Name
COMPACT HVAC-ALWAYS 4, !- Control Type Schedule Name
ThermostatSetpoint:DualSetpoint, !- Control 1 Object Type
S Apartment Dual SP Control; !- Control 1 Name
!- =========== ALL OBJECTS IN CLASS: THERMOSTATSETPOINT:SINGLEHEATING ===========
ThermostatSetpoint:SingleHeating,
AptHeatingSetPoint, !- Name
HTGSETP_APT_SCH; !- Setpoint Temperature Schedule Name
!- =========== ALL OBJECTS IN CLASS: THERMOSTATSETPOINT:SINGLECOOLING ===========
ThermostatSetpoint:SingleCooling,
AptCoolingSetPoint, !- Name
CLGSETP_APT_SCH; !- Setpoint Temperature Schedule Name
!- =========== ALL OBJECTS IN CLASS: DUAL SETPOINT WITH DEADBAND ===========
ThermostatSetpoint:DualSetpoint,
S Apartment Dual SP Control, !- Name
S HTGSETP_APT_SCH, !- Heating Setpoint Temperature Schedule Name
S CLGSETP_APT_SCH; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
N Apartment Dual SP Control, !- Name
N HTGSETP_APT_SCH, !- Heating Setpoint Temperature Schedule Name
N CLGSETP_APT_SCH; !- Cooling Setpoint Temperature Schedule Name
ThermostatSetpoint:DualSetpoint,
Office Dual SP Control, !- Name
HTGSETP_OFF_SCH_NO_OPTIMUM, !- Heating Setpoint Temperature Schedule Name
CLGSETP_OFF_SCH_No_Optimum; !- Cooling Setpoint Temperature Schedule Name
!- =========== ALL OBJECTS IN CLASS: ZONE SUPPLY AIR PATH ===========
AirLoopHVAC:SupplyPath,
Split GSW Supply Path, !- Name
Split GSW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GSW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GNW Supply Path, !- Name
Split GNW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GNW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split Office Supply Path,!- Name
Split Office Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split Office Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GNE Supply Path, !- Name
Split GNE Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GNE Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GN1 Supply Path, !- Name
Split GN1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GN1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GN2 Supply Path, !- Name
Split GN2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GN2 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GS1 Supply Path, !- Name
Split GS1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GS1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split GS2 Supply Path, !- Name
Split GS2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split GS2 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MSW Supply Path, !- Name
Split MSW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MSW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MNW Supply Path, !- Name
Split MNW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MNW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MSE Supply Path, !- Name
Split MSE Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MSE Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MNE Supply Path, !- Name
Split MNE Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MNE Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MN1 Supply Path, !- Name
Split MN1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MN1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MN2 Supply Path, !- Name
Split MN2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MN2 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MS1 Supply Path, !- Name
Split MS1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MS1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split MS2 Supply Path, !- Name
Split MS2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split MS2 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TSW Supply Path, !- Name
Split TSW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TSW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TNW Supply Path, !- Name
Split TNW Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TNW Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TSE Supply Path, !- Name
Split TSE Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TSE Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TNE Supply Path, !- Name
Split TNE Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TNE Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TN1 Supply Path, !- Name
Split TN1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TN1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TN2 Supply Path, !- Name
Split TN2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TN2 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TS1 Supply Path, !- Name
Split TS1 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TS1 Zone Splitter; !- Component 1 Name
AirLoopHVAC:SupplyPath,
Split TS2 Supply Path, !- Name
Split TS2 Supply Path Inlet, !- Supply Air Path Inlet Node Name
AirLoopHVAC:ZoneSplitter,!- Component 1 Object Type
Split TS2 Zone Splitter; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: ZONE RETURN AIR PATH ===========
AirLoopHVAC:ReturnPath,
Split GSW Return Path, !- Name
Split GSW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GSW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GNW Return Path, !- Name
Split GNW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GNW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split Office Return Path,!- Name
Split Office Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split Office Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GNE Return Path, !- Name
Split GNE Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GNE Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GN1 Return Path, !- Name
Split GN1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GN1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GN2 Return Path, !- Name
Split GN2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GN2 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GS1 Return Path, !- Name
Split GS1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GS1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split GS2 Return Path, !- Name
Split GS2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split GS2 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MSW Return Path, !- Name
Split MSW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MSW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MNW Return Path, !- Name
Split MNW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MNW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MSE Return Path, !- Name
Split MSE Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MSE Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MNE Return Path, !- Name
Split MNE Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MNE Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MN1 Return Path, !- Name
Split MN1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MN1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MN2 Return Path, !- Name
Split MN2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MN2 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MS1 Return Path, !- Name
Split MS1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MS1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split MS2 Return Path, !- Name
Split MS2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split MS2 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TSW Return Path, !- Name
Split TSW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TSW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TNW Return Path, !- Name
Split TNW Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TNW Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TSE Return Path, !- Name
Split TSE Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TSE Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TNE Return Path, !- Name
Split TNE Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TNE Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TN1 Return Path, !- Name
Split TN1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TN1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TN2 Return Path, !- Name
Split TN2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TN2 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TS1 Return Path, !- Name
Split TS1 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TS1 Zone Mixer; !- Component 1 Name
AirLoopHVAC:ReturnPath,
Split TS2 Return Path, !- Name
Split TS2 Return Air Outlet, !- Return Air Path Outlet Node Name
AirLoopHVAC:ZoneMixer, !- Component 1 Object Type
Split TS2 Zone Mixer; !- Component 1 Name
!- =========== ALL OBJECTS IN CLASS: ZONE SPLITTER ===========
AirLoopHVAC:ZoneSplitter,
Split GSW Zone Splitter, !- Name
Split GSW Supply Path Inlet, !- Inlet Node Name
G SW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GNW Zone Splitter, !- Name
Split GNW Supply Path Inlet, !- Inlet Node Name
G NW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split Office Zone Splitter, !- Name
Split Office Supply Path Inlet, !- Inlet Node Name
Office Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GNE Zone Splitter, !- Name
Split GNE Supply Path Inlet, !- Inlet Node Name
G NE Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GN1 Zone Splitter, !- Name
Split GN1 Supply Path Inlet, !- Inlet Node Name
G N1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GN2 Zone Splitter, !- Name
Split GN2 Supply Path Inlet, !- Inlet Node Name
G N2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GS1 Zone Splitter, !- Name
Split GS1 Supply Path Inlet, !- Inlet Node Name
G S1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split GS2 Zone Splitter, !- Name
Split GS2 Supply Path Inlet, !- Inlet Node Name
G S2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MSW Zone Splitter, !- Name
Split MSW Supply Path Inlet, !- Inlet Node Name
M SW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MNW Zone Splitter, !- Name
Split MNW Supply Path Inlet, !- Inlet Node Name
M NW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MSE Zone Splitter, !- Name
Split MSE Supply Path Inlet, !- Inlet Node Name
M SE Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MNE Zone Splitter, !- Name
Split MNE Supply Path Inlet, !- Inlet Node Name
M NE Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MN1 Zone Splitter, !- Name
Split MN1 Supply Path Inlet, !- Inlet Node Name
M N1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MN2 Zone Splitter, !- Name
Split MN2 Supply Path Inlet, !- Inlet Node Name
M N2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MS1 Zone Splitter, !- Name
Split MS1 Supply Path Inlet, !- Inlet Node Name
M S1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split MS2 Zone Splitter, !- Name
Split MS2 Supply Path Inlet, !- Inlet Node Name
M S2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TSW Zone Splitter, !- Name
Split TSW Supply Path Inlet, !- Inlet Node Name
T SW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TNW Zone Splitter, !- Name
Split TNW Supply Path Inlet, !- Inlet Node Name
T NW Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TSE Zone Splitter, !- Name
Split TSE Supply Path Inlet, !- Inlet Node Name
T SE Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TNE Zone Splitter, !- Name
Split TNE Supply Path Inlet, !- Inlet Node Name
T NE Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TN1 Zone Splitter, !- Name
Split TN1 Supply Path Inlet, !- Inlet Node Name
T N1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TN2 Zone Splitter, !- Name
Split TN2 Supply Path Inlet, !- Inlet Node Name
T N2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TS1 Zone Splitter, !- Name
Split TS1 Supply Path Inlet, !- Inlet Node Name
T S1 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
AirLoopHVAC:ZoneSplitter,
Split TS2 Zone Splitter, !- Name
Split TS2 Supply Path Inlet, !- Inlet Node Name
T S2 Apartment Zone Equip Inlet; !- Outlet 1 Node Name
!- =========== ALL OBJECTS IN CLASS: ZONE MIXER ===========
AirLoopHVAC:ZoneMixer,
Split GSW Zone Mixer, !- Name
Split GSW Return Air Outlet, !- Outlet Node Name
G SW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GNW Zone Mixer, !- Name
Split GNW Return Air Outlet, !- Outlet Node Name
G NW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split Office Zone Mixer, !- Name
Split Office Return Air Outlet, !- Outlet Node Name
Office Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GNE Zone Mixer, !- Name
Split GNE Return Air Outlet, !- Outlet Node Name
G NE Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GN1 Zone Mixer, !- Name
Split GN1 Return Air Outlet, !- Outlet Node Name
G N1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GN2 Zone Mixer, !- Name
Split GN2 Return Air Outlet, !- Outlet Node Name
G N2 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GS1 Zone Mixer, !- Name
Split GS1 Return Air Outlet, !- Outlet Node Name
G S1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split GS2 Zone Mixer, !- Name
Split GS2 Return Air Outlet, !- Outlet Node Name
G S2 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MSW Zone Mixer, !- Name
Split MSW Return Air Outlet, !- Outlet Node Name
M SW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MNW Zone Mixer, !- Name
Split MNW Return Air Outlet, !- Outlet Node Name
M NW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MSE Zone Mixer, !- Name
Split MSE Return Air Outlet, !- Outlet Node Name
M SE Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MNE Zone Mixer, !- Name
Split MNE Return Air Outlet, !- Outlet Node Name
M NE Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MN1 Zone Mixer, !- Name
Split MN1 Return Air Outlet, !- Outlet Node Name
M N1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MN2 Zone Mixer, !- Name
Split MN2 Return Air Outlet, !- Outlet Node Name
M N2 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MS1 Zone Mixer, !- Name
Split MS1 Return Air Outlet, !- Outlet Node Name
M S1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split MS2 Zone Mixer, !- Name
Split MS2 Return Air Outlet, !- Outlet Node Name
M S2 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TSW Zone Mixer, !- Name
Split TSW Return Air Outlet, !- Outlet Node Name
T SW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TNW Zone Mixer, !- Name
Split TNW Return Air Outlet, !- Outlet Node Name
T NW Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TSE Zone Mixer, !- Name
Split TSE Return Air Outlet, !- Outlet Node Name
T SE Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TNE Zone Mixer, !- Name
Split TNE Return Air Outlet, !- Outlet Node Name
T NE Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TN1 Zone Mixer, !- Name
Split TN1 Return Air Outlet, !- Outlet Node Name
T N1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TN2 Zone Mixer, !- Name
Split TN2 Return Air Outlet, !- Outlet Node Name
T N2 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TS1 Zone Mixer, !- Name
Split TS1 Return Air Outlet, !- Outlet Node Name
T S1 Apartment Return Outlet; !- Inlet 1 Node Name
AirLoopHVAC:ZoneMixer,
Split TS2 Zone Mixer, !- Name
Split TS2 Return Air Outlet, !- Outlet Node Name
T S2 Apartment Return Outlet; !- Inlet 1 Node Name
WaterHeater:Mixed,
G SW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G SW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G NW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G NW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G NE Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G NE Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G N1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G N1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G N2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G N2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G S1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G S1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
G S2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
G S2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M SW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M SW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M NW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M NW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M SE Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M SE Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M NE Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M NE Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M N1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M N1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M N2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M N2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M S1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M S1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
M S2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
M S2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
7.31768861973252E-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T SW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T SW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T NW Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T NW Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T SE Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T SE Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T NE Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T NE Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T N1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T N1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T N2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T N2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T S1 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T S1 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
WaterHeater:Mixed,
T S2 Apartment Water Heater, !- Name
0.1892706, !- Tank Volume {m3}
Hot Water Setpoint Temp Schedule, !- Setpoint Temperature Schedule Name
1.1111111405455, !- Deadband Temperature Difference {deltaC}
82.2222244003673, !- Maximum Temperature Limit {C}
Cycle, !- Heater Control Type
14653.55, !- Heater Maximum Capacity {W}
0, !- Heater Minimum Capacity {W}
, !- Heater Ignition Minimum Flow Rate {m3/s}
, !- Heater Ignition Delay {s}
Electricity, !- Heater Fuel Type
1, !- Heater Thermal Efficiency,
, !- Part Load Factor Curve Name
, !- Off Cycle Parasitic Fuel Consumption Rate {W}
Electricity, !- Off Cycle Parasitic Fuel Type
0, !- Off Cycle Parasitic Heat Fraction to Tank
, !- On Cycle Parasitic Fuel Consumption Rate {W}
, !- On Cycle Parasitic Fuel Type
0, !- On Cycle Parasitic Heat Fraction to Tank
Zone, !- Ambient Temperature Indicator
, !- Ambient Temperature Schedule Name
T S2 Apartment, !- Ambient Temperature Zone Name
, !- Ambient Temperature Outdoor Air Node Name
2.012559766, !- Off Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- Off Cycle Loss Fraction to Zone
2.012559766, !- On Cycle Loss Coefficient to Ambient Temperature {W/K}
, !- On Cycle Loss Fraction to Zone
3.66e-06, !- Peak Use Flow Rate {m3/s}
APT_DHW_SCH; !- Use Flow Rate Fraction Schedule Name
!- =========== ALL OBJECTS IN CLASS: COIL:GAS:HEATING ===========
Coil:Heating:Fuel,
Split GSW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GSW Supply Fan Outlet, !- Air Inlet Node Name
Split GSW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GNW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GNW Supply Fan Outlet, !- Air Inlet Node Name
Split GNW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split Office Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split Office Supply Fan Outlet, !- Air Inlet Node Name
Split Office Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GNE Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GNE Supply Fan Outlet, !- Air Inlet Node Name
Split GNE Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GN1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GN1 Supply Fan Outlet, !- Air Inlet Node Name
Split GN1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GN2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GN2 Supply Fan Outlet, !- Air Inlet Node Name
Split GN2 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GS1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GS1 Supply Fan Outlet, !- Air Inlet Node Name
Split GS1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split GS2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split GS2 Supply Fan Outlet, !- Air Inlet Node Name
Split GS2 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MSW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MSW Supply Fan Outlet, !- Air Inlet Node Name
Split MSW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MNW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MNW Supply Fan Outlet, !- Air Inlet Node Name
Split MNW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MSE Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MSE Supply Fan Outlet, !- Air Inlet Node Name
Split MSE Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MNE Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MNE Supply Fan Outlet, !- Air Inlet Node Name
Split MNE Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MN1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MN1 Supply Fan Outlet, !- Air Inlet Node Name
Split MN1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MN2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MN2 Supply Fan Outlet, !- Air Inlet Node Name
Split MN2 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MS1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MS1 Supply Fan Outlet, !- Air Inlet Node Name
Split MS1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split MS2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split MS2 Supply Fan Outlet, !- Air Inlet Node Name
Split MS2 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TSW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TSW Supply Fan Outlet, !- Air Inlet Node Name
Split TSW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TNW Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TNW Supply Fan Outlet, !- Air Inlet Node Name
Split TNW Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TSE Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TSE Supply Fan Outlet, !- Air Inlet Node Name
Split TSE Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TNE Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TNE Supply Fan Outlet, !- Air Inlet Node Name
Split TNE Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TN1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TN1 Supply Fan Outlet, !- Air Inlet Node Name
Split TN1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TN2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TN2 Supply Fan Outlet, !- Air Inlet Node Name
Split TN2 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TS1 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TS1 Supply Fan Outlet, !- Air Inlet Node Name
Split TS1 Heating Coil Outlet; !- Air Outlet Node Name
Coil:Heating:Fuel,
Split TS2 Heating Coil, !- Name
All On, !- Availability Schedule Name
NaturalGas, !- Fuel Type
0.81, !- Burner Efficiency
autosize, !- Nominal Capacity {W}
Split TS2 Supply Fan Outlet, !- Air Inlet Node Name
Split TS2 Heating Coil Outlet; !- Air Outlet Node Name
!- =========== ALL OBJECTS IN CLASS: COIL:DX:COOLINGBYPASSFACTOREMPIRICAL ===========
Coil:Cooling:DX:SingleSpeed,
Split GSW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GSW Heating Coil Outlet, !- Air Inlet Node Name
Split GSW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GSW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GNW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GNW Heating Coil Outlet, !- Air Inlet Node Name
Split GNW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GNW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split Office Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split Office Heating Coil Outlet, !- Air Inlet Node Name
Split Office Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split Office Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GNE Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GNE Heating Coil Outlet, !- Air Inlet Node Name
Split GNE Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GNE Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GN1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GN1 Heating Coil Outlet, !- Air Inlet Node Name
Split GN1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GN1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GN2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GN2 Heating Coil Outlet, !- Air Inlet Node Name
Split GN2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GN2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GS1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GS1 Heating Coil Outlet, !- Air Inlet Node Name
Split GS1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GS1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split GS2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split GS2 Heating Coil Outlet, !- Air Inlet Node Name
Split GS2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split GS2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MSW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MSW Heating Coil Outlet, !- Air Inlet Node Name
Split MSW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MSW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MNW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MNW Heating Coil Outlet, !- Air Inlet Node Name
Split MNW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MNW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MSE Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MSE Heating Coil Outlet, !- Air Inlet Node Name
Split MSE Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MSE Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MNE Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MNE Heating Coil Outlet, !- Air Inlet Node Name
Split MNE Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MNE Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MN1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MN1 Heating Coil Outlet, !- Air Inlet Node Name
Split MN1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MN1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MN2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MN2 Heating Coil Outlet, !- Air Inlet Node Name
Split MN2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MN2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MS1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MS1 Heating Coil Outlet, !- Air Inlet Node Name
Split MS1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MS1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split MS2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split MS2 Heating Coil Outlet, !- Air Inlet Node Name
Split MS2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split MS2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TSW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TSW Heating Coil Outlet, !- Air Inlet Node Name
Split TSW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TSW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TNW Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TNW Heating Coil Outlet, !- Air Inlet Node Name
Split TNW Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TNW Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TSE Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TSE Heating Coil Outlet, !- Air Inlet Node Name
Split TSE Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TSE Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TNE Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TNE Heating Coil Outlet, !- Air Inlet Node Name
Split TNE Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TNE Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TN1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TN1 Heating Coil Outlet, !- Air Inlet Node Name
Split TN1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TN1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TN2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TN2 Heating Coil Outlet, !- Air Inlet Node Name
Split TN2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TN2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TS1 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TS1 Heating Coil Outlet, !- Air Inlet Node Name
Split TS1 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TS1 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
Coil:Cooling:DX:SingleSpeed,
Split TS2 Cooling Coil, !- Name
All On, !- Availability Schedule Name
autosize, !- Gross Rated Total Cooling Capacity {W}
autosize, !- Gross Rated Sensible Heat Ratio
4.11713235489972, !- Gross Rated Cooling COP {W/W}
autosize, !- Rated Air Flow Rate {m3/s}
, !- Rated Evaporator Fan Power Per Volume Flow Rate {W/(m3/s)}
Split TS2 Heating Coil Outlet, !- Air Inlet Node Name
Split TS2 Air Loop Outlet, !- Air Outlet Node Name
Split DX Coil Cap-FT, !- Total Cooling Capacity Function of Temperature Curve Name
Split DX Coil Cap-FF, !- Total Cooling Capacity Function of Flow Fraction Curve Name
Split DX Coil EIR-FT, !- Energy Input Ratio Function of Temperature Curve Name
Split DX Coil EIR-FF, !- Energy Input Ratio Function of Flow Fraction Curve Name
Split DX Coil PLF, !- Part Load Fraction Correlation Curve Name
, !- Minimum Outdoor Dry-Bulb Temperature for Compressor Operation {C}
0, !- Nominal Time for Condensate Removal to Begin {s}
0, !- Ratio of Initial Moisture Evaporation Rate and Steady State Latent Capacity {dimensionless}
0, !- Maximum Cycling Rate {cycles/hr}
0, !- Latent Capacity Time Constant {s}
Split TS2 Cooling Coil Condenser Inlet, !- Condenser Air Inlet Node Name
AirCooled, !- Condenser Type
0, !- Evaporative Condenser Effectiveness {dimensionless}
, !- Evaporative Condenser Air Flow Rate {m3/s}
0, !- Evaporative Condenser Pump Rated Power Consumption {W}
0, !- Crankcase Heater Capacity {W}
10; !- Maximum Outdoor Dry-Bulb Temperature for Crankcase Heater Operation {C}
!- =========== ALL OBJECTS IN CLASS: FAN:SIMPLE:ONOFF ===========
Fan:OnOff,
Split GSW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GSW Mixed Air Outlet, !- Air Inlet Node Name
Split GSW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GNW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GNW Mixed Air Outlet, !- Air Inlet Node Name
Split GNW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split Office Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split Office Mixed Air Outlet, !- Air Inlet Node Name
Split Office Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GNE Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GNE Mixed Air Outlet, !- Air Inlet Node Name
Split GNE Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GN1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GN1 Mixed Air Outlet, !- Air Inlet Node Name
Split GN1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GN2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GN2 Mixed Air Outlet, !- Air Inlet Node Name
Split GN2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GS1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GS1 Mixed Air Outlet, !- Air Inlet Node Name
Split GS1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split GS2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split GS2 Mixed Air Outlet, !- Air Inlet Node Name
Split GS2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MSW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MSW Mixed Air Outlet, !- Air Inlet Node Name
Split MSW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MNW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MNW Mixed Air Outlet, !- Air Inlet Node Name
Split MNW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MSE Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MSE Mixed Air Outlet, !- Air Inlet Node Name
Split MSE Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MNE Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MNE Mixed Air Outlet, !- Air Inlet Node Name
Split MNE Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MN1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MN1 Mixed Air Outlet, !- Air Inlet Node Name
Split MN1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MN2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MN2 Mixed Air Outlet, !- Air Inlet Node Name
Split MN2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MS1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MS1 Mixed Air Outlet, !- Air Inlet Node Name
Split MS1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split MS2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split MS2 Mixed Air Outlet, !- Air Inlet Node Name
Split MS2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TSW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TSW Mixed Air Outlet, !- Air Inlet Node Name
Split TSW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TNW Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TNW Mixed Air Outlet, !- Air Inlet Node Name
Split TNW Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TSE Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TSE Mixed Air Outlet, !- Air Inlet Node Name
Split TSE Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TNE Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TNE Mixed Air Outlet, !- Air Inlet Node Name
Split TNE Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TN1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TN1 Mixed Air Outlet, !- Air Inlet Node Name
Split TN1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TN2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TN2 Mixed Air Outlet, !- Air Inlet Node Name
Split TN2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TS1 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TS1 Mixed Air Outlet, !- Air Inlet Node Name
Split TS1 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
Fan:OnOff,
Split TS2 Supply Fan, !- Name
All On, !- Availability Schedule Name
0.55575, !- Fan Total Efficiency
622.5, !- Pressure Rise {Pa}
autosize, !- Maximum Flow Rate {m3/s}
0.855, !- Motor Efficiency
1, !- Motor In Airstream Fraction
Split TS2 Mixed Air Outlet, !- Air Inlet Node Name
Split TS2 Supply Fan Outlet, !- Air Outlet Node Name
, !- Fan Power Ratio Function of Speed Ratio Curve Name
, !- Fan Efficiency Ratio Function of Speed Ratio Curve Name
General; !- End-Use Subcategory
!No PV for this case
!- =========== ALL OBJECTS IN CLASS: REPORT METERFILEONLY ===========
Output:Meter:MeterFileOnly,Electricity:Facility,Hourly;
Output:Meter:MeterFileOnly,ElectricityNet:Facility,Hourly;
Output:Meter:MeterFileOnly,Gas:Facility,Hourly;
!- =========== ALL OBJECTS IN CLASS: REPORT ===========
Output:Surfaces:Drawing,DXF,RegularPolyline;
Output:Surfaces:List,Details;
!- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:STYLE ===========
OutputControl:Table:Style,
CommaAndHTML; !- Column Separator
!- =========== ALL OBJECTS IN CLASS: OUTPUTCONTROL:REPORTINGTOLERANCES ===========
OutputControl:ReportingTolerances,
0.556, !- Tolerance for Time Heating Setpoint Not Met {deltaC}
0.556; !- Tolerance for Time Cooling Setpoint Not Met {deltaC}
!- =========== ALL OBJECTS IN CLASS: REPORT:TABLE:PREDEFINED ===========
Output:Table:SummaryReports,
AllSummaryAndMonthly; !- Report 1 Name
Output:Table:Monthly,
NameHolderMonthlySummary TaskPurpose ProgressIndicator, !- Name ProgressIndicator,ForDetermination2019, ...
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeName ASHRAE901, !- Name ASHRAE901, ASHRAE1891, IECC, Title24, ORSC, IGCC, ...
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeYear 2019, !- Name all years for ASHRAE90.1, IECC, ASHRAE189.1
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary CodeAmendment NoneAmend, !- Name StateAmend,EEM, NoneAmend for national or state without amendment
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary PrototypeName ApartmentMidRise, !- Name 16 Prototypes
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary TaskScope National, !- Name National, State, City
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary State National, !- Name National for national analysis, NewYork, Utah,... for state analysis, or city name for city analysis. Spell out the name of the state without space between words
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary ClimateZone 6A, !- Name 0-8
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
Output:Table:Monthly,
NameHolderMonthlySummary RepresentCity USA_MN_Rochester, !- Name representative city like Honolulu for national, for each state, for city analysis. this is not the city of the weather file. The weather city will be extracted from epw file
3, !- Digits After Decimal
Site Outdoor Air Drybulb, !- Variable or Meter 1 Name
SumOrAverage, !- Aggregation Type for Variable or Meter 1
Heating:Gas, !- Variable or Meter 2 Name
SumOrAverage; !- Aggregation Type for Variable or Meter 2
!- =========== ALL OBJECTS IN CLASS: OUTPUT:VARIABLE ===========
! Output:Variable,*,Site Outdoor Air Drybulb Temperature,Hourly;
! Output:Variable,*,Site Outdoor Air Wetbulb Temperature,Hourly;
! Output:Variable,OCC_APT_SCH,Schedule Value,Hourly;
! Output:Variable,OCC_OFF_SCH,Schedule Value,Hourly;
!
!! outdoor air flow rate
!
! Output:Variable,Split Office Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GSW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNE Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSE Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNE Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNW Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSE Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNE Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS1 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS2 Outside Air Inlet, System Node Standard Density Volume Flow Rate,Hourly;
!
!! return Air T
!
! Output:Variable,Split Office Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GSW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GNW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GNE Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GN1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GN2 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GS1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split GS2 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MSW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MNW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MSE Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MNE Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MN1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MN2 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MS1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split MS2 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TSW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TNW Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TSE Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TNE Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TN1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TN2 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TS1 Air Loop Inlet, System Node Temperature,Hourly;
! Output:Variable,Split TS2 Air Loop Inlet, System Node Temperature,Hourly;
!
!! return Air T Wetbulb
!
! Output:Variable,Split Office Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GSW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GNW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GNE Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GN1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GN2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GS1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GS2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MSW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MNW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MSE Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MNE Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MN1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MN2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MS1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MS2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TSW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TNW Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TSE Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TNE Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TN1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TN2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TS1 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TS2 Air Loop Inlet, System Node Wetbulb Temperature,Hourly;
!
!! return Air T flow rate
!
! Output:Variable,Split Office Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GSW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNE Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSE Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNE Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNW Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSE Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNE Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS1 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS2 Air Loop Inlet, System Node Standard Density Volume Flow Rate,Hourly;
!
!! supply Air T
!
! Output:Variable,Split Office Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GSW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GNW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GNE Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GN1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GN2 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GS1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split GS2 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MSW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MNW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MSE Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MNE Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MN1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MN2 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MS1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split MS2 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TSW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TNW Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TSE Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TNE Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TN1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TN2 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TS1 Air Loop Outlet, System Node Temperature,Hourly;
! Output:Variable,Split TS2 Air Loop Outlet, System Node Temperature,Hourly;
!
!! supply Air T Wetbulb
!
! Output:Variable,Split Office Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GSW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GNW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GNE Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GN1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GN2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GS1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split GS2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MSW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MNW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MSE Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MNE Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MN1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MN2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MS1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split MS2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TSW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TNW Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TSE Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TNE Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TN1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TN2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TS1 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
! Output:Variable,Split TS2 Air Loop Outlet, System Node Wetbulb Temperature,Hourly;
!
!! supply Air T flow rate
!
! Output:Variable,Split Office Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GSW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GNE Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GN2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split GS2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MSE Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MNE Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MN2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split MS2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNW Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TSE Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TNE Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TN2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS1 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
! Output:Variable,Split TS2 Air Loop Outlet, System Node Standard Density Volume Flow Rate,Hourly;
!
! ! coil load
!
! Output:Variable,*,Air System Cooling Coil Total Cooling Energy,hourly; !- HVAC Sum J
! Output:Variable,*,Air System Heating Coil Total Heating Energy,hourly; !- HVAC Sum J
!
! ! fan (52) and pump (2)
!
! Output:Variable,*,Fan Electric Power,hourly; !- HVAC Average W
! Output:Variable,*,Pump Electric Power,hourly; !- HVAC Average W
! Output:Variable,*,Humidifier Electric Power,hourly; !- HVAC Average W
!
! ! SHW
!
! Output:Variable,*,Water Heater Heating Rate,Hourly; ! The average heating rate supplied by the heater element or burner.
!
!
! ! Utility and Submeter
!
! Output:Meter,Electricity:Facility,Hourly;
! Output:Meter,Gas:Facility,Hourly;
! Output:Meter,InteriorLights:Electricity,Hourly;
! Output:Meter,ExteriorLights:Electricity,Hourly;
! Output:Meter,InteriorEquipment:Electricity,Hourly;
! Output:Meter,ExteriorEquipment:Electricity,Hourly;
! Output:Meter,Fans:Electricity,Hourly;
! Output:Meter,Pumps:Electricity,Hourly;
! Output:Meter,Heating:Electricity,Hourly;
! Output:Meter,Cooling:Electricity,Hourly;
! Output:Meter,HeatRejection:Electricity,Hourly;
! Output:Meter,Humidifier:Electricity,Hourly;
! Output:Meter,HeatRecovery:Electricity,Hourly;
! Output:Meter,DHW:Electricity,Hourly;
! Output:Meter,Cogeneration:Electricity,Hourly;
! Output:Meter,Refrigeration:Electricity,Hourly;
! Output:Meter,WaterSystems:Electricity,Hourly;
!
! Output:Meter,InteriorLights:Gas,Hourly;
! Output:Meter,ExteriorLights:Gas,Hourly;
! Output:Meter,InteriorEquipment:Gas,Hourly;
! Output:Meter,ExteriorEquipment:Gas,Hourly;
! Output:Meter,Fans:Gas,Hourly;
! Output:Meter,Pumps:Gas,Hourly;
! Output:Meter,Heating:Gas,Hourly;
! Output:Meter,Cooling:Gas,Hourly;
! Output:Meter,HeatRejection:Gas,Hourly;
! Output:Meter,Humidifier:Gas,Hourly;
! Output:Meter,HeatRecovery:Gas,Hourly;
! Output:Meter,DHW:Gas,Hourly;
! Output:Meter,Cogeneration:Gas,Hourly;
! Output:Meter,Refrigeration:Gas,Hourly;
! Output:Meter,WaterSystems:Gas,Hourly;
!
! ! coil load
!
! ! Output:Variable,*,Cooling Coil Electric Energy,hourly; !- HVAC Sum J ! 24 outputs
! ! Output:Variable,*,Cooling Coil Total Cooling Energy,hourly; !- HVAC Sum J ! 24 outputs J is 3600 time of W
! ! Output:Variable,*,Cooling Coil Total Cooling Rate,hourly; !- HVAC Average W ! 24 outputs W is 1/3600 of J
! ! Output:Variable,*,Air System Cooling Coil Total Cooling Energy,hourly; !- HVAC Sum J ! 24 outputs {Air System Cooling Coil Total Cooling Energy} which is the same as {Cooling Coil Total Cooling Energy}
! ! Output:Variable,*,Air System DX Cooling Coil Electric Energy,hourly; !- HVAC Sum J ! 24 outputs {Air System DX Cooling Coil Electric Energy} the same as {Cooling Coil Electric Energy}
!
! ! Output:Variable,*,Heating Coil Electric Energy,hourly; !- HVAC Sum J ! 24 outputs all are 0s
! ! Output:Variable,*,Heating Coil Heating Energy,hourly; !- HVAC Sum J ! no outputs
! ! Output:Variable,*,Heating Coil Heating Rate,hourly; !- HVAC Average W ! no outputs
! ! Output:Variable,*,Air System Heating Coil Total Heating Energy,hourly; !- HVAC Sum J ! 24 outputs
! ! Output:Variable,*,Air System DX Heating Coil Electric Energy,hourly; !- HVAC Sum J ! 24 outputs but all are 0s
!- =========== ALL OBJECTS IN CLASS: ZONEVENTILATION:WINDANDSTACKOPENAREA ===========
ZoneVentilation:WindandStackOpenArea,
G SW Apartment Sliding Door Ventilation, !- Name
G SW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G NW Apartment Sliding Door Ventilation, !- Name
G NW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G NE Apartment Sliding Door Ventilation, !- Name
G NE Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G N1 Apartment Sliding Door Ventilation, !- Name
G N1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G N2 Apartment Sliding Door Ventilation, !- Name
G N2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G S1 Apartment Sliding Door Ventilation, !- Name
G S1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
G S2 Apartment Sliding Door Ventilation, !- Name
G S2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M SW Apartment Sliding Door Ventilation, !- Name
M SW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M NW Apartment Sliding Door Ventilation, !- Name
M NW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M SE Apartment Sliding Door Ventilation, !- Name
M SE Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M NE Apartment Sliding Door Ventilation, !- Name
M NE Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M N1 Apartment Sliding Door Ventilation, !- Name
M N1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M N2 Apartment Sliding Door Ventilation, !- Name
M N2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M S1 Apartment Sliding Door Ventilation, !- Name
M S1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
M S2 Apartment Sliding Door Ventilation, !- Name
M S2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T SW Apartment Sliding Door Ventilation, !- Name
T SW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T NW Apartment Sliding Door Ventilation, !- Name
T NW Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T SE Apartment Sliding Door Ventilation, !- Name
T SE Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T NE Apartment Sliding Door Ventilation, !- Name
T NE Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T N1 Apartment Sliding Door Ventilation, !- Name
T N1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T N2 Apartment Sliding Door Ventilation, !- Name
T N2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
0, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T S1 Apartment Sliding Door Ventilation, !- Name
T S1 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
ZoneVentilation:WindandStackOpenArea,
T S2 Apartment Sliding Door Ventilation, !- Name
T S2 Apartment, !- Zone Name
0.0374, !- Opening Area {m2}
Sliding_Doors_Ventilation_Availability_SCH, !- Opening Area Fraction Schedule Name
autocalculate, !- Opening Effectiveness {dimensionless}
180, !- Effective Angle {deg}
6.0957, !- Height Difference {m}
autocalculate, !- Discharge Coefficient for Opening
18.89, !- Minimum Indoor Temperature {C}
, !- Minimum Indoor Temperature Schedule Name
25.56, !- Maximum Indoor Temperature {C}
, !- Maximum Indoor Temperature Schedule Name
-100, !- Delta Temperature {deltaC}
, !- Delta Temperature Schedule Name
15.56, !- Minimum Outdoor Temperature {C}
, !- Minimum Outdoor Temperature Schedule Name
26.67, !- Maximum Outdoor Temperature {C}
, !- Maximum Outdoor Temperature Schedule Name
40; !- Maximum Wind Speed {m/s}
Schedule:Compact,
Sliding_Doors_Ventilation_Availability_SCH, !- Name
Fraction, !- Schedule Type Limits Name
Through: 12/31, !- Field 1
For: WinterDesignDay SummerDesignDay, !- Field 2
Until: 24:00,0, !- Field 3
For: Allotherdays, !- Field 5
Until: 6:00,0, !- Field 6
Until: 22:00,1, !- Field 8
Until: 24:00,0; !- Field 10
EnergyManagementSystem:Sensor,
M_S1_Apartment_Sliding_Door_Ventilation_Sensor, !- Name
M S1 APARTMENT, !- Output:Variable or Output:Meter Index Key Name
Zone Ventilation Standard Density Volume Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Sensor,
M_N1_Apartment_Sliding_Door_Ventilation_Sensor, !- Name
M N1 APARTMENT, !- Output:Variable or Output:Meter Index Key Name
Zone Ventilation Standard Density Volume Flow Rate; !- Output:Variable or Output:Meter Name
EnergyManagementSystem:Actuator,
S_Apartment_CLGSETP_Actuator, ! Name
S CLGSETP_APT_SCH, !- Actuated Component Unique Name
Schedule:Compact, ! Actuated Component Type
Schedule Value; ! Actuated Component Control Type
EnergyManagementSystem:Actuator,
S_Apartment_HTGSETP_Actuator, ! Name
S HTGSETP_APT_SCH, !- Actuated Component Unique Name
Schedule:Compact, ! Actuated Component Type
Schedule Value; ! Actuated Component Control Type
EnergyManagementSystem:Actuator,
N_Apartment_CLGSETP_Actuator, ! Name
N CLGSETP_APT_SCH, !- Actuated Component Unique Name
Schedule:Compact, ! Actuated Component Type
Schedule Value; ! Actuated Component Control Type
EnergyManagementSystem:Actuator,
N_Apartment_HTGSETP_Actuator, ! Name
N HTGSETP_APT_SCH, !- Actuated Component Unique Name
Schedule:Compact, ! Actuated Component Type
Schedule Value; ! Actuated Component Control Type
EnergyManagementSystem:ProgramCallingManager,
Door_Switch_Enabled_Thermostat_Reset, ! Name
BeginTimestepBeforePredictor, ! EnergyPlus Model Calling Point
Door_Switch_Enabled_Thermostat_Reset_Program_N_Apartments,
Door_Switch_Enabled_Thermostat_Reset_Program_S_Apartments;
EnergyManagementSystem:Program,
Door_Switch_Enabled_Thermostat_Reset_Program_S_Apartments, ! Name
IF (M_S1_Apartment_Sliding_Door_Ventilation_Sensor > 0),
SET S_Apartment_CLGSETP_Actuator = 32.22,
SET S_Apartment_HTGSETP_Actuator = 12.78,
ELSE,
SET S_Apartment_CLGSETP_Actuator = null,
SET S_Apartment_HTGSETP_Actuator = null,
ENDIF;
EnergyManagementSystem:Program,
Door_Switch_Enabled_Thermostat_Reset_Program_N_Apartments, ! Name
IF (M_N1_Apartment_Sliding_Door_Ventilation_Sensor > 0),
SET N_Apartment_CLGSETP_Actuator = 32.22,
SET N_Apartment_HTGSETP_Actuator = 12.78,
ELSE,
SET N_Apartment_CLGSETP_Actuator = null,
SET N_Apartment_HTGSETP_Actuator = null,
ENDIF;