""" Calculation of loads for peak heating and cooling SPDX - License - Identifier: LGPL - 3.0 - or -later Copyright © 2022 Concordia CERC group Project Coder Pilar Monsalvete Alvarez de Uribarri pilar.monsalvete@concordia.ca """ import hub.helpers.constants as cte class LoadsCalculation: """ LoadsCalculation class """ def __init__(self, building): self._building = building @staticmethod def _get_load_transmitted(thermal_zone, internal_temperature, ambient_temperature, ground_temperature): load_transmitted_opaque = 0 load_transmitted_transparent = 0 for thermal_boundary in thermal_zone.thermal_boundaries: if thermal_boundary.type == cte.GROUND: external_temperature = ground_temperature elif thermal_boundary.type == cte.INTERIOR_WALL: external_temperature = internal_temperature else: external_temperature = ambient_temperature load_transmitted_opaque += thermal_boundary.u_value * thermal_boundary.opaque_area \ * (internal_temperature - external_temperature) for thermal_opening in thermal_boundary.thermal_openings: load_transmitted_transparent += thermal_opening.overall_u_value \ * (internal_temperature - external_temperature) load_transmitted_opaque += thermal_zone.additional_thermal_bridge_u_value * thermal_zone.footprint_area \ * (internal_temperature - ambient_temperature) load_transmitted = load_transmitted_opaque + load_transmitted_transparent return load_transmitted @staticmethod def _get_load_ventilation(thermal_zone, internal_temperature, ambient_temperature): load_renovation_sensible = 0 for usage in thermal_zone.usages: load_renovation_sensible += cte.AIR_DENSITY * cte.AIR_HEAT_CAPACITY * usage.mechanical_air_change \ * thermal_zone.volume / cte.HOUR_TO_MINUTES / cte.MINUTES_TO_SECONDS \ * (internal_temperature - ambient_temperature) load_infiltration_sensible = cte.AIR_DENSITY * cte.AIR_HEAT_CAPACITY * thermal_zone.infiltration_rate_system_off \ * thermal_zone.volume / cte.HOUR_TO_MINUTES / cte.MINUTES_TO_SECONDS \ * (internal_temperature - ambient_temperature) load_ventilation = load_renovation_sensible + load_infiltration_sensible return load_ventilation def get_heating_transmitted_load(self, ambient_temperature, ground_temperature): heating_load_transmitted = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: internal_temperature = thermal_zone.thermal_control.mean_heating_set_point heating_load_transmitted += self._get_load_transmitted(thermal_zone, internal_temperature, ambient_temperature, ground_temperature) return heating_load_transmitted def get_cooling_transmitted_load(self, ambient_temperature, ground_temperature): cooling_load_transmitted = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: internal_temperature = thermal_zone.thermal_control.mean_cooling_set_point cooling_load_transmitted += self._get_load_transmitted(thermal_zone, internal_temperature, ambient_temperature, ground_temperature) return cooling_load_transmitted def get_heating_ventilation_load_sensible(self, ambient_temperature): heating_ventilation_load = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: internal_temperature = thermal_zone.thermal_control.mean_heating_set_point heating_ventilation_load += self._get_load_ventilation(thermal_zone, internal_temperature, ambient_temperature) return heating_ventilation_load def get_cooling_ventilation_load_sensible(self, ambient_temperature): cooling_ventilation_load = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: internal_temperature = thermal_zone.thermal_control.mean_cooling_set_point cooling_ventilation_load += self._get_load_ventilation(thermal_zone, internal_temperature, ambient_temperature) return cooling_ventilation_load def get_internal_load_sensible(self): cooling_load_occupancy_sensible = 0 cooling_load_lighting = 0 cooling_load_equipment_sensible = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: cooling_load_occupancy_sensible += (thermal_zone.occupancy.sensible_convective_internal_gain + thermal_zone.occupancy.sensible_radiative_internal_gain) \ * thermal_zone.footprint_area cooling_load_lighting += (thermal_zone.lighting.density * thermal_zone.lighting.convective_fraction + thermal_zone.lighting.density * thermal_zone.lighting.radiative_fraction) \ * thermal_zone.footprint_area cooling_load_equipment_sensible += (thermal_zone.appliances.density * thermal_zone.appliances.convective_fraction + thermal_zone.appliances.density * thermal_zone.appliances.radiative_fraction) \ * thermal_zone.footprint_area internal_load = cooling_load_occupancy_sensible + cooling_load_lighting + cooling_load_equipment_sensible return internal_load def get_radiation_load(self, irradiance_format, hour): cooling_load_radiation = 0 for internal_zone in self._building.internal_zones: for thermal_zone in internal_zone.thermal_zones: for thermal_boundary in thermal_zone.thermal_boundaries: for thermal_opening in thermal_boundary.thermal_openings: radiation = thermal_boundary.parent_surface.global_irradiance[cte.HOUR][irradiance_format][hour] cooling_load_radiation += thermal_opening.area * (1 - thermal_opening.frame_ratio) * thermal_opening.g_value \ * radiation return cooling_load_radiation