forked from s_ranjbar/city_retrofit
130 lines
4.9 KiB
Python
130 lines
4.9 KiB
Python
"""
|
|
Cooling and Heating peak loads module
|
|
SPDX - License - Identifier: LGPL - 3.0 - or -later
|
|
Copyright © 2023 Concordia CERC group
|
|
Project Coder Pilar Monsalvete Alvarez de Uribarri pilar.monsalvete@concordia.ca
|
|
Code contributors: Guille Gutierrez guillermo.gutierrezmorote@concordia.ca
|
|
"""
|
|
|
|
import math
|
|
|
|
import hub.helpers.constants as cte
|
|
from hub.helpers.peak_calculation.loads_calculation import LoadsCalculation
|
|
|
|
_MONTH_STARTING_HOUR = [0, 744, 1416, 2160, 2880, 3624, 4344, 5088, 5832, 6552, 7296, 8016, math.inf]
|
|
|
|
|
|
class PeakLoads:
|
|
"""
|
|
PeakLoads class
|
|
"""
|
|
def __init__(self, building=None):
|
|
self._building = building
|
|
|
|
def _can_be_calculated(self):
|
|
levels_of_detail = self._building.level_of_detail
|
|
can_be_calculated = True
|
|
if levels_of_detail.geometry is None:
|
|
can_be_calculated = False
|
|
if levels_of_detail.geometry < 1:
|
|
can_be_calculated = False
|
|
if levels_of_detail.construction is None:
|
|
can_be_calculated = False
|
|
if levels_of_detail.construction < 1:
|
|
can_be_calculated = False
|
|
if levels_of_detail.usage is None:
|
|
can_be_calculated = False
|
|
if levels_of_detail.usage < 1:
|
|
can_be_calculated = False
|
|
if levels_of_detail.weather is None:
|
|
can_be_calculated = False
|
|
if levels_of_detail.weather < 2:
|
|
can_be_calculated = False
|
|
if levels_of_detail.surface_radiation is None:
|
|
can_be_calculated = False
|
|
if levels_of_detail.surface_radiation < 2:
|
|
can_be_calculated = False
|
|
return can_be_calculated
|
|
|
|
@staticmethod
|
|
def peak_loads_from_hourly(hourly_values):
|
|
"""
|
|
Get peak loads from hourly
|
|
:return: [int]
|
|
"""
|
|
month = 1
|
|
peaks = [0 for _ in range(12)]
|
|
for i, value in enumerate(hourly_values):
|
|
if _MONTH_STARTING_HOUR[month] <= i:
|
|
month += 1
|
|
if value > peaks[month-1]:
|
|
peaks[month-1] = value
|
|
return peaks
|
|
|
|
@property
|
|
def heating_peak_loads_from_methodology(self):
|
|
"""
|
|
Get heating peak loads by calculate
|
|
:return: [int]
|
|
"""
|
|
if not self._can_be_calculated():
|
|
return None
|
|
monthly_heating_loads = []
|
|
ambient_temperature = self._building.external_temperature[cte.HOUR]['epw']
|
|
for month in range(0, 12):
|
|
ground_temperature = self._building.ground_temperature[cte.MONTH]['2'][month]
|
|
heating_ambient_temperature = 100
|
|
start_hour = _MONTH_STARTING_HOUR[month]
|
|
end_hour = 8760
|
|
if month < 11:
|
|
end_hour = _MONTH_STARTING_HOUR[month + 1]
|
|
for hour in range(start_hour, end_hour):
|
|
temperature = ambient_temperature[hour]
|
|
if temperature < heating_ambient_temperature:
|
|
heating_ambient_temperature = temperature
|
|
loads = LoadsCalculation(self._building)
|
|
heating_load_transmitted = loads.get_heating_transmitted_load(heating_ambient_temperature, ground_temperature)
|
|
heating_load_ventilation_sensible = loads.get_heating_ventilation_load_sensible(heating_ambient_temperature)
|
|
heating_load_ventilation_latent = 0
|
|
heating_load = heating_load_transmitted + heating_load_ventilation_sensible + heating_load_ventilation_latent
|
|
heating_load = max(heating_load, 0)
|
|
monthly_heating_loads.append(heating_load)
|
|
return monthly_heating_loads
|
|
|
|
@property
|
|
def cooling_peak_loads_from_methodology(self):
|
|
"""
|
|
Get cooling peak loads by calculate
|
|
:return: [int]
|
|
"""
|
|
if not self._can_be_calculated():
|
|
return None
|
|
monthly_cooling_loads = []
|
|
ambient_temperature = self._building.external_temperature[cte.HOUR]['epw']
|
|
for month in range(0, 12):
|
|
ground_temperature = self._building.ground_temperature[cte.MONTH]['2'][month]
|
|
cooling_ambient_temperature = -100
|
|
cooling_calculation_hour = -1
|
|
start_hour = _MONTH_STARTING_HOUR[month]
|
|
end_hour = 8760
|
|
if month < 11:
|
|
end_hour = _MONTH_STARTING_HOUR[month + 1]
|
|
for hour in range(start_hour, end_hour):
|
|
temperature = ambient_temperature[hour]
|
|
if temperature > cooling_ambient_temperature:
|
|
cooling_ambient_temperature = temperature
|
|
cooling_calculation_hour = hour
|
|
loads = LoadsCalculation(self._building)
|
|
cooling_load_transmitted = loads.get_cooling_transmitted_load(cooling_ambient_temperature, ground_temperature)
|
|
cooling_load_renovation_sensible = loads.get_cooling_ventilation_load_sensible(cooling_ambient_temperature)
|
|
cooling_load_internal_gains_sensible = loads.get_internal_load_sensible()
|
|
cooling_load_radiation = loads.get_radiation_load('sra', cooling_calculation_hour)
|
|
cooling_load_sensible = cooling_load_transmitted + cooling_load_renovation_sensible - cooling_load_radiation \
|
|
- cooling_load_internal_gains_sensible
|
|
|
|
cooling_load_latent = 0
|
|
cooling_load = cooling_load_sensible + cooling_load_latent
|
|
cooling_load = min(cooling_load, 0)
|
|
monthly_cooling_loads.append(abs(cooling_load))
|
|
return monthly_cooling_loads
|