import math import hub.helpers.constants as cte from hub.helpers.peak_calculation.loads_calculation import LoadsCalculation _MONTH_STARTING_HOUR = [0, 744, 1416, 2160, 2880, 3624, 4344, 5088, 5832, 6552, 7296, 8016, math.inf] def peak_loads_from_hourly(hourly_values): month = 1 peaks = [0 for _ in range(12)] for i, value in enumerate(hourly_values): if _MONTH_STARTING_HOUR[month] <= i: month += 1 if value > peaks[month-1]: peaks[month-1] = value return peaks def heating_peak_loads_from_methodology(building): monthly_heating_loads = [] ambient_temperature = building.external_temperature[cte.HOUR]['epw'] for month in range(0, 12): ground_temperature = building.ground_temperature[cte.MONTH]['2'][month] heating_ambient_temperature = 100 start_hour = _MONTH_STARTING_HOUR[month] end_hour = 8760 if month < 11: end_hour = _MONTH_STARTING_HOUR[month + 1] for hour in range(start_hour, end_hour): temperature = ambient_temperature[hour] if temperature < heating_ambient_temperature: heating_ambient_temperature = temperature loads = LoadsCalculation(building) heating_load_transmitted = loads.get_heating_transmitted_load(heating_ambient_temperature, ground_temperature) heating_load_ventilation_sensible = loads.get_heating_ventilation_load_sensible(heating_ambient_temperature) heating_load_ventilation_latent = 0 heating_load = heating_load_transmitted + heating_load_ventilation_sensible + heating_load_ventilation_latent if heating_load < 0: heating_load = 0 monthly_heating_loads.append(heating_load) return monthly_heating_loads def cooling_peak_loads_from_methodology(building): monthly_cooling_loads = [] ambient_temperature = building.external_temperature[cte.HOUR]['epw'] for month in range(0, 12): ground_temperature = building.ground_temperature[cte.MONTH]['2'][month] cooling_ambient_temperature = -100 cooling_calculation_hour = -1 start_hour = _MONTH_STARTING_HOUR[month] end_hour = 8760 if month < 11: end_hour = _MONTH_STARTING_HOUR[month + 1] for hour in range(start_hour, end_hour): temperature = ambient_temperature[hour] if temperature > cooling_ambient_temperature: cooling_ambient_temperature = temperature cooling_calculation_hour = hour loads = LoadsCalculation(building) cooling_load_transmitted = loads.get_cooling_transmitted_load(cooling_ambient_temperature, ground_temperature) cooling_load_renovation_sensible = loads.get_cooling_ventilation_load_sensible(cooling_ambient_temperature) cooling_load_internal_gains_sensible = loads.get_internal_load_sensible() cooling_load_radiation = loads.get_radiation_load('sra', cooling_calculation_hour) cooling_load_sensible = cooling_load_transmitted + cooling_load_renovation_sensible - cooling_load_radiation \ - cooling_load_internal_gains_sensible cooling_load_latent = 0 cooling_load = cooling_load_sensible + cooling_load_latent if cooling_load > 0: cooling_load = 0 monthly_cooling_loads.append(abs(cooling_load)) return monthly_cooling_loads