system_assignation/hub/imports/results/peak_load.py

62 lines
2.8 KiB
Python

import hub.helpers.constants as cte
from hub.imports.results.peak_calculation.loads_calculation import LoadsCalculation
class PeakLoad:
_MONTH_STARTING_HOUR = [0, 744, 1416, 2160, 2880, 3624, 4344, 5088, 5832, 6552, 7296, 8016]
def __init__(self, city):
self._city = city
self._weather_format = 'epw'
self._irradiance_format = 'sra'
def enrich(self):
for building in self._city.buildings:
if building.heating
monthly_heating_loads = []
monthly_cooling_loads = []
ambient_temperature = building.external_temperature[cte.HOUR][self._weather_format]
for month in range(0, 12):
ground_temperature = building.ground_temperature[cte.MONTH]['2'][month]
heating_ambient_temperature = 100
cooling_ambient_temperature = -100
cooling_calculation_hour = -1
start_hour = self._MONTH_STARTING_HOUR[month]
end_hour = 8760
if month < 11:
end_hour = self._MONTH_STARTING_HOUR[month + 1]
for hour in range(start_hour, end_hour):
temperature = ambient_temperature[hour]
if temperature < heating_ambient_temperature:
heating_ambient_temperature = temperature
if temperature > cooling_ambient_temperature:
cooling_ambient_temperature = temperature
cooling_calculation_hour = hour
loads = LoadsCalculation(building)
heating_load_transmitted = loads.get_heating_transmitted_load(heating_ambient_temperature, ground_temperature)
heating_load_ventilation_sensible = loads.get_heating_ventilation_load_sensible(heating_ambient_temperature)
heating_load_ventilation_latent = 0
heating_load = heating_load_transmitted + heating_load_ventilation_sensible + heating_load_ventilation_latent
cooling_load_transmitted = loads.get_cooling_transmitted_load(cooling_ambient_temperature, ground_temperature)
cooling_load_renovation_sensible = loads.get_cooling_ventilation_load_sensible(cooling_ambient_temperature)
cooling_load_internal_gains_sensible = loads.get_internal_load_sensible()
cooling_load_radiation = loads.get_radiation_load(self._irradiance_format, cooling_calculation_hour)
cooling_load_sensible = cooling_load_transmitted + cooling_load_renovation_sensible - cooling_load_radiation \
- cooling_load_internal_gains_sensible
cooling_load_latent = 0
cooling_load = cooling_load_sensible + cooling_load_latent
if heating_load < 0:
heating_load = 0
if cooling_load > 0:
cooling_load = 0
monthly_heating_loads.append(heating_load)
monthly_cooling_loads.append(cooling_load)
building. {'monthly heating peak load': monthly_heating_loads,
'monthly cooling peak load': monthly_cooling_loads}