62 lines
2.8 KiB
Python
62 lines
2.8 KiB
Python
import hub.helpers.constants as cte
|
|
from hub.imports.results.peak_calculation.loads_calculation import LoadsCalculation
|
|
|
|
|
|
class PeakLoad:
|
|
_MONTH_STARTING_HOUR = [0, 744, 1416, 2160, 2880, 3624, 4344, 5088, 5832, 6552, 7296, 8016]
|
|
|
|
def __init__(self, city):
|
|
self._city = city
|
|
self._weather_format = 'epw'
|
|
self._irradiance_format = 'sra'
|
|
|
|
def enrich(self):
|
|
for building in self._city.buildings:
|
|
if building.heating
|
|
|
|
|
|
monthly_heating_loads = []
|
|
monthly_cooling_loads = []
|
|
ambient_temperature = building.external_temperature[cte.HOUR][self._weather_format]
|
|
for month in range(0, 12):
|
|
ground_temperature = building.ground_temperature[cte.MONTH]['2'][month]
|
|
heating_ambient_temperature = 100
|
|
cooling_ambient_temperature = -100
|
|
cooling_calculation_hour = -1
|
|
start_hour = self._MONTH_STARTING_HOUR[month]
|
|
end_hour = 8760
|
|
if month < 11:
|
|
end_hour = self._MONTH_STARTING_HOUR[month + 1]
|
|
for hour in range(start_hour, end_hour):
|
|
temperature = ambient_temperature[hour]
|
|
if temperature < heating_ambient_temperature:
|
|
heating_ambient_temperature = temperature
|
|
if temperature > cooling_ambient_temperature:
|
|
cooling_ambient_temperature = temperature
|
|
cooling_calculation_hour = hour
|
|
|
|
loads = LoadsCalculation(building)
|
|
heating_load_transmitted = loads.get_heating_transmitted_load(heating_ambient_temperature, ground_temperature)
|
|
heating_load_ventilation_sensible = loads.get_heating_ventilation_load_sensible(heating_ambient_temperature)
|
|
heating_load_ventilation_latent = 0
|
|
heating_load = heating_load_transmitted + heating_load_ventilation_sensible + heating_load_ventilation_latent
|
|
|
|
cooling_load_transmitted = loads.get_cooling_transmitted_load(cooling_ambient_temperature, ground_temperature)
|
|
cooling_load_renovation_sensible = loads.get_cooling_ventilation_load_sensible(cooling_ambient_temperature)
|
|
cooling_load_internal_gains_sensible = loads.get_internal_load_sensible()
|
|
cooling_load_radiation = loads.get_radiation_load(self._irradiance_format, cooling_calculation_hour)
|
|
cooling_load_sensible = cooling_load_transmitted + cooling_load_renovation_sensible - cooling_load_radiation \
|
|
- cooling_load_internal_gains_sensible
|
|
|
|
cooling_load_latent = 0
|
|
cooling_load = cooling_load_sensible + cooling_load_latent
|
|
if heating_load < 0:
|
|
heating_load = 0
|
|
if cooling_load > 0:
|
|
cooling_load = 0
|
|
monthly_heating_loads.append(heating_load)
|
|
monthly_cooling_loads.append(cooling_load)
|
|
building. {'monthly heating peak load': monthly_heating_loads,
|
|
'monthly cooling peak load': monthly_cooling_loads}
|
|
|