Energy System rule-based sizing
SPDX - License - Identifier: LGPL - 3.0 - or -later
Copyright © 2023 Concordia CERC group
Project Coder Saeed Ranjbar saeed.ranjbar@concordia.ca
"""
import hub.helpers.constants as cte
class SystemSizing:
"""
The energy system sizing class
"""
def __init__(self, buildings):
self.buildings = buildings
def hvac_sizing(self):
for building in self.buildings:
peak_heating_demand = building.heating_peak_load[cte.YEAR][0] / 3600
peak_cooling_demand = building.cooling_peak_load[cte.YEAR][0] / 3600
if peak_heating_demand > peak_cooling_demand:
sizing_demand = peak_heating_demand
for system in building.energy_systems:
if 'Heating' in system.demand_types:
for generation in system.generation_systems:
if generation.system_type == 'Heat Pump':
if generation.source_medium == cte.AIR:
generation.source_temperature = building.external_temperature
generation.nominal_heat_output = 0.6 * sizing_demand / 1000
if generation.energy_storage_systems is not None:
for storage in generation.energy_storage_systems:
if storage.type_energy_stored == 'thermal':
storage.volume = building.heating_peak_load[cte.YEAR][0] / (cte.WATER_HEAT_CAPACITY*cte.WATER_DENSITY * 20)
elif generation.system_type == 'Boiler':
generation.nominal_heat_output = 0.4 * sizing_demand / 1000
else:
sizing_demand = peak_cooling_demand
for system in building.energy_systems:
if 'Cooling' in system.demand_types:
for generation in system.generation_systems:
if generation.system_type == 'Heat Pump':
generation.nominal_heat_output = sizing_demand / 1000
def montreal_custom(self):
for building in self.buildings:
energy_systems = building.energy_systems
for energy_system in energy_systems:
demand_types = energy_system.demand_types
generation_systems = energy_system.generation_systems
if cte.HEATING in demand_types:
if len(generation_systems) == 1:
for generation in generation_systems:
generation.nominal_heat_output = building.heating_peak_load[cte.YEAR][0] / 3600
else:
for generation in generation_systems:
generation.nominal_heat_output = building.heating_peak_load[cte.YEAR][0] / (len(generation_systems) * 3600)
elif cte.COOLING in demand_types:
if len(generation_systems) == 1:
for generation in generation_systems:
generation.nominal_cooling_output = building.cooling_peak_load[cte.YEAR][0] / 3600
else:
for generation in generation_systems:
generation.nominal_heat_output = building.cooling_peak_load[cte.YEAR][0] / (len(generation_systems) * 3600)